Evaluating the contamination level of polluted insulators based on the characteristics of leakage current

被引:9
|
作者
Zhao, Shihua [1 ]
Jiang, Xingliang [2 ]
Xie, Yanbin [2 ]
机构
[1] State Grid Hunan Elect Power Corp Res Inst, Changsha 410007, Hunan, Peoples R China
[2] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400030, Peoples R China
来源
INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS | 2015年 / 25卷 / 10期
关键词
leakage current; contamination level; relative humidity; temperature; insulators; prediction; support vector machine; CURRENT WAVE-FORMS; FREQUENCY-CHARACTERISTICS; POLYMER INSULATORS; SILICONE-RUBBER; NEURAL-NETWORK; CLASSIFICATION;
D O I
10.1002/etep.1951
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Effective prediction of the contamination level of insulators is an important approach to the prevention of pollution flashover accidents, and the leakage current (LC) is an efficient factor to analyze and detect the contamination level of insulators. In order to predict how severe the contamination level of insulators is and prevent pollution flashover accidents, firstly, some artificial pollution tests have been investigated under different contamination levels, relative humidity (RH), and ambient temperature (T). Secondly, based on the experimental data, the three characteristics of LC, namely the maximum pulse amplitude (I-h), the energy ratio (K), and the energy (E), have been extracted. They reflect jointly the LC from different perspectives. Thirdly, the variation laws between the three characteristics and the contamination level, RH and T, have been obtained. Fourthly, the prediction of the contamination level by using least squares support vector machine (LS-SVM) model has been presented, in which the three characteristics, RH and T are used as the inputs of model, and the contamination level is used as the output of model. Finally, this model has been verified with the test data obtained in the artificial climate chamber, and the prediction results are consistent with the test results. Therefore, the LS-SVM model is acceptable to predict the contamination level of insulators and is of significance for the prevention of pollution flashover accidents. Copyright (c) 2014 John Wiley & Sons, Ltd.
引用
收藏
页码:2109 / 2123
页数:15
相关论文
共 50 条
  • [31] Impacts of contamination and hydrophobicity level on the leakage currents of composite insulators
    Jiang, X. (xljiang@cqu.edu.cn), 1600, Science Press (39):
  • [32] Use of Leakage Currents of Insulators to Determine the Stage Characteristics of the Flashover Process and Contamination Level Prediction
    Li, Jingyan
    Sima, Wenxia
    Sun, Caixin
    Sebo, Stephen A.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (02) : 490 - 501
  • [33] Flashover Voltage Prediction of Composite Insulators Based on the Characteristics of Leakage Current
    Zhao, Shihua
    Jiang, Xingliang
    Zhang, Zhijing
    Hu, Jianlin
    Shu, Lichun
    IEEE TRANSACTIONS ON POWER DELIVERY, 2013, 28 (03) : 1699 - 1708
  • [34] Estimation of the Pollution Critical Level on the Surface of Glass Insulators Based on Leakage Current
    Barbosa, Vandilson R. N.
    Lira, George R. S.
    Costa, Edson G.
    Galdino, Giovanny M. B.
    Oliveira, Alysson H. P.
    Junior, Almir C. Santos
    IEEE TRANSACTIONS ON POWER DELIVERY, 2024, 39 (02) : 1222 - 1232
  • [35] Comparison of leakage current properties between polymeric insulators and porcelain insulators under salt polluted conditions
    Homma, H
    Kuroyagi, T
    Ishino, R
    Takahashi, T
    PROCEEDINGS OF THE 2005 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, VOLS, 1-3, 2005, : 348 - 351
  • [36] Research on Leakage Current Sampling and Denoising Method of Contamination Glass Insulators
    Liu Zhengfa
    Wu Gaolin
    Zhou Qing
    Fu Qigang
    Xiao Qianbo
    Hu Jianlin
    Bi Maoqiang
    2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 892 - 895
  • [37] Relation between leakage current and surface contamination of suspension porcelain insulators
    College of Electrical and Electronic Engineering, North China Electric Power University, Baoding 071003, China
    Gaodianya Jishu/High Voltage Engineering, 2008, 34 (04): : 655 - 659
  • [38] Chirplet-Fractal Characteristics of Leakage Current on HV Insulators
    Hui, Ali
    Lin, Hui
    PROCEEDINGS OF THE 2011 INTERNATIONAL CONFERENCE ON INFORMATICS, CYBERNETICS, AND COMPUTER ENGINEERING (ICCE2011), VOL 1: INTELLIGENT CONTROL AND NETWORK COMMUNICATION, 2011, 110 (01): : 157 - +
  • [39] Chirplet-Fractal Characteristics of Leakage Current on HV Insulators
    Hui, Ali
    Lin, Hui
    2010 INTERNATIONAL COLLOQUIUM ON COMPUTING, COMMUNICATION, CONTROL, AND MANAGEMENT (CCCM2010), VOL I, 2010, : 294 - 298
  • [40] Flashover Pattern Recognition by HMM Based on Fractal Characteristics of Leakage Current on HV Insulators
    Ali, Hui
    RECENT TRENDS IN MATERIALS AND MECHANICAL ENGINEERING MATERIALS, MECHATRONICS AND AUTOMATION, PTS 1-3, 2011, 55-57 : 1148 - 1151