Study on structure optimization and distribution characteristics of centrifugal refrigerant distributor for air conditioner

被引:2
|
作者
Tang, Qingqing [1 ]
Dai, Yuande [1 ]
Pan, Chuang [1 ]
机构
[1] Nanchang Univ, Sch Adv Mfg, Nanchang 330031, Jiangxi, Peoples R China
关键词
Centrifugal refrigerant distributor; Two-phase flow; Mal-distribution; Taguchi method; Structure optimization; FLOW MALDISTRIBUTION; FORCE;
D O I
10.1016/j.ijrefrig.2023.09.019
中图分类号
O414.1 [热力学];
学科分类号
摘要
The refrigerant distributor helps resolve non-uniform flow distribution issues in multi-path evaporators. Using the CFD method, this paper investigates the distribution mechanism of R410A in a centrifugal distributor under air-conditioning conditions and explores the impact of structural factors on its distribution performance. The Taguchi method is employed to identify the optimal combination of structural parameters and optimization direction for achieving distribution uniformity. Furthermore, the flow distribution characteristics of the optimized distributor are investigated under different conditions. The results show that, under the working conditions of an inlet mass flow rate of 50 kg & sdot;h- 1 and an inlet quality of 0.1, the non-uniformity of the mass flow rate in the outlet branches of the optimized distributor is only 1.07 %, which represents a decrease of 7.64 % compared to the original distributor. Additionally, the non-uniformity of the outlet branch quality also decreased by 9.41 %. These findings indicate that the optimized distributor exhibits superior distribution performance. Nonetheless, the degradation of the optimized centrifugal distributor's uniform distribution performance with increasing refrigerant inlet mass flow rate and quality suggests that it is more suitable for low mass flow rate and quality conditions.
引用
收藏
页码:123 / 132
页数:10
相关论文
共 50 条
  • [1] Optimization study on the structure and the flow of a refrigerant distributor for air conditioner
    Zhang, Derun
    Pu, Liang
    Nian, Luozhu
    Meng, Zhongyi
    Gu, Tangtang
    Liu, Min
    Zhou, Yachen
    INTERNATIONAL JOURNAL OF REFRIGERATION, 2021, 131 (131) : 847 - 856
  • [2] Study of refrigerant mal-distribution and optimization in distributor for air conditioner
    Pu, Liang
    Nian, Luozhu
    Zhang, Derun
    Gu, Tangtang
    Liu, Min
    Zhou, Yachen
    Yuan, Fengming
    Chen, Wei
    SUSTAINABLE ENERGY TECHNOLOGIES AND ASSESSMENTS, 2021, 46
  • [3] Performance Evaluation and Optimization of A Refrigerant Distributor for Air Conditioner
    Yoshioka, Shun
    Kim, Hyunyoung
    Kasai, Kazushige
    JOURNAL OF THERMAL SCIENCE AND TECHNOLOGY, 2008, 3 (01): : 68 - 77
  • [4] Performance evaluation and optimization of a refrigerant distributor for air conditioner
    Yoshioka, Shun
    Kim, Hyunyoung
    Kasai, Kazushige
    PROCEEDINGS OF THE ASME/JSME THERMAL ENGINEERING SUMMER HEAT TRANSFER CONFERENCE 2007, VOL 2, 2007, : 603 - 609
  • [5] Numerical Approach to Study Nonuniform Gas-Liquid Distribution in the Refrigerant Distributor in an Air Conditioner
    Ishii, Eiji
    Ishikawa, Masanori
    Yoshimura, Kazuki
    JOURNAL OF FLUIDS ENGINEERING-TRANSACTIONS OF THE ASME, 2015, 137 (11):
  • [6] STUDY OF FACTORS INFLUENCING NON-UNIFORM GAS-LIQUID DISTRIBUTION IN THE REFRIGERANT DISTRIBUTOR IN AN AIR CONDITIONER
    Ishii, Eiji
    Yoshimura, Kazuki
    ASME FLUIDS ENGINEERING DIVISION SUMMER MEETING - 2014, VOL 1C: SYMPOSIA, 2014,
  • [7] GAS-LIQUID FLOW SIMULATION IN REFRIGERANT DISTRIBUTOR FOR AIR CONDITIONER
    Ishii, Eiji
    Yoshimura, Kazuki
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2013, 21 (03)
  • [8] OPTIMIZATION OF THE RESERVE-TYPE DISTRIBUTOR FOR R410A AIR CONDITIONER
    Zhang, Chi
    Wang, Ying
    Chen, Jiangping
    INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2014, 22 (04)
  • [9] The experimental investigation of refrigerant distribution and leaking characteristics of R290 in split type household air conditioner
    Tang, Weier
    He, Guogeng
    Cai, Dehua
    Zhu, Yihao
    Zhang, Aoni
    Tian, Qiqi
    APPLIED THERMAL ENGINEERING, 2017, 115 : 72 - 80
  • [10] Evaporative characteristics of refrigerant R410A in air-conditioner systems
    Duan, X. T.
    Xue, Y. Q.
    Wang, F.
    Wu, Z. M.
    Rui, S. J.
    CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 560 - 564