STATOR TURN-TO-TURN FAULT DETECTION OF SYNCHRONOUS GENERATOR USING TOTAL HARMONIC DISTORTION (THD) ANALYZING OF MAGNETIC FLUX LINKAGE

被引:0
|
作者
Yaghobi, H. [1 ]
Ansari, K. [2 ]
Mashhadi, H. Rajabi [2 ]
机构
[1] Semnan Univ, Dept Elect Engn, Semnan, Iran
[2] Ferdowsi Univ Mashhad, Dept Elect Engn, Mashhad, Iran
关键词
Synchronous generator; inter-turn fault; magnetic flux linkage; harmonic analysis; ELECTRICAL MACHINES; INTERNAL FAULTS; DIAGNOSIS; MOTORS; LOAD; MODEL;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Diagnostics of synchronous generator turn-to-turn faults can be accomplished by analyzing the anomalies of machine local variable such as magnetic flux linkage. On the other hand, because current transformers and voltage transformers are usually installed in the machine for different purposes as default, the monitoring schemes that depend on the study of these inputs have become a topic of interest. As a consequence, in the last two decades, a variety of methods have been proposed based only on the global external variable (such as stator current and voltage). It must be noted that the global external variable analysis techniques are not capable of detecting all of the potential faults in electrical machines and some researches, including this work, aim to transfer a part of the global external variables analysis knowledge to techniques that monitor the signatures produced by the fault to the electromagnetic flux signals (local variable). Hence, this contribution deals with the analysis of the stator turn-to-turn short circuit fault of salient-pole synchronous generator. In this paper, a fault indicator based on harmonic analysis of the magnetic flux linkage is investigated. Experimental results derived from a 4-pole, 380V, 1500 rpm, 50 Hz, 50 KVA, 3-phase salient-pole synchronous generator, show that the proposed method is useful and effective.
引用
收藏
页码:161 / 182
页数:22
相关论文
共 50 条
  • [31] Transformer Practical Turn-to-Turn Fault Detection Performance using Negative Sequence and Space Vector-Based Methods
    Farzin, Nima
    Vakilian, Mehdi
    Hajipour, Ehsan
    2019 INTERNATIONAL CONFERENCE ON PROTECTION AND AUTOMATION OF POWER SYSTEM (IPAPS), 2019, : 1 - 6
  • [32] An on-line stator turn fault detection method for interior PM synchronous motor drives
    Lee, Youngkook
    Habetler, Thomas G.
    APEC 2007: TWENTY-SECOND ANNUAL IEEE APPLIED POWER ELECTRONICS CONFERENCE AND EXPOSITION, VOLS 1 AND 2, 2007, : 825 - +
  • [33] Turn-to-turn and phase-to-phase short circuit fault detection of wind turbine permanent magnet generator based on equivalent magnetic network modelling by wavelet transform approach
    Ghods, Mehrage
    Tabarniarami, Zabihollah
    Faiz, Jawad
    Bazrafshan, Mohammad Amin
    IET ELECTRIC POWER APPLICATIONS, 2024, 18 (09) : 1005 - 1020
  • [34] Inter-turn stator winding fault detection in synchronous generator based on the extended alpha beta 0 reference frame conversion
    Xia, Changliang
    Fang, Hongwei
    DYNAMICS OF CONTINUOUS DISCRETE AND IMPULSIVE SYSTEMS-SERIES B-APPLICATIONS & ALGORITHMS, 2006, 13E : 708 - 713
  • [35] A Flux-Based Differential Technique for Turn-to-Turn Fault Detection and Defective Region Identification in Line-Connected and Inverter-Fed Induction Motors
    Dehghan, Hamed
    Haghjoo, Farhad
    Cruz, Sergio M. A.
    IEEE TRANSACTIONS ON ENERGY CONVERSION, 2018, 33 (04) : 1876 - 1885
  • [36] A Novel Stator Turn Fault Detection Technique by Using Equivalent High Frequency Impedance
    Wang, Bo
    Hu, Jiapeng
    Wang, Guanghui
    Hua, Wei
    IEEE ACCESS, 2020, 8 : 130540 - 130550
  • [37] A Temperature and Magnetic Field-Based Approach for Stator Inter-Turn Fault Detection
    Wu, Yi-Hang
    Liu, Ming-Yao
    Song, Han
    Li, Cong
    Yang, Xue-Li
    IEEE SENSORS JOURNAL, 2022, 22 (18) : 17799 - 17807
  • [38] Inter-turn fault detection in stator winding of PMSM using wavelet transform
    Moosavi, S. S.
    Esmaili, Q.
    Djerdir, A.
    Amirat, Y. Ait
    2017 IEEE VEHICLE POWER AND PROPULSION CONFERENCE (VPPC), 2017,
  • [39] Permanent Magnet Generator Turn Fault Detection Using Kalman Filter Technique
    Wang, Bo
    Wang, Jiabin
    Griffo, Antonio
    Patel, Vipulkumar I.
    Sun, Zhigang
    Chong, Ellis
    Smitham, Riona
    2016 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2016,
  • [40] A Novel Radial Flux Sensing Technique for Stator Turn Fault Detection in Induction Motors in Online Mode Using Observer Coil
    Surya, G. N.
    Khan, Z. J.
    Ballal, M. S.
    2015 INTERNATIONAL CONFERENCE ON CONDITION ASSESSMENT TECHNIQUES IN ELECTRICAL SYSTEMS (CATCON), 2015, : 93 - 98