Performance analysis of an earth-to-air heat exchanger assisted by a wind tower for passive cooling of buildings in arid and hot climate

被引:76
|
作者
Benhammou, M. [1 ]
Draoui, B. [1 ]
Zerrouki, M. [1 ]
Marif, Y. [1 ]
机构
[1] Ctr Dev Energies Renouvelables, Div Convers Therm & Thermodynam, Unite Rech Energies Renouvelables Milieu Saharien, Adrar, Algeria
关键词
Passive cooling; Earth-to-air heat exchanger; Wind tower; Air flow velocity; Daily cooling potential; PRESSURE COEFFICIENTS; NUMERICAL-SIMULATION; THERMAL PERFORMANCE; TUBE SYSTEM; DESIGN; VENTILATION; REGIONS; FLOW; SOIL;
D O I
10.1016/j.enconman.2014.11.042
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this paper, a new design of passive cooling system which consists in an Earth-to-Air Heat Exchanger (EAHE) assisted by a wind tower is presented. This system is intended for the summer cooling in hot and arid regions of Algeria. A transient analytical model was developed in order to investigate the influence of design parameters on the performance of the EAHE. The model of the EAHE is validated against both theoretical and experimental data carried out by other authors. Since it is well-known that the performance of the EAHE systems is more influenced by the air flow velocity, another model was presented to predict the air velocity inside the buried pipe. Moreover, a burying depth of 2 m was adopted and the period under consideration is July where the ambient temperature exceeds 45 degrees C. This study was also extended to examine the behaviour of system during the whole year. In addition, a sensitivity survey was curried out to investigate the influence of tower and pipe dimensions on the air flow velocity and the performances of the EAHE. Results showed that the wind tower dimensions (height, cross section) have not an important impact compared to the pipe dimensions (length, diameter). It is found that a tower with a total height of 5.1 m and a cross section area of 0.57 m(2) can generate an air flow rate of 592.61 m(3)/h. Furthermore, it has been also observed that the daily cooling potential reached a maximum of 30.7 kWh corresponding to a pipe length of 70 m. The cooling effectiveness of the system is compared to that of traditional passive cooling system consisting in a wind tower with wet surfaces. The results indicated that the ambient air after passing through the wind tower coupled to the EAHE is colder than of that of the leaving the conventional cooling tower. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:1 / 11
页数:11
相关论文
共 50 条
  • [2] Experimental and numerical study of an earth-to-air heat exchanger for air cooling in a residential building in hot semi-arid climate
    Khabbaz, Mohamed
    Benhamou, Brahim
    Limam, Karim
    Hollmuller, Pierre
    Hamdi, Hassan
    Bennouna, Amin
    ENERGY AND BUILDINGS, 2016, 125 : 109 - 121
  • [3] Improvement of the summer cooling induced by an earth-to-air heat exchanger integrated in a residential building under hot and arid climate
    Benhammou, Mohammed
    Draoui, Belkacem
    Hamouda, Messaoud
    APPLIED ENERGY, 2017, 208 : 428 - 445
  • [4] Parametric study on thermal performance of earth-to-air heat exchanger used for cooling of buildings
    Benhammou, Mohammed
    Draoui, Belkacem
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2015, 44 : 348 - 355
  • [5] Earth-to-Air Heat Exchanger for Cooling Applications in a Hot and Dry Climate: Numerical and Experimental Study
    Albarghooth, A.
    Ramiar, A.
    Ramyar, R.
    INTERNATIONAL JOURNAL OF ENGINEERING, 2023, 36 (01): : 78 - 89
  • [6] Performance assessment of solar chimney coupled with earth-to-air heat exchanger: A passive alternative for an indoor swimming pool ventilation in hot-arid climate
    Pouranian, Fatemeh
    Akbari, Habibollah
    Hosseinalipour, S. M.
    APPLIED ENERGY, 2021, 299
  • [7] Earth-to-air heat exchanger for NZEB in Mediterranean climate
    Ascione, Fabrizio
    D'Agostino, Diana
    Marino, Concetta
    Minichiello, Francesco
    RENEWABLE ENERGY, 2016, 99 : 553 - 563
  • [8] Performance of a coupled cooling system with earth-to-air heat exchanger and solar chimney
    Li, Haorong
    Yu, Yuebin
    Niu, Fuxin
    Shafik, Michel
    Chen, Bing
    RENEWABLE ENERGY, 2014, 62 : 468 - 477
  • [9] Parametric study on the performance of the earth-to-air heat exchanger for cooling and heating applications
    Hasan, Mushtaq, I
    Noori, Sajad W.
    Shkarah, Ahmed J.
    HEAT TRANSFER-ASIAN RESEARCH, 2019, 48 (05): : 1805 - 1829
  • [10] Modelling and performance analysis of an earth-to-air heat exchanger in a pilot installation
    Rosa, N.
    Santos, P.
    Costa, J. J.
    Gervasio, H.
    JOURNAL OF BUILDING PHYSICS, 2018, 42 (03) : 259 - 287