Performance analysis of an earth-to-air heat exchanger assisted by a wind tower for passive cooling of buildings in arid and hot climate

被引:76
|
作者
Benhammou, M. [1 ]
Draoui, B. [1 ]
Zerrouki, M. [1 ]
Marif, Y. [1 ]
机构
[1] Ctr Dev Energies Renouvelables, Div Convers Therm & Thermodynam, Unite Rech Energies Renouvelables Milieu Saharien, Adrar, Algeria
关键词
Passive cooling; Earth-to-air heat exchanger; Wind tower; Air flow velocity; Daily cooling potential; PRESSURE COEFFICIENTS; NUMERICAL-SIMULATION; THERMAL PERFORMANCE; TUBE SYSTEM; DESIGN; VENTILATION; REGIONS; FLOW; SOIL;
D O I
10.1016/j.enconman.2014.11.042
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, a new design of passive cooling system which consists in an Earth-to-Air Heat Exchanger (EAHE) assisted by a wind tower is presented. This system is intended for the summer cooling in hot and arid regions of Algeria. A transient analytical model was developed in order to investigate the influence of design parameters on the performance of the EAHE. The model of the EAHE is validated against both theoretical and experimental data carried out by other authors. Since it is well-known that the performance of the EAHE systems is more influenced by the air flow velocity, another model was presented to predict the air velocity inside the buried pipe. Moreover, a burying depth of 2 m was adopted and the period under consideration is July where the ambient temperature exceeds 45 degrees C. This study was also extended to examine the behaviour of system during the whole year. In addition, a sensitivity survey was curried out to investigate the influence of tower and pipe dimensions on the air flow velocity and the performances of the EAHE. Results showed that the wind tower dimensions (height, cross section) have not an important impact compared to the pipe dimensions (length, diameter). It is found that a tower with a total height of 5.1 m and a cross section area of 0.57 m(2) can generate an air flow rate of 592.61 m(3)/h. Furthermore, it has been also observed that the daily cooling potential reached a maximum of 30.7 kWh corresponding to a pipe length of 70 m. The cooling effectiveness of the system is compared to that of traditional passive cooling system consisting in a wind tower with wet surfaces. The results indicated that the ambient air after passing through the wind tower coupled to the EAHE is colder than of that of the leaving the conventional cooling tower. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 11
页数:11
相关论文
共 50 条
  • [31] Parametric Analysis on an Earth-to-Air Heat Exchanger Employed in an Air Conditioning System
    D'Agostino, Diana
    Esposito, Francesco
    Greco, Adriana
    Masselli, Claudia
    Minichiello, Francesco
    ENERGIES, 2020, 13 (11)
  • [32] Heating and cooling potential of an earth-to-air heat exchanger using artificial neural network
    Kumar, R
    Kaushik, SC
    Garg, SN
    RENEWABLE ENERGY, 2006, 31 (08) : 1139 - 1155
  • [33] Parametric study on the thermal performance of phase change material-assisted earth-to-air heat exchanger
    Liu, Qinggong
    Huang, Yi
    Ma, Yin
    Peng, Yuanling
    Wang, Yong
    ENERGY AND BUILDINGS, 2021, 238
  • [35] THE DECREASE OF COOLING LOAD IN THE VAPOR COMPRESSION SYSTEM BY THE EARTH-TO-AIR HEAT EXCHANGER SYSTEM
    Arunwattana, Weerawoot
    SURANAREE JOURNAL OF SCIENCE AND TECHNOLOGY, 2008, 15 (01): : 49 - 55
  • [36] Analysis of an earth-to-air heat exchanger for enhanced residential thermal comfort
    Dewangan, Chandraprakash
    Shukla, Anuj Kumar
    Salhotra, Rahul
    Dewan, Anupam
    ENVIRONMENTAL PROGRESS & SUSTAINABLE ENERGY, 2024, 43 (03)
  • [37] Thermal and environmental assessment of a passive building equipped with an earth-to-air heat exchanger in France
    Thiers, Stephane
    Peuportier, Bruno
    SOLAR ENERGY, 2008, 82 (09) : 820 - 831
  • [38] Thermal analysis of earth-to-air heat exchanger using laboratory simulator
    Yusof, T. M.
    Ibrahim, H.
    Azmi, W. H.
    Rejab, M. R. M.
    APPLIED THERMAL ENGINEERING, 2018, 134 : 130 - 140
  • [39] Experimental and numerical study on cooling performance of a novel earth-to-air heat exchanger system with an inlet plenum chamber
    Yang, Qizhi
    Hu, Zhiru
    Tao, Yao
    Shi, Long
    Tu, Jiyuan
    Chai, Jie
    Wang, Yong
    ENERGY CONVERSION AND MANAGEMENT, 2023, 277
  • [40] Influence of parameters on performance of earth air heat exchanger in hot-dry climate
    Baljit Singh
    Rakesh Kumar
    A. K. Asati
    Journal of Mechanical Science and Technology, 2018, 32 : 5457 - 5463