A current-based algorithm for one-end fault location in series capacitor compensated double-circuit transmission lines

被引:2
|
作者
Taheri, Reyhaneh [1 ]
Eslami, Mahdiyeh [1 ,3 ]
Damchi, Yaser [2 ]
机构
[1] Islamic Azad Univ, Dept Elect Engn, Kerman Branch, Kerman, Iran
[2] Shahrood Univ Technol, Fac Elect Engn, Shahrood, Iran
[3] Islamic Azad Univ, Dept Elect Engn, Kerman Branch, POB 7635131167, Kerman, Iran
关键词
Fault location algorithm (FLA); Series capacitor compensated double -circuit; transmission line (SCCDCTL); MOV; Zero -sequence mutual coupling impedance; (ZSMCI); Negative and zero -sequence currents; IMPEDANCE; PROTECTION; ANGLE;
D O I
10.1016/j.compeleceng.2023.108618
中图分类号
TP3 [计算技术、计算机技术];
学科分类号
0812 ;
摘要
Fault location is essential in series capacitor compensated double-circuit transmission lines regarding their capacity in transferring large amounts of power. The main challenge in the fault location of these lines is the nonlinear behavior of the metal-oxide varistor (MOV) in protecting the series capacitor against overvoltage during faults. In this paper, considering the MOV model and zero-sequence mutual coupling impedance between the two circuits, a new algorithm is presented for the location of single-line-to-ground faults, using currents measured at one end of the line. In this algorithm, first, a fault location is obtained for each data window, and then the exact location is calculated using statistical techniques. The proposed algorithm is independent of the measured voltages, and as a result, no error in the voltage measurement affects its accuracy. In addition, needing no telecommunication channel to access the data of the remote substation leads to reliability increasing and cost reductions. Not requiring pre-fault data is another advantage of the algorithm. The results indicate that the algorithm is independent of fault location and resistance, fault occurrence time, load conditions, and compensation level. In addition, the fault location error in all scenarios is within the standard range.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Single-end current-based algorithm for fault location in series capacitor compensated transmission lines
    Taheri, Reyhaneh
    Eslami, Mahdiyeh
    Damchi, Yaser
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2020, 123
  • [2] One-end impedance based fault location in double-circuit transmission lines with different configurations
    Ramar, K.
    Low, H. S.
    Ngu, E. E.
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 64 : 1159 - 1165
  • [3] Two-End Unsynchronized Fault Location Algorithm for Double-Circuit Series Compensated Lines
    Fulczyk, Marek
    Balcerek, Przemyslaw
    Izykowski, Jan
    Rosolowski, Eugeniusz
    Saha, Murari Mohan
    [J]. 2008 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-11, 2008, : 1641 - +
  • [4] A New Fault-Location Algorithm for Series-Compensated Double-Circuit Transmission Lines Based on the Distributed Parameter Model
    Zhang, Ying
    Liang, Jun
    Yun, Zhihao
    Dong, Xiaoming
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2017, 32 (06) : 2398 - 2407
  • [5] New Fault-Location Algorithm for Series-Compensated Double-Circuit Transmission Line
    Cai, Daiying
    Zhang, Jun
    [J]. IEEE ACCESS, 2020, 8 : 210685 - 210694
  • [6] A Fault Location Algorithm for Two-End Series-Compensated Double-Circuit Transmission Lines Using the Distributed Parameter Line Model
    Kang, Ning
    Gombos, Gergely
    Mousavi, Mirrasoul J.
    Feng, Xiaoming
    [J]. ELECTRIC POWER COMPONENTS AND SYSTEMS, 2017, 45 (06) : 615 - 623
  • [7] A Fault-Location Algorithm for Series-Compensated Double-Circuit Transmission Lines Using the Distributed Parameter Line Model
    Kang, Ning
    Chen, Jiaxiong
    Liao, Yuan
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2015, 30 (01) : 360 - 367
  • [8] Fault Location on Double-Circuit Series-Compensated Lines Using Two-End Unsynchronized Measurements
    Izykowski, Jan
    Rosolowski, Eugeniusz
    Balcerek, Przemyslaw
    Fulczyk, Marek
    Saha, Murari Mohan
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) : 2072 - 2080
  • [9] One-end fault location method for untransposed four-circuit transmission lines
    Ngu, E. E.
    Ramar, K.
    Eisa, Amir
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2012, 43 (01) : 660 - 669
  • [10] Accurate fault location algorithm for double-circuit series compensated lines using a limited number of two-end synchronized measurements