Energy-saving Technique Targeting Chilled-water Air Conditioning Equipment in Data Centers

被引:0
|
作者
Nakata, Tatsuya [1 ]
Kaneko, Shinichiro [1 ]
Yoshii, Ari [1 ]
Sekiguchi, Keisuke [1 ]
Yanagi, Masahide [1 ]
机构
[1] NTT FACIL INC, Tsuchiura, Ibaraki, Japan
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Chilled-water cooled computer room air conditioners can be broadly divided into three subsystems: heat sources, delivery systems, and air conditioners. In the typical data center employing chilled-water air conditioners, these three subsystem operate independently of one another, making it very difficult to assess whether the air conditioning system as a whole is operating at maximum efficiency. Defining a reliable data center as one in which the ambient temperature environment of room is kept constant, this study investigates a scheme for integrating control over these three subsystems and reducing the power consumed by the air conditioning system by shifting the setpoints of heat generators and pumps while monitoring conditions in the room to ensure reliability is maintained. Experimental results reveal that the power consumption of the air conditioning system can be slashed by 20% thus demonstrating the energy-saving potential of this approach.
引用
收藏
页数:6
相关论文
共 50 条
  • [1] Equipment energy-saving optimization method for central air-conditioning chilled water system
    Yu, Junqi
    Gao, Zhikun
    Zhao, Anjun
    Hu, Qun
    [J]. Harbin Gongye Daxue Xuebao/Journal of Harbin Institute of Technology, 2022, 54 (12): : 143 - 150
  • [2] Application of energy-saving control strategy in air conditioning terminal equipment based on constant temperature difference of chilled water
    Mao, Zubing
    Li, Feilong
    Su, Qianjin
    Fang, Zhaosong
    Xu, Xiaoning
    Ding, Yunfei
    [J]. CASE STUDIES IN THERMAL ENGINEERING, 2021, 28
  • [3] Energy-saving Analysis of Chilled Water System for Large Temperature Difference Air Conditioning
    Lee, Chengwen
    Chang, Yungchung
    [J]. 2018 4TH INTERNATIONAL CONFERENCE ON ENVIRONMENTAL SCIENCE AND MATERIAL APPLICATION, 2019, 252
  • [4] An Optimal Hybrid Control Method for Energy-Saving of Chilled Water System in Central Air Conditioning
    Zhang, Yan
    Chu, Xiaoli
    Liu, Yongqiang
    [J]. JOURNAL OF CONTROL SCIENCE AND ENGINEERING, 2018, 2018
  • [5] Design of a chilled-water storage unit for solar air-conditioning
    Serag-Eldin, M. A.
    [J]. INTERNATIONAL JOURNAL OF SUSTAINABLE ENERGY, 2013, 32 (05) : 385 - 405
  • [6] Individual Thermal Environments of Building with a Novel Air-Conditioning Energy-Saving Equipment
    Nguyen Anh Tuan
    Wu, Wu-Chieh
    Huy Bich Nguyen
    [J]. FRONTIERS OF GREEN BUILDING, MATERIALS AND CIVIL ENGINEERING III, PTS 1-3, 2013, 368-370 : 645 - +
  • [7] Research on energy saving control of chilled water system of central air conditioning system
    Ju, Li Zhuang
    Cai, Lv
    Jie, Mei
    [J]. PROCEEDINGS OF THE 28TH CHINESE CONTROL AND DECISION CONFERENCE (2016 CCDC), 2016, : 2875 - 2878
  • [8] Experimental investigation on the performance of chilled-water air conditioning unit using alumina nanofluids
    Ahmed, M. Salem
    Hady, Mohamed R. Abdel
    Abdallah, G.
    [J]. THERMAL SCIENCE AND ENGINEERING PROGRESS, 2018, 5 : 589 - 596
  • [9] Energy Consumption Comparison of Large-scale Air-conditioning System With Different Temperature of Chilled-Water
    Jiang, Xiaojiang
    Xiao, Jianren
    Li, Xingyou
    [J]. 10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 2100 - 2104
  • [10] Energy-saving Technology of Refrigeration and Air-conditioning
    王玉鹏
    罗展雄
    谭琴
    [J]. 装备制造技术, 2008, (10) : 24 - 26