Condition monitoring of in-service oil-filled transformers: Case studies and experience

被引:27
|
作者
Rao, U. Mohan [1 ]
Fofana, I. [1 ]
Betie, A. [2 ]
Senoussaoui, M. L. [3 ]
Brahami, M. [3 ]
Briosso, E. [4 ]
机构
[1] Univ Quebec Chicoutimi, Res Chair Aging Power Network Infrastruct ViAHT, Chicoutimi, PQ G7H 2B1, Canada
[2] Inst Natl Polytech Houphouet Boigny, Dept Elect Engn, Yamoussoukro, Cote Ivoire
[3] Univ Djillali Liabes Sidi Bel Abbes, Intelligent Control & Elect Power Syst Lab, Sidi Bel Abbes, Algeria
[4] CTM, Salto Grande, Uruguay
关键词
Reactors; Aging; Power transformer insulation; Oil insulation; Power transformers; aging; insulation oil; monitoring; reactor; transformer;
D O I
10.1109/MEI.2019.8878258
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Transformers are one of the most strategic components in balancing the voltage levels and hence a high priority is given to their performance [1]. It is established that, insulation technology plays a critical role in judging the performance and service life in oil filled apparatus [2]. Performance of the insulation system depends mainly on the deterioration behavior of insulation oil and paper. The mechanisms that are responsible for premature aging of oil/paper insulation are almost the same in all the oil filled apparatus. Yet, there will be a significant difference in the intensity of the aging mechanisms in different apparatus. This intensity is attributable to rating, design, and duration of operation for different machines. The detailed discussions on these mechanisms are presented in the subsequent sections of this paper. However, aging of service insulants is unavoidable and is to be maintained at a lower rate or arrested to the greatest possible extent, such that, catastrophic failures and unscheduled outages may be mitigated [3]. Normally, utilities follow scheduled condition monitoring activities to avoid the consequences of premature aging. Hence, knowledge on these in-service condition monitoring activities will be helpful in understanding the exact deterioration rate of the insulation system. Real time in-service experience of several transformer fleets that belong to United Kingdom utilities are reported in [4]. An early degradation of insulation is noticed through increase in acidity and furan concentration in oil for several transformers in the fleet. Authors investigated this early degradation in different perspectives including loading conditions, manufacturers, and oil chemistry changes. It is inferred that changes in oil chemistry is an important attribute for early degradation and hence utilities are advised to adopt different asset management strategies for affected and unaffected transformers in a fleet. Recently, failure rate data of service aged transformer fleets of an Australian utility were analyzed to establish the relationship between aging and different failure types [5]. It is noticed that degradation of the insulation system will be rapid after 20 years of service aging thus entailing the frequent condition monitoring activities after 20 years to identify premature aging failures.
引用
收藏
页码:33 / 42
页数:10
相关论文
共 50 条
  • [31] The use of TEV sensors for online PD detection in oil-filled transformers
    Lachance, Mathieu
    Al-Gunaid, Mohammed
    2023 IEEE ELECTRICAL INSULATION CONFERENCE, EIC, 2023,
  • [32] Oil-filled cable leak location by continuous monitoring
    不详
    INSIGHT, 2004, 46 (09) : 514 - 514
  • [33] FIELD EXPERIENCE WITH AN ONLINE GAS MONITORING DEVICE FOR OIL FILLED INSTRUMENT TRANSFORMERS
    MATTHIESSEN, P
    ELLIS, KP
    IEEE TRANSACTIONS ON POWER DELIVERY, 1994, 9 (03) : 1476 - 1479
  • [34] Cellulose insulation in oil-filled power transformers: Part I - History and development
    Prevost, TA
    Oommen, TV
    IEEE ELECTRICAL INSULATION MAGAZINE, 2006, 22 (01) : 28 - 35
  • [35] Assessment of Insulation System State for Oil-Filled High-Voltage Transformers
    Zenova E.V.
    Chernyshev V.A.
    Russian Electrical Engineering, 2019, 90 (02): : 140 - 146
  • [36] Dielectric withstand voltage tests and test conversion factors for oil-filled transformers
    Okabe, Shigemitsu
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2008, 15 (02) : 583 - 590
  • [37] Temperature dependant relaxation studies on oil-filled transformer
    Cao, HY
    Birlasekaran, S
    CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, : 174 - 178
  • [38] RESEARCH ON THE EFFECT OF AMBIENT TEMPERATURE VARIATION ON THERMOMETERS FOR OIL-FILLED POWER TRANSFORMERS
    Dai, Yuansheng
    Shan, Huaping
    2012 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2012,
  • [39] A Spreadsheet Based Dissolved Gas Analysis Diagnostic Tool For Oil-Filled Transformers
    Mekkayil, Anju
    Pillai, Gobind
    Malcolm, Marc
    2020 55TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC), 2020,
  • [40] On-line condition monitoring of EHV XLPE oil-filled terminations by using a new sensing system
    Kapelrud, Andre
    Meyer, Hans Kristian H.
    Liland, Knut B.
    Madshaven, Inge
    Vedum, Jon
    Mithassel, Benedikt
    Liverud, Anders E.
    Gaspari, Roberto
    Hvidsten, Sverre
    2024 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATIONS, ICHVE 2024, 2024,