Fault detection for the reliability of the refrigerant inventory of the system air conditioner

被引:0
|
作者
Tae, Sang-Jin [1 ]
Cho, Keumnam [2 ]
Kim, Hoon Mo
机构
[1] Sungkyunkwan Univ, Grad Sch, Suwon 440746, South Korea
[2] Sungkyunkwan Univ, Sch Mech Engn, Suwon, South Korea
来源
关键词
charged refrigerant amount; system air-conditioner; fuzzy algorithm;
D O I
10.4028/www.scientific.net/SSP.120.169
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
This study developed a program for detecting charged refrigerant amount in system air-conditioner. System air-conditioner is an air-conditioning system with multiple indoor units. Due to the complexity of the system, it is more difficult to detect the refrigerant amount charged in system air-conditioner than in a general single air-conditioner. Experiments were performed for 6 HP outdoor units with 3 indoor units in a psychrometric calorimeter. The experimental amount of charged refrigerant was ranged from 60% to 140% with 10% increase. Fuzzy algorithm was employed for detecting the charged refrigerant amount in a system air-conditioner. The experimental data were used for curve fitting for general ranges for indoor and outdoor temperature conditions. Membership function were determined for whole ranges of experimentally measured data and rule-base were defined for each amount of refrigerant charge. Developed program successfully predicted the measured data within 10% resolution range.
引用
收藏
页码:169 / +
页数:3
相关论文
共 50 条
  • [31] The climate change impact on air conditioner system and reliability in Malaysia-A review
    Yau, Y. H.
    Pean, H. L.
    RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2011, 15 (09): : 4939 - 4949
  • [32] Design of a steady-state detector for fault detection and diagnosis of a residential air conditioner
    Kim, Minsung
    Yoon, Seok Ho
    Domanski, Piotr A.
    Payne, W. Vance
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (05): : 790 - 799
  • [33] Hotspot Detection for Wall-Mounted Air-Conditioner System
    Jadin, Mohd Shawal
    Khai, Ng Boon
    Sulaiman, Norizam
    Salah, Wael A.
    2017 INTERNATIONAL CONFERENCE ON PROMISING ELECTRONIC TECHNOLOGIES (ICPET 2017), 2017, : 118 - 123
  • [34] Numerical Simulation of Strongly Flammable Refrigerant Leakage from a Split Air Conditioner
    Ito, Makoto
    Ashihara, Naoya
    Dang, Chaobin
    Hihara, Eiji
    Chen, Yu
    14TH IIR GUSTAV-LORENTZEN CONFERENCE ON NATURAL FLUIDS, 2020, : 598 - 603
  • [35] Research on the flammability hazards of an air conditioner using refrigerant R-290
    Zhang, Wang
    Yang, Zhao
    Li, Jin
    Ren, Chang-xing
    Lv, Dong
    Wang, Jie
    Zhang, Xin
    Wu, Wei
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2013, 36 (05): : 1483 - 1494
  • [36] Extending the capillary tube of a propane air-conditioner to reduce the refrigerant charge
    Siang, Jeri Tangalajuk
    Sharifian, Ahmad
    1ST INTERNATIONAL CONFERENCE ON ENERGY AND POWER, ICEP2016, 2017, 110 : 229 - 234
  • [37] Evaporative characteristics of refrigerant R410A in air-conditioner systems
    Duan, X. T.
    Xue, Y. Q.
    Wang, F.
    Wu, Z. M.
    Rui, S. J.
    CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 560 - 564
  • [38] Experimental study on refrigerant migration of room air-conditioner at starting and stopping
    Shi, WX
    Wang, BL
    Liu, T
    Li, XT
    CRYOGENICS AND REFRIGERATION - PROCEEDINGS OF ICCR'2003, 2003, : 660 - 663
  • [39] An empirical model for simulating the effects of refrigerant charge faults on air conditioner performance
    Cheung, Howard
    Braun, James E.
    SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2017, 23 (05) : 776 - 786
  • [40] Study on structure optimization and distribution characteristics of centrifugal refrigerant distributor for air conditioner
    Tang, Qingqing
    Dai, Yuande
    Pan, Chuang
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2023, 156 : 123 - 132