Synchrophasors-Based Transmission Line Protection in the Presence of STATCOM

被引:7
|
作者
Ghorbani A. [1 ]
Ghorbani M. [2 ]
Ebrahimi S.Y. [3 ]
机构
[1] Department of Electrical Engineering, Abhar Branch, Islamic Azad University, Abhar
[2] Department of Electrical, Biomedical and Mechatronics Engineering, Qazvin Branch, Islamic Azad University, Qazvin
[3] Department of Electrical Engineering, Hidaj Branch, Islamic Azad University, Hidaj
关键词
Flexible AC transmission system (FACTS) controllers; Ground distance relay; Phasor measurement units (PMUs); Static synchronous compensator (STATCOM);
D O I
10.1007/s40313-016-0288-5
中图分类号
学科分类号
摘要
Distance relay identifies the type and location of fault by measuring the transmission line impedance. However, any other factors that cause miscalculating the measured impedance make the relay detect the fault in incorrect location or do not detect the fault at all. One of the important factors which directly increases the measured impedance by the relay is fault resistance. Another factor that indirectly changes the impedance of the transmission line is static synchronous compensator (STATCOM). When a fault occurs, measured signals by the relay change due to the variation of current injected by the STATCOM and it makes the calculated impedance to be incorrect. This paper provides a method based on the combination of distance and differential protection. At first, faulty transmission line is detected according to the current data of buses. After that the fault location is calculated using the proposed algorithm on the transmission line. This algorithm is based on active power calculation of the buses. Fault resistance is calculated from the active powers, and its effect will be deducted from calculated impedance by the algorithm. Furthermore, by choosing the appropriate data bus, the effect of STATCOM is eliminated and fault location will be detected. © 2016, Brazilian Society for Automatics--SBA.
引用
下载
收藏
页码:147 / 157
页数:10
相关论文
共 50 条
  • [21] Modified Distance Protection in Presence of SSSC on a Transmission Line
    Jamali, S.
    Kazemi, A.
    Shateri, H.
    2009 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-8, 2009, : 1189 - 1196
  • [22] Modified Transmission Line Protection Scheme in the Presence of SCC
    Naeini, Ehsan Mostaghimi
    Vaseghi, Behrouz
    Mahdavian, Mehdi
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2017, 12 (02) : 533 - 540
  • [23] Adaptive distance protection of transmission line in presence of SVC
    Singh, Arvind R.
    Dambhare, Sanjay S.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2013, 53 : 78 - 84
  • [24] FDST BASED STATCOM COMPENSATED SINGLE CIRCUIT TRANSMISSION LINE
    Mishra, S. K.
    Tripathy, L. N.
    Swain, S. C.
    PROCEEDINGS OF 2ND INTERNATIONAL CONFERENCE ON 2017 DEVICES FOR INTEGRATED CIRCUIT (DEVIC), 2017, : 756 - 760
  • [25] Secure Remote Backup Protection of Transmission Lines Using Synchrophasors
    Navalkar, Prashant V.
    Soman, Shreevardhan A.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (01) : 87 - 96
  • [26] DWT approach based differential relaying scheme for single circuit and double circuit transmission line protection including STATCOM
    Mishra, S. K.
    Tripathy, L. N.
    Swain, S. C.
    AIN SHAMS ENGINEERING JOURNAL, 2019, 10 (01) : 93 - 102
  • [27] Automated Failure Diagnosis in Transmission Network Protection System Using Synchrophasors
    Cui, B.
    Srivastava, A. K.
    Banerjee, P.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2018, 33 (05) : 2207 - 2216
  • [28] Faulty phase selection of transmission line with STATCOM
    Zhu, Gaole
    Liu, Qing
    Dianwang Jishu/Power System Technology, 2014, 38 (12): : 3535 - 3540
  • [29] Relaying Scheme for STATCOM Compensated Transmission Line
    Gupta, Om Hari
    Tripathy, Manoj
    2016 IEEE 6TH INTERNATIONAL CONFERENCE ON POWER SYSTEMS (ICPS), 2016,
  • [30] Fuzzy-Wavelet Based Double Line Transmission System Protection Scheme in the Presence of SVC
    Goli R.
    Shaik A.G.
    Tulasi Ram S.S.
    Journal of The Institution of Engineers (India): Series B, 2015, 96 (2) : 131 - 140