Condition monitoring of in-service oil-filled transformers: Case studies and experience

被引:27
|
作者
Rao, U. Mohan [1 ]
Fofana, I. [1 ]
Betie, A. [2 ]
Senoussaoui, M. L. [3 ]
Brahami, M. [3 ]
Briosso, E. [4 ]
机构
[1] Univ Quebec Chicoutimi, Res Chair Aging Power Network Infrastruct ViAHT, Chicoutimi, PQ G7H 2B1, Canada
[2] Inst Natl Polytech Houphouet Boigny, Dept Elect Engn, Yamoussoukro, Cote Ivoire
[3] Univ Djillali Liabes Sidi Bel Abbes, Intelligent Control & Elect Power Syst Lab, Sidi Bel Abbes, Algeria
[4] CTM, Salto Grande, Uruguay
关键词
Reactors; Aging; Power transformer insulation; Oil insulation; Power transformers; aging; insulation oil; monitoring; reactor; transformer;
D O I
10.1109/MEI.2019.8878258
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Transformers are one of the most strategic components in balancing the voltage levels and hence a high priority is given to their performance [1]. It is established that, insulation technology plays a critical role in judging the performance and service life in oil filled apparatus [2]. Performance of the insulation system depends mainly on the deterioration behavior of insulation oil and paper. The mechanisms that are responsible for premature aging of oil/paper insulation are almost the same in all the oil filled apparatus. Yet, there will be a significant difference in the intensity of the aging mechanisms in different apparatus. This intensity is attributable to rating, design, and duration of operation for different machines. The detailed discussions on these mechanisms are presented in the subsequent sections of this paper. However, aging of service insulants is unavoidable and is to be maintained at a lower rate or arrested to the greatest possible extent, such that, catastrophic failures and unscheduled outages may be mitigated [3]. Normally, utilities follow scheduled condition monitoring activities to avoid the consequences of premature aging. Hence, knowledge on these in-service condition monitoring activities will be helpful in understanding the exact deterioration rate of the insulation system. Real time in-service experience of several transformer fleets that belong to United Kingdom utilities are reported in [4]. An early degradation of insulation is noticed through increase in acidity and furan concentration in oil for several transformers in the fleet. Authors investigated this early degradation in different perspectives including loading conditions, manufacturers, and oil chemistry changes. It is inferred that changes in oil chemistry is an important attribute for early degradation and hence utilities are advised to adopt different asset management strategies for affected and unaffected transformers in a fleet. Recently, failure rate data of service aged transformer fleets of an Australian utility were analyzed to establish the relationship between aging and different failure types [5]. It is noticed that degradation of the insulation system will be rapid after 20 years of service aging thus entailing the frequent condition monitoring activities after 20 years to identify premature aging failures.
引用
收藏
页码:33 / 42
页数:10
相关论文
共 50 条
  • [41] Endophthalmitis in silicone oil-filled eye: A case report
    Yan, Hui-Chao
    Wang, Ze-Lu
    Yu, Wen-Zhen
    Zhao, Ming-Wei
    Liang, Jian-Hong
    Yin, Hong
    Shi, Xuan
    Miao, Heng
    WORLD JOURNAL OF CLINICAL CASES, 2024, 12 (01)
  • [42] Assessment of In-Service Transformers Filled with Synthetic Ester at 33 kV and Below
    Daghrah, Muhammad
    Onay, Oguz
    IEEE ELECTRICAL INSULATION MAGAZINE, 2021, 37 (05) : 6 - 13
  • [43] Intelligent optical fibre monitoring of oil-filled circuit breakers
    Cosgrave, J
    Stangherlin, S
    Humphries, J
    Jones, GR
    Piazza, C
    Volponi, S
    Sfondrini, L
    IEE PROCEEDINGS-GENERATION TRANSMISSION AND DISTRIBUTION, 1999, 146 (06) : 557 - 562
  • [44] In-service monitoring of the current switch metal condition
    Shvets' V.P.
    Muzyka M.R.
    Makovets'Kyi I.V.
    Bulakh P.O.
    Strength of Materials, 2011, 43 (1) : 73 - 76
  • [45] IN-SERVICE MONITORING OF THE CURRENT SWITCH METAL CONDITION
    Shvets', V. P.
    Muzyka, M. R.
    Makovets'kyi, I. V.
    Bulakh, P. O.
    STRENGTH OF MATERIALS, 2011, 43 (01) : 73 - 76
  • [46] REVIEW OF CHEMICAL INDICATORS OF DEGRADATION OF CELLULOSIC ELECTRICAL PAPER INSULATION IN OIL-FILLED TRANSFORMERS
    EMSLEY, AM
    STEVENS, GC
    IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 1994, 141 (05) : 324 - 334
  • [47] Comparative Analysis of the Results of Diagnostic Measurements with an Internal Inspection of Oil-Filled Power Transformers
    Piotrowski, Tomasz
    Rozga, Pawel
    Kozak, Ryszard
    ENERGIES, 2019, 12 (11)
  • [48] Temperature rise of small oil-filled distribution transformers supplying nonsinusoidal load currents
    Galli, AW
    Cox, MD
    IEEE TRANSACTIONS ON POWER DELIVERY, 1996, 11 (01) : 283 - 291
  • [49] Fault diagnosis for oil-filled transformers using voting based extreme learning machine
    Liwei Zhang
    Jian Zhai
    Cluster Computing, 2019, 22 : 8363 - 8370
  • [50] Optical chemosensors for transformers'oil degradation monitoring: case studies
    De Maria, Letizia
    Cennamo, Nunzio
    Zeni, Luigi
    Scatiggio, Fabio
    Pesavento, Maria
    2018 AEIT INTERNATIONAL ANNUAL CONFERENCE, 2018,