The impact of temperature on mean local air age and thermal comfort in a stratum ventilated office

被引:46
|
作者
Tian, Lin [1 ,2 ]
Lin, Zhang [1 ,2 ]
Liu, Jing [3 ]
Yao, Ting [1 ,2 ]
Wang, Qiuwang [3 ]
机构
[1] City Univ Hong Kong, Bldg Energy & Environm Technol Res Unit, Sch Energy & Environm, Hong Kong, Hong Kong, Peoples R China
[2] City Univ Hong Kong, Div Bldg Sci & Technol, Hong Kong, Hong Kong, Peoples R China
[3] Xi An Jiao Tong Univ, State Key Lab Multiphase Flow Power Engn, Xian 710049, Peoples R China
关键词
Stratum ventilation; Mean local air age; Thermal comfort; Elevated indoor temperatures; INDOOR; QUALITY;
D O I
10.1016/j.buildenv.2010.08.013
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The influence of the supply air temperature on the mean local air age and thermal comfort of a typical individual office under stratum ventilation is investigated by a numerical method, which is validated by an experiment carried out by the authors. The results show that for an office, when the supply air temperature is increased from 19 degrees C to 21 degrees C, the corresponding mean occupied zone temperature rises from 24.5 degrees C to 26.5 degrees C. The inhaled air quality for the occupant is improved when supply air temperature rises from 19 C to 21 degrees C. Also, the thermal comfort indices (predicted mean vote or PMV, predicted percentage of dissatisfied or PPD and predicted dissatisfied or PD) fulfill the requirements of ISO 7730 and CR 175 1998. For summer cooling operation, stratum ventilation may offer a feasible solution to elevated indoor temperatures, which are recommended by several governments in East Asia. (C) 2010 Elsevier Ltd. All rights reserved.
引用
收藏
页码:501 / 510
页数:10
相关论文
共 50 条
  • [1] Optimization of room air temperature in stratum-ventilated rooms for both thermal comfort and energy saving
    Zhang, Sheng
    Cheng, Yong
    Fang, Zhaosong
    Huan, Chao
    Lin, Zhang
    [J]. APPLIED ENERGY, 2017, 204 : 420 - 431
  • [2] Mean age of air in a naturally ventilated office: Experimental data and simulations
    Buratti, C.
    Mariani, R.
    Moretti, E.
    [J]. ENERGY AND BUILDINGS, 2011, 43 (08) : 2021 - 2027
  • [3] A Thermal Comfort Levels Investigation of a Naturally Ventilated and Air-Conditioned Office
    Daghigh, R.
    Adam, N. M.
    Sopian, K.
    Zaharim, A.
    Sahari, B. B.
    [J]. SMO 08: PROCEEDINGS OF THE 8TH WSEAS INTERNATIONAL CONFERENCE ON SIMULATION, MODELLING AND OPTIMIZATION, 2008, : 189 - +
  • [4] Thermal comfort study of naturally ventilated office
    Laska, Marta
    [J]. 9TH CONFERENCE ON INTERDISCIPLINARY PROBLEMS IN ENVIRONMENTAL PROTECTION AND ENGINEERING (EKO-DOK 2017), 2017, 17
  • [5] Effects of temperature and supply airflow rate on thermal comfort in a stratum-ventilated room
    Cheng, Yong
    Lin, Zhang
    Fong, Alan M. L.
    [J]. BUILDING AND ENVIRONMENT, 2015, 92 : 269 - 277
  • [6] Analysis on the impact of mean radiant temperature for the thermal comfort of underfloor air distribution systems
    Chung, Jae Dong
    Hong, Hiki
    Yoo, Hoseon
    [J]. ENERGY AND BUILDINGS, 2010, 42 (12) : 2353 - 2359
  • [7] Influences of Air Exchange Effectiveness and its Rate on Thermal Comfort: Naturally Ventilated Office
    Daghigh, R.
    Adam, N. M.
    Sahari, B. B.
    Sopian, K.
    Alghoul, M. A.
    [J]. JOURNAL OF BUILDING PHYSICS, 2008, 32 (02) : 175 - 194
  • [9] Impact of summer office set air-conditioning temperature on energy consumption and thermal comfort
    Liu Hong
    Ma Xiao-lei
    Gao Ya-feng
    [J]. JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2009, 16 : 6 - 11
  • [10] Impact of summer office set air-conditioning temperature on energy consumption and thermal comfort
    刘红
    马小磊
    高亚峰
    [J]. Journal of Central South University, 2009, 16 (S1) : 6 - 11