REVIEW OF CHEMICAL INDICATORS OF DEGRADATION OF CELLULOSIC ELECTRICAL PAPER INSULATION IN OIL-FILLED TRANSFORMERS

被引:264
|
作者
EMSLEY, AM [1 ]
STEVENS, GC [1 ]
机构
[1] NATL POWER RES & TECHNOL,LEATHERHEAD KT22 7SE,SURREY,ENGLAND
关键词
CHEMICAL INDICATORS; CONDITION MONITORING; DEGRADATION; ELECTRICAL INSULATION; LIFE PREDICTION; POWER TRANSFORMERS; 2-FURALDEHYDE;
D O I
10.1049/ip-smt:19949957
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Chemical and thermal degradation of electrical insulation in oil-filled transformers, mechanisms of failure and methods of condition monitoring and of life prediction are reviewed. An insulation life prediction model is developed and estimates of insulation life are presented under a variety of oil/paper conditions. Systematic measurements of the concentration of chemical indicators in transformer oil are used to demonstrate that furaldehyde and related products can be used to detect high rates of paper degradation. Similarly, phenol and related products indicate electrical degradation in phenol-formaldehyde resins.
引用
收藏
页码:324 / 334
页数:11
相关论文
共 50 条
  • [1] Depolymerization processes in the thermal degradation of cellulosic paper insulation in electrical transformers
    Levchik, S
    Scheirs, J
    Camino, G
    Tumiatti, W
    Avidano, M
    [J]. POLYMER DEGRADATION AND STABILITY, 1998, 61 (03) : 507 - 511
  • [2] Electrical insulation crepe paper for oil-filled equipment and for activity in air fluid
    Kurochkin, A.A.
    Razumov, N.
    [J]. Tselliuloza, Bumaga, Karton/Pulp, Paper, Board, 2001, (5-6):
  • [3] Estimating the DP Value of the Paper Insulation of Oil-Filled Power Transformers Using an ANFIS Algorithm
    Rhamadhan, Firza Zulmi
    Kinkeldey, Tobias
    Werle, Peter
    Suwarno
    [J]. 2021 11TH INTERNATIONAL CONFERENCE ON POWER, ENERGY AND ELECTRICAL ENGINEERING (CPEEE 2021), 2021, : 202 - 207
  • [4] Study of the mechanism of thermal degradation of cellulosic paper insulation in electrical transformer oil
    Scheirs, J
    Camino, G
    Tumiatti, W
    Avidano, M
    [J]. ANGEWANDTE MAKROMOLEKULARE CHEMIE, 1998, 259 : 19 - 24
  • [5] Possible Indicators of Aging in Oil-Filled Transformers Part 1: Measurements
    Birlasekaran, S.
    Ledwich, G.
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2010, 26 (01) : 26 - 32
  • [6] Cellulose insulation in oil-filled power transformers: Part II - Maintaining insulation integrity and life
    Oommen, TV
    Prevost, TA
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2006, 22 (02) : 5 - 14
  • [7] Cellulose insulation in oil-filled power transformers: Part I - History and development
    Prevost, TA
    Oommen, TV
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2006, 22 (01) : 28 - 35
  • [8] Assessment of Insulation System State for Oil-Filled High-Voltage Transformers
    Zenova E.V.
    Chernyshev V.A.
    [J]. Russian Electrical Engineering, 2019, 90 (02): : 140 - 146
  • [9] THE ANALYSIS OF GASES IN TRANSFORMERS AND OTHER OIL-FILLED ELECTRICAL-EQUIPMENT
    KAWADA, H
    ISHII, T
    [J]. JOURNAL OF JAPAN SOCIETY OF LUBRICATION ENGINEERS, 1980, 25 (11): : 734 - 739
  • [10] Physical-chemical oil tests, monitoring and diagnostics of oil-filled transformers
    Gradnik, MK