Investigation on the Energy Saving Potential of Using a Novel Dew Point Cooling System in Data Centres

被引:11
|
作者
Bi, Yin [1 ,2 ]
Wang, Yugang [1 ,3 ]
Ma, Xiaoli [1 ]
Zhao, Xudong [1 ]
机构
[1] Univ Hull, Sch Engn & Comp Sci, Kingston Upon Hull HU6 7RX, Yorks, England
[2] Guangdong Univ Technol, Sch Civil & Transportat Engn, Guangzhou 510006, Guangdong, Peoples R China
[3] Jimei Univ, Sch Mech & Energy Engn, Xiamen 361021, Peoples R China
来源
ENERGIES | 2017年 / 10卷 / 11期
基金
欧盟地平线“2020”; 英国工程与自然科学研究理事会;
关键词
dew point cooling; data centres; energy saving; energy usage effectiveness; cooling load; INDIRECT EVAPORATIVE COOLER; COUNTER-FLOW; HEAT-EXCHANGERS; PERFORMANCE; OPTIMIZATION; CONSERVATION;
D O I
10.3390/en10111732
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Information technology (IT) has brought significant changes in people's lives. As an important part of the IT industry, data centres (DCs) have been rapidly growing in both the number and size over the past 40 years. Around 30% to 40% of electricity consumption in DCs is used for space cooling, thus leading to very inefficient DC operation. To identify ways to reduce the energy consumption for space cooling and increase the energy efficiency of DCs' operation, a dedicated investigation into the energy usage in DCs has been undertaken and a novel high performance dew point cooling system was introduced into a DC operational scheme. Based on the cooling load in DCs, a case study was carried out to evaluate the energy consumptions and energy usage effectiveness when using the novel dew point cooling system in different scales of DCs in various climates. It was found that by using the novel dew point cooling system, for 10 typical climates a DC can have a much lower power usage effectiveness (PUE) of 1.10 to 1.22 compared to that of 1.7 to 3.7 by using existing traditional cooling systems, leading to significantly increased energy efficiency of the DC operation. In addition, the energy performance by managing the cooling air supply at the different levels in DCs, i.e., room, row and rack level, was simulated by using a dynamic computer model. It was found that cooling air supply at rack level can provide a higher energy efficiency in DCs. Based on the above work, the energy saving potential in DCs was conducted by comparing DCs using an the novel dew point cooling system and the optimum management scheme for the cooling air supply to that using traditional air cooling systems and the same supply air management. Annual electricity consumptions for the two cases were given. It was found that by using the novel dew point cooling system and optimum management system for the cooling air supply, an 87.7-91.6% electricity consumption saving for space cooling in DCs could be achieved in 10 typical cities at 10 selected climatic conditions.
引用
收藏
页数:21
相关论文
共 50 条
  • [11] Using data centres for combined heating and cooling: An investigation for London
    Davies, G. F.
    Maidment, G. G.
    Tozer, R. M.
    APPLIED THERMAL ENGINEERING, 2016, 94 : 296 - 304
  • [12] Investigation of Energy Saving Potential in Buildings Using Novel Developed Lightweight Concrete
    Ahmet Erhan Akan
    Fatih Ünal
    Fatih Koçyiğit
    International Journal of Thermophysics, 2021, 42
  • [13] Investigation of Energy Saving Potential in Buildings Using Novel Developed Lightweight Concrete
    Akan, Ahmet Erhan
    unal, Fatih
    Kocyigit, Fatih
    INTERNATIONAL JOURNAL OF THERMOPHYSICS, 2020, 42 (01)
  • [14] Investigation of Energy Saving Potential in Buildings Using Novel Developed Lightweight Concrete
    Akan, Ahmet Erhan
    Ünal, Fatih
    Koçyiğit, Fatih
    International Journal of Thermophysics, 2021, 42 (01)
  • [15] Study on Energy Saving Potential of Radiant Cooling System in China
    Yin Xinglei
    Tian Zhe
    Liu Kuixing
    Li Feng
    MATERIALS SCIENCE AND INFORMATION TECHNOLOGY, PTS 1-8, 2012, 433-440 : 1458 - 1464
  • [16] Investigation of dew point evaporative cooling with vacuum membrane dehumidification
    Lin, Jie
    Duc Thuan Bui
    Wang, Ruzhu
    Chua, Kian Jon
    PROCEEDINGS OF THE 9TH INTERNATIONAL CONFERENCE ON APPLIED ENERGY, 2017, 142 : 3851 - 3856
  • [17] Energy Saving Analysis of Free Cooling System in the Data Center
    Yang, Yong
    Wang, Bo
    Zhou, Qinbin
    10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 1815 - 1819
  • [18] Energy saving potential of using heat pipes for CPU cooling
    Wang, Yabo
    Wang, Bin
    Zhu, Kai
    Li, Hailong
    He, Wei
    Liu, Shengchun
    APPLIED THERMAL ENGINEERING, 2018, 143 : 630 - 638
  • [19] A 'System' Integration for Energy Recovery within Data Centres Using Combined Cooling and Power Technology
    Luo, Y.
    Andresen, J.
    Clarke, H.
    Rajendra, M.
    Maroto-Valer, M.
    15TH GLOBAL CONFERENCE ON SUSTAINABLE MANUFACTURING, 2018, 21 : 710 - 716
  • [20] Feasibility investigation on a novel rack-level cooling system for energy-saving retrofit of medium-and-small data centers
    Li, Xiuming
    Zhang, Ce
    Dong, Jiaxiang
    Han, Zongwei
    Wang, Shengwei
    APPLIED THERMAL ENGINEERING, 2023, 229