Performance analysis of an earth-to-air heat exchanger assisted by a wind tower for passive cooling of buildings in arid and hot climate

被引:76
|
作者
Benhammou, M. [1 ]
Draoui, B. [1 ]
Zerrouki, M. [1 ]
Marif, Y. [1 ]
机构
[1] Ctr Dev Energies Renouvelables, Div Convers Therm & Thermodynam, Unite Rech Energies Renouvelables Milieu Saharien, Adrar, Algeria
关键词
Passive cooling; Earth-to-air heat exchanger; Wind tower; Air flow velocity; Daily cooling potential; PRESSURE COEFFICIENTS; NUMERICAL-SIMULATION; THERMAL PERFORMANCE; TUBE SYSTEM; DESIGN; VENTILATION; REGIONS; FLOW; SOIL;
D O I
10.1016/j.enconman.2014.11.042
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, a new design of passive cooling system which consists in an Earth-to-Air Heat Exchanger (EAHE) assisted by a wind tower is presented. This system is intended for the summer cooling in hot and arid regions of Algeria. A transient analytical model was developed in order to investigate the influence of design parameters on the performance of the EAHE. The model of the EAHE is validated against both theoretical and experimental data carried out by other authors. Since it is well-known that the performance of the EAHE systems is more influenced by the air flow velocity, another model was presented to predict the air velocity inside the buried pipe. Moreover, a burying depth of 2 m was adopted and the period under consideration is July where the ambient temperature exceeds 45 degrees C. This study was also extended to examine the behaviour of system during the whole year. In addition, a sensitivity survey was curried out to investigate the influence of tower and pipe dimensions on the air flow velocity and the performances of the EAHE. Results showed that the wind tower dimensions (height, cross section) have not an important impact compared to the pipe dimensions (length, diameter). It is found that a tower with a total height of 5.1 m and a cross section area of 0.57 m(2) can generate an air flow rate of 592.61 m(3)/h. Furthermore, it has been also observed that the daily cooling potential reached a maximum of 30.7 kWh corresponding to a pipe length of 70 m. The cooling effectiveness of the system is compared to that of traditional passive cooling system consisting in a wind tower with wet surfaces. The results indicated that the ambient air after passing through the wind tower coupled to the EAHE is colder than of that of the leaving the conventional cooling tower. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 11
页数:11
相关论文
共 50 条
  • [21] Experimental study of an earth-to-air heat exchanger coupled to the solar chimney for heating and cooling applications in arid regions
    Sakhri, Nasreddine
    Menni, Younes
    Chamkha, Ali J.
    Lorenzini, Giulio
    Ameur, Houari
    Kaid, Noureddine
    Bensafi, Mohammed
    JOURNAL OF THERMAL ANALYSIS AND CALORIMETRY, 2021, 145 (06) : 3349 - 3358
  • [22] Cooling Performance of an Earth to Air Heat Fxchanger in Hot Semi-arid Climate Parametric study
    Mahach, Hassan
    Benhamou, Brahim
    2018 6TH INTERNATIONAL RENEWABLE AND SUSTAINABLE ENERGY CONFERENCE (IRSEC), 2018, : 754 - 758
  • [23] Experimental study to investigate the effect of water impregnation on thermal performance of earth air tunnel heat exchanger for summer cooling in hot and arid climate
    Agrawal, Kamal Kumar
    Misra, Rohit
    Yadav, Tejpal
    Das Agrawal, Ghanshyam
    Jamuwa, Doraj Kamal
    RENEWABLE ENERGY, 2018, 120 : 255 - 265
  • [24] Performance analysis of domed roof integrated with earth-to-air heat exchanger system to meet thermal comfort conditions in buildings
    Akbarpoor, Ali Mirzazade
    Poshtiri, Amin Haghighi
    Biglari, Faraz
    RENEWABLE ENERGY, 2021, 168 (168) : 1265 - 1293
  • [25] Performance assessment of a novel type of Earth-to-Air Heat Exchanger consisting of a composite pipe integrating a convective zone for summer cooling of buildings
    Benhammou, M.
    Boubekeur, L.
    Moungar, H.
    Sahli, Y.
    JOURNAL OF ENERGY STORAGE, 2023, 62
  • [26] A parametric analysis of the cooling performance of vertical earth-air heat exchanger in a subtropical climate
    Ahmed, S. F.
    Khan, M. M. K.
    Amanullah, M. T. O.
    Rasul, M. G.
    Hassan, N. M. S.
    RENEWABLE ENERGY, 2021, 172 : 350 - 367
  • [27] The effect of greenhouse vegetation coverage and area on the performance of an earth-to-air heat exchanger for heating and cooling modes
    Mogharreb, Mohsen Mohammadi
    Abbaspour-Fard, Mohammad Hossein
    Goldani, Morteza
    Emadi, Bagher
    INTERNATIONAL JOURNAL OF SUSTAINABLE ENGINEERING, 2014, 7 (03) : 245 - 252
  • [28] Experimental investigation of the performance of earth-to-air heat exchangers in arid environments
    Sakhri, Nasreddine
    Menni, Younes
    Ameur, Houari
    JOURNAL OF ARID ENVIRONMENTS, 2020, 180
  • [29] Study on Performance Analysis of Earth-Air-Pipe Heat Exchanger as Passive Cooling and Heating System
    Verma, Mahendra Kumar
    Bansal, Vikas
    Rana, Kunj Bihari
    ADVANCES IN FLUID AND THERMAL ENGINEERING, 2019, : 821 - 836
  • [30] Parametric study on the thermal performance of phase change material-assisted earth-to-air heat exchanger
    Liu, Qinggong
    Huang, Yi
    Ma, Yin
    Peng, Yuanling
    Wang, Yong
    Wang, Yong (cqwangyong@cqu.edu.cn), 1600, Elsevier Ltd (238):