Modelling and comparison analysis of grid-connected DFIG-based wind farm in weak grid

被引:9
|
作者
Yan, Cai [1 ]
Yao, Wei [1 ]
Wen, Jianfeng [1 ]
Fang, Jiakun [1 ]
Ai, Xiaomeng [1 ]
Wen, Jinyu [1 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Elect & Elect Engn, State Key Lab Adv Electromagnet Engn & Technol, Wuhan 430074, Peoples R China
关键词
stators; power generation control; wind power plants; rotors; asynchronous generators; shafts; eigenvalues and eigenfunctions; phase locked loops; grid-connected DFIG-based wind farm; weak grid; modelling comparison analysis; grid-connected double-fed induction generator; linear system analysis; PLL dynamics; eigenvalue analysis; FED INDUCTION GENERATOR; STABILITY ANALYSIS; IMPEDANCE-MODEL; DAMPING CONTROL; CONVERTERS; TURBINES;
D O I
10.1049/iet-rpg.2019.1382
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study proposes a generic method for modelling and comparison analysis of grid-connected double-fed induction generator (DFIG)-based wind farms in a weak grid. A detailed model of DFIG in a weak grid is established and used as a benchmark. Specifically, the detailed model consists of the mechanical part, generator part, rotor side converter, and phase-locked loop (PLL). Two simplified models of grid-connected DFIG-based wind farms in a weak grid are compared with the detailed model to investigate the mechanism of sub-synchronous oscillation (SSO) as well as the influential factors through linear system analysis. The first simplified model ignores shafting dynamics, stator flux dynamics, and PLL dynamics. The same assumptions are used in the latter, except that PLL dynamics are considered. Time-domain simulation and eigenvalue analysis are used to verify the accuracy of the simplified models. The block diagrams of the linearised system are derived based on the proposed model, and the oscillation mechanism is explained by linear system analysis. Through eigenvalue analysis and the root locus method, the influences of the parameters of the DFIG and its controllers on the system stability are identified and analysed.
引用
收藏
页码:2406 / 2415
页数:10
相关论文
共 50 条
  • [1] Analysis of Influencing Factors on Transient Voltage Stability of a Grid-connected DFIG-based Wind Farm
    Li, Sheng
    Ma, Ya-nan
    Cheng, Jie-lei
    Gong, Tian-tian
    Wang, Cheng
    2ND INTERNATIONAL CONFERENCE ON ENERGY AND POWER ENGINEERING (EPE 2018), 2018, : 212 - 216
  • [2] Stability Analysis for DFIG-Based Wind Farm Grid-Connected System Under All Wind Speed Conditions
    Du, Chengmao
    Du, Xiong
    Tong, Chenghui
    Li, Ying
    Zhou, Peipeng
    IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, 2023, 59 (02) : 2430 - 2445
  • [3] Impedance Modeling and Stability Analysis of Grid-Connected DFIG-Based Wind Farm With a VSC-HVDC
    Sun, Kun
    Yao, Wei
    Fang, Jiakun
    Ai, Xiaomeng
    Wen, Jinyu
    Cheng, Shijie
    IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2020, 8 (02) : 1375 - 1390
  • [4] Virtual Synchronous Control for Grid-Connected DFIG-Based Wind Turbines
    Wang, Shuo
    Hu, Jiabing
    Yuan, Xiaoming
    IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2015, 3 (04) : 932 - 944
  • [5] Virtual Synchronous Control of Grid-Connected DFIG-based Wind Turbines
    Zhao, Yangyang
    Chai, Jianyun
    Sun, Xudong
    2015 THIRTIETH ANNUAL IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION (APEC 2015), 2015, : 2980 - 2983
  • [6] Maximum Power Control of Grid-connected DFIG-Based Wind Systems
    Sylla, Abdoulaye Mamadie
    Doumbia, Mamadou Lamine
    2012 IEEE ELECTRICAL POWER AND ENERGY CONFERENCE (EPEC), 2012, : 267 - 273
  • [7] Stability Augmentation of a Grid-Connected Wind Farm by Fuzzy-Logic-Controlled DFIG-Based Wind Turbines
    Hazari, Md. Rifat
    Mannan, Mohammad Abdul
    Muyeen, S. M.
    Umemura, Atsushi
    Takahashi, Rion
    Tamura, Junji
    APPLIED SCIENCES-BASEL, 2018, 8 (01):
  • [8] Dynamic Stability Analysis of the Weak Grid-Connected DFIG-based Wind Turbines under Severe Symmetrical Faults
    Liu, Ruikuo
    Yao, Jun
    Pei, Jinxin
    Wang, Xuewei
    Sun, Peng
    Guo, Xiaolong
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 1512 - 1517
  • [9] Experimental investigation of grid-connected operations for DFIG-based wind turbines with asymmetrical grid faults
    Zheng, Zhong
    Yang, Geng
    Geng, Hua
    Qinghua Daxue Xuebao/Journal of Tsinghua University, 2013, 53 (07): : 1036 - 1040
  • [10] Sub-synchronous resonance analysis of grid-connected DFIG-based wind farms
    Su, Jun-Lin
    Shi, Li-Bao
    Yao, Liang-Zhong
    Ni, Yi-Xin
    Qin, Shi-Yao
    Wang, Rui-Ming
    Zhang, Jin-Ping
    2014 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2014,