Investigation on the Energy Saving Potential of Using a Novel Dew Point Cooling System in Data Centres

被引:11
|
作者
Bi, Yin [1 ,2 ]
Wang, Yugang [1 ,3 ]
Ma, Xiaoli [1 ]
Zhao, Xudong [1 ]
机构
[1] Univ Hull, Sch Engn & Comp Sci, Kingston Upon Hull HU6 7RX, Yorks, England
[2] Guangdong Univ Technol, Sch Civil & Transportat Engn, Guangzhou 510006, Guangdong, Peoples R China
[3] Jimei Univ, Sch Mech & Energy Engn, Xiamen 361021, Peoples R China
来源
ENERGIES | 2017年 / 10卷 / 11期
基金
欧盟地平线“2020”; 英国工程与自然科学研究理事会;
关键词
dew point cooling; data centres; energy saving; energy usage effectiveness; cooling load; INDIRECT EVAPORATIVE COOLER; COUNTER-FLOW; HEAT-EXCHANGERS; PERFORMANCE; OPTIMIZATION; CONSERVATION;
D O I
10.3390/en10111732
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Information technology (IT) has brought significant changes in people's lives. As an important part of the IT industry, data centres (DCs) have been rapidly growing in both the number and size over the past 40 years. Around 30% to 40% of electricity consumption in DCs is used for space cooling, thus leading to very inefficient DC operation. To identify ways to reduce the energy consumption for space cooling and increase the energy efficiency of DCs' operation, a dedicated investigation into the energy usage in DCs has been undertaken and a novel high performance dew point cooling system was introduced into a DC operational scheme. Based on the cooling load in DCs, a case study was carried out to evaluate the energy consumptions and energy usage effectiveness when using the novel dew point cooling system in different scales of DCs in various climates. It was found that by using the novel dew point cooling system, for 10 typical climates a DC can have a much lower power usage effectiveness (PUE) of 1.10 to 1.22 compared to that of 1.7 to 3.7 by using existing traditional cooling systems, leading to significantly increased energy efficiency of the DC operation. In addition, the energy performance by managing the cooling air supply at the different levels in DCs, i.e., room, row and rack level, was simulated by using a dynamic computer model. It was found that cooling air supply at rack level can provide a higher energy efficiency in DCs. Based on the above work, the energy saving potential in DCs was conducted by comparing DCs using an the novel dew point cooling system and the optimum management scheme for the cooling air supply to that using traditional air cooling systems and the same supply air management. Annual electricity consumptions for the two cases were given. It was found that by using the novel dew point cooling system and optimum management system for the cooling air supply, an 87.7-91.6% electricity consumption saving for space cooling in DCs could be achieved in 10 typical cities at 10 selected climatic conditions.
引用
收藏
页数:21
相关论文
共 50 条
  • [41] Energy saving analysis of evaporative cooling composite air conditioning system for data centers
    Han, Zongwei
    Sun, Xiaoqing
    Wei, Haotian
    Ji, Qiang
    Xue, Da
    APPLIED THERMAL ENGINEERING, 2021, 186
  • [42] Hybrid Desiccant Cooling System Using Condensing Heat as the Regeneration Source. Part II: Energy Saving Potential
    Han Xing
    Zhang Xu
    MANUFACTURING SCIENCE AND TECHNOLOGY, PTS 1-8, 2012, 383-390 : 6431 - 6435
  • [43] Operating energy savings in a liquid desiccant and dew point evaporative cooling-assisted 100% outdoor air system
    Ham, Sang-Woo
    Lee, Sung-Joon
    Jeong, Jae-Weon
    ENERGY AND BUILDINGS, 2016, 116 : 535 - 552
  • [44] Numerical investigation of the energy performance of a guideless irregular heat and mass exchanger with corrugated heat transfer surface for dew point cooling
    Xu, Peng
    Ma, Xiaoli
    Diallo, Thierno M. O.
    Zhao, Xudong
    Fancey, Kevin
    Li, Deying
    Chen, Hongbing
    ENERGY, 2016, 109 : 803 - 817
  • [45] Energy Saving Performance of Distributed Heating and Cooling System
    Endo, Naoki
    Maeda, Tetsuhiko
    Hasegawa, Yasuo
    ELECTRICAL ENGINEERING IN JAPAN, 2011, 174 (02) : 46 - 53
  • [46] Novel battery thermal management via scalable dew-point evaporative cooling
    Lin, Jie
    Chu, Howie N.
    Thu, Kyaw
    Wojtala, Malgorzata
    Gao, Fei
    Chua, Kian Jon
    ENERGY CONVERSION AND MANAGEMENT, 2023, 283
  • [47] Research on thermodynamic performance of a novel building cooling system integrating dew point evaporative cooling, air-carrying energy radiant air conditioning and vacuum membrane-based dehumidification (DAV-cooling system)
    Chun, Liang
    Gong, Guangcai
    Peng, Pei
    Wan, Yangda
    Chua, Kian Jon
    Fang, Xi
    Li, Wenqiang
    ENERGY CONVERSION AND MANAGEMENT, 2021, 245
  • [48] Comparative investigation of energy-saving potential and technical economy of rooftop radiative cooling and photovoltaic systems
    Li, Hao
    Zhang, Ji
    Liu, Xiaohua
    Zhang, Tao
    APPLIED ENERGY, 2022, 328
  • [49] PRIMARY ENERGY SAVING POTENTIAL OF SOLAR COOLING IN RESIDENTIAL BUILDINGS
    Lopez, Jose Urena
    Klesse, Andreas
    Wagner, Hermann-J.
    PROCEEDINGS OF THE ASME 5TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY 2011, PTS A-C, 2012, : 285 - 290
  • [50] Energy Saving Potential of Low-Temperature Cooling of Computers
    Khalifa, H. Ezzat
    Erden, Hamza Salih
    de Rouge, Romain B.
    2014 IEEE INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS (ITHERM), 2014, : 1121 - 1128