One-end fault location method for untransposed four-circuit transmission lines

被引:15
|
作者
Ngu, E. E. [1 ]
Ramar, K. [1 ]
Eisa, Amir [2 ]
机构
[1] Multimedia Univ Malaysia, Fac Engn, Cyberjaya 63100, Malaysia
[2] Sudan Univ Sci & Technol, Khartoum, Sudan
关键词
Distributed parameters; Fault location; One-end method; Four-circuits; Transmission line; ALGORITHM; PROTECTION;
D O I
10.1016/j.ijepes.2012.06.033
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a fault location method suitable for untransposed four-circuit parallel transmission lines using the data available at one end of the line. The proposed method employs an accurate distributed parameter line model that fully accounts for mutual coupling between all the lines and shunt capacitance effects. The fault location algorithms are developed in phase-components, one for the case where the fault is in any one of the circuits, the second for the case where the fault involves any two circuits and the third for the case where the fault involves more than two circuits. The proposed method is tested using the transient data obtained by simulating a 500-kV four-circuit overhead transmission line under different fault conditions. The simulations are done using the software "DIgSILENT PoweFactory". Results obtained indicate that the method is capable of estimating the fault distance with high accuracy for various fault conditions. Also the robustness of the fault location method is investigated. (C) 2012 Elsevier Ltd. All rights reserved.