An integrated evaluation study of the ventilation rate, the exposure and the indoor air quality in naturally ventilated classrooms in the Mediterranean region during spring

被引:72
|
作者
Dorizas, Paraskevi Vivian [1 ]
Assimakopoulos, Margarita-Niki
Helmis, Constantinos
Santamouris, Mattheos
机构
[1] Univ Athens, Fac Phys, Dept Environm Phys, Athens 15784, Greece
关键词
IAQ; PM; CO2; Ventilation; Health; Naturally ventilated schools; PARTICULATE MATTER; PRIMARY-SCHOOL; SUPPLY RATE; PERFORMANCE; CHILDREN; ATHENS; CARBON; POLLUTANTS; PARTICLES; POLLUTION;
D O I
10.1016/j.scitotenv.2014.09.060
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
Ventilation rates and indoor air pollutants have been extensively monitored in nine naturally ventilated primary schools of Athens, Greece during spring. The ventilation rates and pollutant levels were studied during the teaching and non-teaching periods and ventilation profiles were created for each of the schools. The median ventilation rates per school ranged between 0.7 and 8 ACH while the average ventilation rate in all schools (11.7 l/s/p) was greater than the minimum recommended rates by ASHRAE for school classrooms. The average carbon dioxide (CO2) concentrations per school varied between 893 and 2082 ppm, while the majority of the cases were slightly above the recommended limit values. CO2 concentrations were also positively correlated to the number of students and negatively correlated to the ventilation rates. Particles of several size ranges (PM10, PM5, PM2.5, PM1, PM0.5 and UFP) were also measured and analyzed. PM10 concentrations exceeded the recommended limit values by more than 10 times for the majority of the cases. There were also many cases that the PM2.5 concentrations exceeded their limit values. PM concentrations were significantly affected by the ventilation rates and the presence of students. All of the measured particle sizes were greater during teaching than the non-teaching hours. For most of the cases the indoor to outdoor (I/O) concentrations ratios of PM10 and PM2.5 were much greater than one, indicating that the indoor environment was being mostly affected by indoor sources instead of the outdoor air. Furthermore it was found that chalk and marker boards' usage significantly affect indoor pollutant concentrations. Overall, the measured levels of exposure were for most of the cases greater than the recommended guideline values due to the intense presence of indoor pollution sources, even though the ventilation rates were in general satisfactory. (C) 2014 Elsevier B.V. All rights reserved.
引用
收藏
页码:557 / 570
页数:14
相关论文
共 29 条
  • [1] Indoor Air Quality in Naturally Ventilated Italian Classrooms
    Fuoco, Fernanda Carmen
    Stabile, Luca
    Buonanno, Giorgio
    Trassiera, Concepcion Vargas
    Massimo, Angelamaria
    Russi, Aldo
    Mazaheri, Mandana
    Morawska, Lidia
    Andrade, Alexandro
    [J]. ATMOSPHERE, 2015, 6 (11) : 1652 - 1675
  • [2] Effect of natural ventilation and manual airing on indoor air quality in naturally ventilated Italian classrooms
    Stabile, Luca
    Dell'Isola, Marco
    Frattolillo, Andrea
    Massimo, Angelamaria
    Russi, Aldo
    [J]. BUILDING AND ENVIRONMENT, 2016, 98 : 180 - 189
  • [3] IMPROVING INDOOR AIR QUALITY OF NATURALLY VENTILATED CLASSROOMS IN THE NORTHEAST OF PORTUGAL
    Rodrigues, Filipe
    Feliciano, Manuel
    [J]. ENVIRONMENTAL ENGINEERING AND MANAGEMENT JOURNAL, 2019, 18 (07): : 1423 - 1437
  • [4] Monitoring and modelling indoor air quality and ventilation in classrooms within a purpose-designed naturally ventilated school
    Kolokotroni, M
    Ge, YT
    Katsoulas, D
    [J]. INDOOR AND BUILT ENVIRONMENT, 2002, 11 (06) : 316 - 326
  • [5] Indoor Air Quality in UK School Classrooms Ventilated by Natural Ventilation Windcatchers
    Jones, Benjamin M.
    Kirby, Ray
    [J]. INTERNATIONAL JOURNAL OF VENTILATION, 2012, 10 (04) : 323 - 337
  • [6] Measurement and evaluation of indoor air quality in naturally ventilated residential buildings
    Yin, Haiguo
    Liu, Chunxue
    Zhang, Leiming
    Li, Angui
    Ma, Zhenjun
    [J]. INDOOR AND BUILT ENVIRONMENT, 2019, 28 (10) : 1307 - 1323
  • [7] A ventilation intervention study in classrooms to improve indoor air quality: the FRESH study
    Jeannette TM Rosbach
    Machiel Vonk
    Frans Duijm
    Jan T van Ginkel
    Ulrike Gehring
    Bert Brunekreef
    [J]. Environmental Health, 12
  • [8] A ventilation intervention study in classrooms to improve indoor air quality: the FRESH study
    Rosbach, Jeannette T. M.
    Vonk, Machiel
    Duijm, Frans
    van Ginkel, Jan T.
    Gehring, Ulrike
    Brunekreef, Bert
    [J]. ENVIRONMENTAL HEALTH, 2013, 12
  • [9] Evaluation of Indoor Air Quality in Classrooms Equipped with Cross-Flow Ventilation
    Conceicao, Eusebio Z. E.
    Farinho, Joao P.
    Lucio, Ma Manuela J. R.
    [J]. INTERNATIONAL JOURNAL OF VENTILATION, 2012, 11 (01) : 53 - 67
  • [10] Indoor Air Quality in Naturally Ventilated Classrooms. Lessons Learned from a Case Study in a COVID-19 Scenario
    Meiss, Alberto
    Jimeno-Merino, Hector
    Poza-Casado, Irene
    Llorente-Alvarez, Alfredo
    Angel Padilla-Marcos, Miguel
    [J]. SUSTAINABILITY, 2021, 13 (15)