Changing microbial concentrations are associated with ventilation performance in Taiwan's air-conditioned office buildings

被引:60
|
作者
Wu, PC
Li, YY
Chiang, CM
Huang, CY
Lee, CC
Li, FC
Su, HJ
机构
[1] Natl Cheng Kung Univ, Coll Med, Dept Environm & Occupat Hlth, Tainan 70428, Taiwan
[2] Natl Cheng Kung Univ, Coll Design & Planning, Dept Architecture, Tainan 70101, Taiwan
关键词
microbes; fungi; bacteria; office building; ventilation; air change rate;
D O I
10.1111/j.1600-0668.2004.00313.x
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Our study conducted serial environmental measurements in 12 large office buildings with two different ventilation designs to obtain airborne microbial concentrations in typical office buildings, and to examine the effects of occupant density, ventilation type and air exchange efficiency on indoor microbial concentrations. Duplicate samples of airborne fungi and bacteria, a total of 2477 measurements, were collected based on a scheme of conducting sampling three times a day for at least seven consecutive days at every study building. Air change rates (ACHs) were also estimated by tracer gas concentration decay method, and measured by continuous Multi-Gas monitor for each building. Most sampling sites were with total fungal and bacteria concentrations higher than 1000 CFU/m(3), an often-quoted guideline in earlier research. Significantly higher concentrations of fungi and bacteria, as well as higher indoor/outdoor (I/O) ratios across most groups of airborne microbes, were identified in buildings with fan coil unit (FCU) system than those with air-handling unit (AHU) system (Student's t test, P < 0.0001). Older buildings and higher air exchange rates were statistically associated with greater indoor bacteria levels in FCU ventilated buildings (R-2 = 0.452); a pattern not found in AHU buildings. Increasing ACH seemed to be the determinant factor for rising indoor fungal and Cladosporium concentrations in those FCU buildings (R-2 = 0.346; 0.518). Our data indicated that FCU ventilated buildings might have provided more outdoor matters into indoor environments through direct penetration of outdoor air. Results also demonstrated a quantitative association between rising numbers of occupants and increasing indoor levels of yeast in both FCU and AHU ventilated buildings. The regression model identified in this study may be considered a reference value for proposing an optimal ACH, while with adequate filtration of fresh air, as an effective strategy in lowering indoor microbial concentrations in air-conditioned buildings.
引用
下载
收藏
页码:19 / 26
页数:8
相关论文
共 50 条
  • [31] The effectiveness of phase change materials in relation to summer thermal comfort in air-conditioned office buildings
    Vincenzo Costanzo
    Gianpiero Evola
    Luigi Marletta
    Francesco Nocera
    Building Simulation, 2018, 11 : 1145 - 1161
  • [32] Bacterial and Fungal Aerosols in Air-Conditioned Office Buildings in Warsaw, Poland-The Winter Season
    Golofit-Szymczak, Malgorzata
    Gorny, Rafal L.
    INTERNATIONAL JOURNAL OF OCCUPATIONAL SAFETY AND ERGONOMICS, 2010, 16 (04) : 465 - 476
  • [33] The effectiveness of phase change materials in relation to summer thermal comfort in air-conditioned office buildings
    Costanzo, Vincenzo
    Evola, Gianpiero
    Marletta, Luigi
    Nocera, Francesco
    BUILDING SIMULATION, 2018, 11 (06) : 1145 - 1161
  • [34] Thermal and Energy Performance of Pitch and Wall Insulation for Air-Conditioned Buildings in Malaysia
    Halim, Noor Hafizah Abdul
    Zakaria, Nor Zaini
    Ahmed, Azni Zain
    SUSTAINABLE CITIES DEVELOPMENT AND ENVIRONMENT, PTS 1-3, 2012, 209-211 : 1766 - 1769
  • [35] Envelope wall/roof thermal performance parameters for non air-conditioned buildings
    Barrios, G.
    Huelsz, G.
    Rojas, J.
    Ochoa, J. M.
    Marincic, I.
    ENERGY AND BUILDINGS, 2012, 50 : 120 - 127
  • [36] Impact of ventilation scenario on air exchange rates and on indoor particle number concentrations in an air-conditioned classroom
    Guo, H.
    Morawska, L.
    He, C.
    Gilbert, D.
    ATMOSPHERIC ENVIRONMENT, 2008, 42 (04) : 757 - 768
  • [37] An alternative approach for the performance rating of air-cooled chillers used in air-conditioned buildings
    Yu, F. W.
    Chan, K. T.
    BUILDING AND ENVIRONMENT, 2006, 41 (12) : 1723 - 1730
  • [38] Hybrid Ventilation in an Air-Conditioned Office Building with a Multistory Atrium for Thermal Comfort: A Practical Case Study
    Hsu, Hao-Hsiang
    Chiang, Wei-Hwa
    Huang, Jian-Sheng
    BUILDINGS, 2021, 11 (12)
  • [39] Energy performance of air-conditioned buildings based on short-term weather forecast
    Ignjatovic, Marko G.
    Blagojevic, Bratislav D.
    Stojiljkovic, Mirko M.
    Andelkovic, Aleksandar S.
    Blagojevic, Milena B.
    Mitrovic, Dejan M.
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2022, 28 (01) : 55 - 72
  • [40] Thermal performance of non air-conditioned buildings with vaulted roofs in comparison with flat roofs
    Tang, RS
    Meir, IA
    Wu, T
    BUILDING AND ENVIRONMENT, 2006, 41 (03) : 268 - 276