Effects of temperature and supply airflow rate on thermal comfort in a stratum-ventilated room

被引:66
|
作者
Cheng, Yong [1 ]
Lin, Zhang [2 ]
Fong, Alan M. L. [2 ]
机构
[1] City Univ Hong Kong, Dept Architectural & Civil Engn, Hong Kong, Hong Kong, Peoples R China
[2] City Univ Hong Kong, Div Bldg Sci & Technol, Hong Kong, Hong Kong, Peoples R China
关键词
Stratum ventilation; Temperature; Air movement; Comfort; Draft; Human subject test; DISPLACEMENT VENTILATION; NEUTRAL TEMPERATURE; ENERGY-CONSUMPTION; SENSATION; PERFORMANCE; ENVIRONMENT; SYSTEM; IMPACT; BODY; HEAD;
D O I
10.1016/j.buildenv.2015.04.036
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Providing an appropriate thermal comfort level is crucial for the technical feasibility of stratum ventilation at elevated room temperatures. This paper presents a subjective study of thermal comfort in a stratum-ventilated environmental chamber. Overall thermal sensation (OTS), local thermal sensation (LTS) of body segments, overall thermal comfort (OTC) and draft were investigated. The objectives of this study were twofold: to evaluate the effect of room temperature on thermal comfort (Test Series 1) and to assess the effect of supply airflow rate and supply air temperature on thermal comfort (Test Series 2). Test Series 1 revealed that the room temperature had a great impact on the OTS, LTS, OTC and draft. Under 10 air change per hour (ACH), a room temperature of 27 degrees C provided neutral OTS, satisfactory OTC and low draft risk. However, at room temperatures of 24 and 29 degrees C, the percentages of subjects feeling comfortable were obviously less than 80%. Test Series 2 showed that at the room temperature of 27 degrees C, increasing the supply airflow rate from 7 ACH to 17 ACH only exhibited a small influence on the thermal sensation and draft, indicating a preference for air movement. More than 80% subjects felt comfortable at 27 degrees C. However, to minimize draft complaints, the supply air temperature should not be below 20 degrees C. These results show that stratum ventilation provides a thermally comfortable environment, so that people can have the feeling of "cool head and warm feet", with low draft risk at a room temperature up to 27 degrees C. (C) 2015 Elsevier Ltd. All rights reserved.
引用
收藏
页码:269 / 277
页数:9
相关论文
共 50 条
  • [1] Optimization of room air temperature in stratum-ventilated rooms for both thermal comfort and energy saving
    Zhang, Sheng
    Cheng, Yong
    Fang, Zhaosong
    Huan, Chao
    Lin, Zhang
    [J]. APPLIED ENERGY, 2017, 204 : 420 - 431
  • [2] Uniformity of stratum-ventilated thermal environment and thermal sensation
    Cheng, Y.
    Fong, M. L.
    Yao, T.
    Lin, Z.
    Fong, K. F.
    [J]. INDOOR AIR, 2014, 24 (05) : 521 - 532
  • [3] Development of a nodal model for predicting the vertical temperature profile in a stratum-ventilated room
    Huan, Chao
    Wang, Fenghao
    Wu, Xiaozhou
    Lin, Zhang
    Ma, Zhenjun
    Wang, Zhihua
    [J]. ENERGY AND BUILDINGS, 2018, 159 : 99 - 108
  • [4] Technical feasibility of a stratum-ventilated room for multiple rows of occupants
    Cheng, Yong
    Lin, Zhang
    [J]. BUILDING AND ENVIRONMENT, 2015, 94 : 580 - 592
  • [5] The impact of temperature on mean local air age and thermal comfort in a stratum ventilated office
    Tian, Lin
    Lin, Zhang
    Liu, Jing
    Yao, Ting
    Wang, Qiuwang
    [J]. BUILDING AND ENVIRONMENT, 2011, 46 (02) : 501 - 510
  • [6] The effect of temperature, metabolic rate and dynamic localized airflow on thermal comfort
    Ugursal, Ahmet
    Culp, Charles H.
    [J]. APPLIED ENERGY, 2013, 111 : 64 - 73
  • [7] Experimental investigation into the interaction between the human body and room airflow and its effect on thermal comfort under stratum ventilation
    Cheng, Y.
    Lin, Z.
    [J]. INDOOR AIR, 2016, 26 (02) : 274 - 285
  • [8] Airflow and thermal comfort evaluation of a room with different outlet opening sizes and elevations ventilated by a two-sided wind catcher
    Goudarzi, Navid
    Sheikhshahrokhdehkordi, Mohammadamin
    Khalesi, Javad
    Hosseiniirani, Seyedehhamideh
    [J]. JOURNAL OF BUILDING ENGINEERING, 2021, 37
  • [9] Computational fluid dynamics simulation of thermal comfort in naturally ventilated room
    Raczkowski, Andrzej
    Suchorab, Zbigniew
    Brzyski, Przemyslaw
    [J]. III INTERNATIONAL CONFERENCE OF COMPUTATIONAL METHODS IN ENGINEERING SCIENCE (CMES 18), 2019, 252
  • [10] Effects of airflow rate and supply air temperature on the airflow pattern under active chilled beam system
    Wu, Bingjie
    Cai, Wenjian
    Chen, Haoran
    [J]. PROCEEDINGS OF THE 2018 13TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA 2018), 2018, : 1593 - 1598