Evaluating the contamination level of polluted insulators based on the characteristics of leakage current

被引:9
|
作者
Zhao, Shihua [1 ]
Jiang, Xingliang [2 ]
Xie, Yanbin [2 ]
机构
[1] State Grid Hunan Elect Power Corp Res Inst, Changsha 410007, Hunan, Peoples R China
[2] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400030, Peoples R China
来源
INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS | 2015年 / 25卷 / 10期
关键词
leakage current; contamination level; relative humidity; temperature; insulators; prediction; support vector machine; CURRENT WAVE-FORMS; FREQUENCY-CHARACTERISTICS; POLYMER INSULATORS; SILICONE-RUBBER; NEURAL-NETWORK; CLASSIFICATION;
D O I
10.1002/etep.1951
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Effective prediction of the contamination level of insulators is an important approach to the prevention of pollution flashover accidents, and the leakage current (LC) is an efficient factor to analyze and detect the contamination level of insulators. In order to predict how severe the contamination level of insulators is and prevent pollution flashover accidents, firstly, some artificial pollution tests have been investigated under different contamination levels, relative humidity (RH), and ambient temperature (T). Secondly, based on the experimental data, the three characteristics of LC, namely the maximum pulse amplitude (I-h), the energy ratio (K), and the energy (E), have been extracted. They reflect jointly the LC from different perspectives. Thirdly, the variation laws between the three characteristics and the contamination level, RH and T, have been obtained. Fourthly, the prediction of the contamination level by using least squares support vector machine (LS-SVM) model has been presented, in which the three characteristics, RH and T are used as the inputs of model, and the contamination level is used as the output of model. Finally, this model has been verified with the test data obtained in the artificial climate chamber, and the prediction results are consistent with the test results. Therefore, the LS-SVM model is acceptable to predict the contamination level of insulators and is of significance for the prevention of pollution flashover accidents. Copyright (c) 2014 John Wiley & Sons, Ltd.
引用
收藏
页码:2109 / 2123
页数:15
相关论文
共 50 条
  • [11] Experimental research on the frequency and phase characteristics of leakage current of artificially polluted insulators
    Jiang, Xing-Liang
    Shi, Yan
    Huang, Huan
    Sun, Cai-Xin
    Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2010, 30 (07): : 118 - 124
  • [12] Characterizing Leakage Current on Polluted Insulators by Measuring Nonlinearity
    Sokolowski, Peter
    Li, Xiangjun
    Yu, Xinghuo
    Feng, Yong
    2014 IEEE 23RD INTERNATIONAL SYMPOSIUM ON INDUSTRIAL ELECTRONICS (ISIE), 2014, : 2427 - 2432
  • [13] Leakage current patterns on artificially polluted composite insulators
    Fernando, MARM
    Gubanski, SM
    IEEE 1996 ANNUAL REPORT - CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS I & II, 1996, : 394 - 397
  • [15] Estimation of Contamination Level of Overhead Insulators Based on Surface Leakage Current Employing Detrended Fluctuation Analysis
    Deb, Suhas
    Das, Santanu
    Pradhan, Arpan Kumar
    Banik, Apu
    Chatterjee, Biswendu
    Dalai, Sovan
    IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2020, 67 (07) : 5729 - 5736
  • [16] Experimental validation of machine learning for contamination classification of polluted high voltage insulators using leakage current
    Umer Amir Khan
    Mansoor Asif
    Muhammad Hamza Zafar
    Luai Alhems
    Scientific Reports, 15 (1)
  • [17] Experimental-based models for predicting the flashover voltage of polluted SiR insulators using leakage current characteristics
    Dadashizadeh Samakosh, Jaber
    Mirzaie, Mohammad
    IET SCIENCE MEASUREMENT & TECHNOLOGY, 2020, 14 (10) : 943 - 952
  • [18] The Leakage Current Components as a Diagnostic Tool to Estimate Contamination Level on High Voltage Insulators
    Salem, Ali A.
    Abd-Rahman, R.
    Al-Gailani, Samir Ahmed
    Kamarudin, M. S.
    Ahmad, Hussein
    Salam, Zainal
    IEEE ACCESS, 2020, 8 : 92514 - 92528
  • [19] Signature analysis for leakage current wave forms of polluted insulators
    Karady, GG
    Amarh, F
    1999 IEEE TRANSMISSION AND DISTRIBUTION CONFERENCE, VOLS 1 & 2, 1999, : 806 - 811
  • [20] Analysis of the Leakage Current on Polluted Insulators Using Correlation Coefficie
    Li, Xiangjun
    Feng, Yong
    Wong, Khoi Loon
    Sokolwski, Peter
    Yu, Xinghuo
    IECON 2011: 37TH ANNUAL CONFERENCE ON IEEE INDUSTRIAL ELECTRONICS SOCIETY, 2011,