Partial Discharge-induced Degradation Characteristics of Insulating Materials of Gas-filled Power Transformers

被引:9
|
作者
Okabe, Shigemitsu [1 ]
Ueta, Genyo [1 ]
Wada, Haruhisa [2 ]
Okubo, Hitoshi [3 ]
机构
[1] Tokyo Elect Power Co Ltd, Tsurumi Ku, Kanagawa 2308510, Japan
[2] Toshiba Co Ltd, Kawasaki Ku, Kanagawa 2100862, Japan
[3] Nagoya Univ, Dept Elect Engn & Comp Sci, Furo 4648603, Japan
关键词
Gas-filled power transformer; partial discharge (PD); polyethylene terephthalate (PET) film; Nomex (R) board; pressboard; residual impulse withstand voltage; harmful partial discharge level; insulation degradation;
D O I
10.1109/TDEI.2010.5658221
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The soundness of a transformer under an operating voltage is evaluated in partial discharge (PD) test of long-duration ac withstand voltage test. At present, the same criteria for evaluating oil-filled transformers are adopted as those for evaluating gas-filled transformers in this PD test. However, gas-filled transformers are made of different insulating materials than those for oil-filled transformers, and therefore they may have different strengths against PDs from oil-filled transformers. Therefore, it is necessary to establish PD evaluation criteria for gas-filled transformers. This paper, as the first step toward this objective, discusses the study of solid insulating materials used in gas-filled transformers in terms of the generated PD magnitudes and the degrees of damage of insulation and examines the harmful PD levels that lower the residual impulse withstand voltage. As a result, it identified the PD-induced degradation patterns of some insulating materials used in gas-filled transformers, i.e., polyethylene terephthalate (PET) films and Nomex (R) boards and evaluated the harmful PD levels based on the residual impulse withstand voltages. It was also verified that the insulations of pressboards are not degraded even by relatively large PDs.
引用
收藏
页码:1715 / 1723
页数:9
相关论文
共 50 条
  • [1] Partial Discharge-induced Degradation Characteristics of Insulating Structure Constituting Oil-immersed Power Transformers
    Okabe, Shigemitsu
    Ueta, Genyo
    Wada, Haruhisa
    Okubo, Hitoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (05) : 1649 - 1656
  • [2] Deterioration Characteristics Due to Partial Discharges in Insulating Structure Constituting Gas-filled Power Transformers
    Okabe, Shigemitsu
    Ueta, Genyo
    Wada, Haruhisa
    Okubo, Hitoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) : 1204 - 1213
  • [3] Partial Discharge-induced Degradation Characteristics of Oil-impregnated Insulating Material Used in Oil-immersed Power Transformers
    Okabe, Shigemitsu
    Ueta, Genyo
    Wada, Haruhisa
    Okubo, Hitoshi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2010, 17 (04) : 1225 - 1233
  • [4] Partial Discharge-induced Degradation Characteristics of Epoxy/TiO2 Nanocomposite
    Du, B. X.
    Zhang, J. W.
    Li, Jie
    Hu, W. J.
    Wu, Kai
    2011 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, 2011, : 676 - 679
  • [5] Partial discharge-induced crack growth in dielectric materials
    JiaCheng Luo
    CunFa Gao
    XiangHua Dai
    Science China Physics, Mechanics and Astronomy, 2010, 53 : 886 - 891
  • [7] Partial discharge-induced crack growth in dielectric materials
    Luo JiaCheng
    Gao CunFa
    Dai XiangHua
    SCIENCE CHINA-PHYSICS MECHANICS & ASTRONOMY, 2010, 53 (05) : 886 - 891
  • [8] Biological degradation of gas-filled composite materials on the base of polyethylene
    Grigoreva, E. A.
    Kolesnikova, N. N.
    Popov, A. A.
    Olkhov, A. A.
    INTERNATIONAL CONFERENCE MODERN TECHNOLOGIES AND MATERIALS OF NEW GENERATIONS, 2018, 286
  • [9] Innovation on energy power technology (9): Large capacity gas-filled transformers
    Toda, Katsutoshi
    IEEJ Transactions on Power and Energy, 2008, 128 (08) : 989 - 992
  • [10] Partial Discharge Signal Propagation Characteristics Inside the Winding of Gas-filled Power Transformer - Study Using the Equivalent Circuit of the Winding Model
    Okabe, Shigemitsu
    Ueta, Genyo
    Wada, Haruhisa
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (05) : 1668 - 1677