Thermal interference of adjacent legs in a vertical U-tube heat exchanger for a ground-coupled heat pump

被引:0
|
作者
Muraya, NK
ONeal, DL
Heffington, WM
机构
来源
关键词
D O I
暂无
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
A transient finite-element model of the heat transfer around a vertical U-tube heat exchanger for a ground-coupled heat pump was developed to study the thermal interference that occurs between the adjacent legs of the U-tube. Parametric studies examined performance on two-dimensional horizontal cross sections as a function of soil properties (temperature, thermal conductivity, and diffusivity), separation distance of the legs, diameter of the tubes, and imposed wall surface temperatures. Thermal interference was quantified by defining a heat exchanger effectiveness. This value was the ratio of the heat transfer form the two legs of the U-tube in the heat exchanger to the heat transfer from the two legs if they were each in an infinite medium. The impacts of separation distance, leg temperatures, different ambient soil temperatures, and backfills were all investigated. The effectiveness had to be modified to account properly for backfills. Results with different source and ambient temperatures were nondimensionalized into a single plot. Effectiveness results were most sensitive to separation distance and backfill thermal conductivity.
引用
收藏
页码:12 / 21
页数:10
相关论文
共 50 条
  • [1] Research on Hydraulic Characteristics of U-Tube Heat Exchanger Loop in Ground-Coupled Heat Pump System
    Song, Wei
    Yang, Jiaming
    Zheng, Changjin
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 3186 - 3193
  • [2] Simulation and experimental analysis of optimal buried depth of the vertical U-tube ground heat exchanger for a ground-coupled heat pump system
    Chen, Jinhua
    Xia, Lei
    Li, Baizhan
    Mmereki, Daniel
    RENEWABLE ENERGY, 2015, 73 : 46 - 54
  • [3] Numerical Analysis of the Heat Transfer Characteristics of Vertical U-Tube Ground Heat Exchanger Used in Ground Coupled Heat Pump
    Yang, Weibo
    Shi, Mingheng
    Chen, Zhenqian
    6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 1857 - 1864
  • [4] Heating system with vapour compressor heat pump and vertical U-tube ground heat exchanger
    Hanuszkiewicz-Drapala, Malgorzata
    Skladzien, Jan
    ARCHIVES OF THERMODYNAMICS, 2010, 31 (04) : 93 - 110
  • [5] A new solution for thermal interference of vertical U-tube ground heat exchanger for cold area in China
    Li, Xiao-Yan
    Li, Tian-Yang
    Qu, Dong-Qi
    Yu, Jia-Wen
    GEOTHERMICS, 2017, 65 : 72 - 80
  • [6] A NUMERICAL MODEL FOR THE SIMULATION OF A VERTICAL U-BEND GROUND HEAT EXCHANGER USED IN A GROUND-COUPLED HEAT PUMP
    Yang, Weibo
    Liang, Xingfu
    Shi, Mingheng
    Chen, Zhenqian
    INTERNATIONAL JOURNAL OF GREEN ENERGY, 2014, 11 (07) : 761 - 785
  • [7] Thermal performance of the vertical ground heat exchanger with a novel elliptical single U-tube
    Jahanbin, Aminhossein
    GEOTHERMICS, 2020, 86
  • [8] New Correlations for Thermal Resistances of Vertical Single U-Tube Ground Heat Exchanger
    Liao, Quan
    Zhou, Chao
    Cui, Wenzhi
    Jen, T.C.
    Journal of Thermal Science and Engineering Applications, 2012, 4 (03)
  • [9] New global thermal numerical model of vertical U-tube ground heat exchanger
    Chwieduk, Michal
    RENEWABLE ENERGY, 2021, 168 : 343 - 352
  • [10] Comparison of vertical U-tube ground heat exchanger thermal resistance calculation methods
    Chen, Chao
    Wang, Yong-Fei
    Ren, Yan
    Chen, Jiang
    Han, Yun-Quan
    Wang, Chun-Xue
    Hunan Daxue Xuebao/Journal of Hunan University Natural Sciences, 2009, 36 (SUPPL. 2): : 58 - 62