Accurate one-end fault location for overhead transmission lines in interconnected power systems

被引:23
|
作者
Eisa, Amir A. A. [1 ]
Ramar, K. [1 ]
机构
[1] Multimedia Univ, Fac Engn, Cyberjaya 63100, Malaysia
关键词
Fault location; Transmission lines; Distributed parameters; One-end measurements; ALGORITHM;
D O I
10.1016/j.ijepes.2009.11.005
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a new one-end fault location method for overhead transmission lines embedded in a general n-bus interconnected power system. High accuracy in fault location is achieved by using both an accurate distributed parameters model for the faulted transmission line, and a two-bus Thevenin equivalent network model for the power system that accurately accounts for its interconnectivity. The method has been tested using transient fault data obtained from PSCAD/EMTDC simulations of an 11-bus interconnected power system. The results obtained indicate that the method is capable of estimating the fault distance with high accuracy for various fault conditions. They also indicate that method is sensitive to errors in the value of the local bus impedance, but is insensitive to errors in the value of the remote bus impedance. (C) 2009 Elsevier Ltd. All rights reserved.
引用
收藏
页码:383 / 389
页数:7
相关论文
共 50 条