A NUMERICAL MODEL FOR THE SIMULATION OF A VERTICAL U-BEND GROUND HEAT EXCHANGER USED IN A GROUND-COUPLED HEAT PUMP

被引:16
|
作者
Yang, Weibo [1 ]
Liang, Xingfu [1 ]
Shi, Mingheng [2 ]
Chen, Zhenqian [2 ]
机构
[1] Yangzhou Univ, Sch Energy & Power Engn, Yangzhou 225127, Peoples R China
[2] Southeast Univ, Sch Energy & Environm, Nanjing, Jiangsu, Peoples R China
关键词
Ground-coupled heat pump (GCHP); Ground heat exchanger (GHE); Numerical model; Groundwater advection; Experimental validation; PERFORMANCE;
D O I
10.1080/15435075.2013.829474
中图分类号
O414.1 [热力学];
学科分类号
摘要
Heat transfer between the ground heat exchanger (GHE) and surrounding soil is a common problem for the optimum design and simulation of ground-coupled heat pump (GCHP). In this article, a quasi-three-dimensional numerical model of vertical U-bend GHE was proposed and developed by coupling the one-dimensional model of fluid in the depth direction with the two-dimensional heat transfer model of soil in the level direction but considering the soil temperature variation along depth. In the model, the soil in depth direction was divided into saturated and unsaturated regions by water table, and the influence of groundwater advection on the heat transfer performance of GHE was considered for the saturated soil region. Based on the model, the variations of heat rejection and fluid outlet temperature of GHE with time were discussed, and the influences of soil thermal properties and groundwater advection on the heat transfer performance of GHE were analyzed. The results show that the heat rejection in cooling mode will decrease with time, and an intermittent heat rejection mode can improve the heat transfer performance. Meanwhile, the increases of soil thermal conductivity and heat capacity can all enhance the heat transfer characteristics, and the exist of groundwater advection can improve the heat exchange between the GHE and surrounding soil. Furthermore, an experimental validation was performed in a solar-geothermal multifunctional heat pump experiment system. The results indicate the predicted values of heat rejection rate of GHE are agreed well with the corresponding measured data, and the guess average relative error for the daily heat rejection is about 5.5%. This means the numerical model proposed in this article is feasible and thus can be used to simulate the heat transfer of GHE.
引用
收藏
页码:761 / 785
页数:25
相关论文
共 50 条
  • [1] Numerical simulation and experimental verification on heat transfer process of a vertical U-bend ground heat exchanger
    Yang, W. B.
    Liu, G. Y.
    Shi, M. H.
    Chen, Z. Q.
    [J]. CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 780 - 784
  • [2] Numerical Analysis of the Heat Transfer Characteristics of Vertical U-Tube Ground Heat Exchanger Used in Ground Coupled Heat Pump
    Yang, Weibo
    Shi, Mingheng
    Chen, Zhenqian
    [J]. 6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 1857 - 1864
  • [3] Simulation and experimental analysis of optimal buried depth of the vertical U-tube ground heat exchanger for a ground-coupled heat pump system
    Chen, Jinhua
    Xia, Lei
    Li, Baizhan
    Mmereki, Daniel
    [J]. RENEWABLE ENERGY, 2015, 73 : 46 - 54
  • [4] Thermal interference of adjacent legs in a vertical U-tube heat exchanger for a ground-coupled heat pump
    Muraya, NK
    ONeal, DL
    Heffington, WM
    [J]. ASHRAE TRANSACTIONS 1996, VOL 102, PT 2, 1996, 102 : 12 - 21
  • [5] Numerical Simulation of Soil Temperature Field Surrounding Vertical U Tube Heat Exchanger for Ground Coupled Heat Pump
    Bai, Tian
    Zhang, Jianli
    Zheng, Maoyu
    Zhang, Hui
    He, Maoting
    [J]. PROCEEDINGS OF THE SECOND INTERNATIONAL CONFERENCE ON MODELLING AND SIMULATION (ICMS2009), VOL 3, 2009, : 275 - 280
  • [6] Optimization and Analysis of a Vertical Ground-Coupled Heat Pump
    Kord, Ali Siavoshi
    Jazayeri, Seyed Ali
    [J]. INTERNATIONAL JOURNAL OF RENEWABLE ENERGY RESEARCH, 2012, 2 (01): : 33 - 37
  • [7] Numerical simulation of a ground-coupled heat pump system with vertical plate heat exchangers: A comprehensive parametric study
    Amadeh, Ali
    Habibi, Mohammad
    Hakkaki-Fard, Ali
    [J]. Geothermics, 2020, 88
  • [8] Numerical simulation of a ground-coupled heat pump system with vertical plate heat exchangers: A comprehensive parametric study
    Amadeh, Ali
    Habibi, Mohammad
    Hakkaki-Fard, Ali
    [J]. GEOTHERMICS, 2020, 88
  • [9] Hourly simulation of a Ground-Coupled Heat Pump system
    Naldi, C.
    Zanchini, E.
    [J]. 34TH UIT HEAT TRANSFER CONFERENCE 2016, 2017, 796
  • [10] Research on Hydraulic Characteristics of U-Tube Heat Exchanger Loop in Ground-Coupled Heat Pump System
    Song, Wei
    Yang, Jiaming
    Zheng, Changjin
    [J]. 10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 3186 - 3193