Industrial-scale investigations of anthracite combustion characteristics and NOx emissions in a retrofitted 300 MWe down-fired utility boiler with swirl burners

被引:35
|
作者
Chen, Zhichao [1 ]
Wang, Qingxiang [1 ]
Zhang, Xiaoyan [1 ]
Zeng, Lingyan [1 ]
Zhang, Xin [1 ]
He, Tao [1 ]
Liu, Tao [1 ]
Li, Zhengqi [1 ]
机构
[1] Harbin Inst Technol, Sch Energy Sci & Engn, 92 West Dazhi St, Harbin 150001, Heilongjiang, Peoples R China
基金
中国国家自然科学基金;
关键词
Down-fired boiler; Swirl burner; Overfire air ratio; Pulverized coal combustion; NOx emissions; AIR RATIO OPTIMIZATION; COAL COMBUSTION; MULTIPLE INJECTION; STAGED-AIR; FLOW; ANGLE; FIELD; TEMPERATURE; REDUCTION; LOCATION;
D O I
10.1016/j.apenergy.2017.05.138
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
To burn anthracite and reduce NOx emissions, a new combustion system was applied to a 300 MWe Babcock & Wilcox (B&W) down-fired boiler that included overfire air (OFA) and a decreased flow area of the inner and outer secondary air ducts of the installed swirl burners. Industrial-scale measurements (adjusting OFA ratios from 15.4% to 22.6%) were conducted to evaluate the overall performance of the retrofitted boiler. The experimental results demonstrated that the new combustion system promoted coal/air flow ignition and combustion stability. When the OFA ratio was less than 19.7%, the influence of the burner secondary air ratio on coal/air flow ignition was greater than that of the recirculation region below the arches. The overall combustion level in the primary combustion zone depended on the oxygen content and the recirculation region in the lower furnace instead of the early or late ignition of the coal/air flow. Oxygen and carbon monoxide concentration measurements in the near-sidewall region revealed that the fullness degree of the coal flame varied under different OFA ratios. Considering both environmental and economic effects, 19.7% was chosen as the optimal OFA ratio, thereby achieving a significant NOx reduction of 47% without increasing carbon content in the fly ash. (C) 2017 Elsevier Ltd. All rights reserved.
引用
收藏
页码:169 / 177
页数:9
相关论文
共 50 条
  • [1] Improved NOx Emissions and Combustion Characteristics for a Retrofitted Down-fired 300-MWe Utility Boiler
    Li, Zhengqi
    Ren, Feng
    Chen, Zhichao
    Liu, Guangkui
    Xu, Zhenxing
    [J]. ENVIRONMENTAL SCIENCE & TECHNOLOGY, 2010, 44 (10) : 3926 - 3931
  • [2] Influence of Staged-Air on Combustion Characteristics and NOx Emissions of a 300 MWe Down-Fired Boiler with Swirl Burners
    Li, Zhengqi
    Fan, Subo
    Liu, Guangkui
    Yang, Xuehai
    Chen, Zhichao
    Su, Wei
    Wang, Lin
    [J]. ENERGY & FUELS, 2010, 24 (01) : 38 - 45
  • [3] Anthracite combustion characteristics and NOx formation of a 300 MWe down-fired boiler with swirl burners at different loads after the implementation of a new combustion system
    Chen, Zhichao
    Wang, Qingxiang
    Wang, Bingnan
    Zeng, Lingyan
    Che, Miaomiao
    Zhang, Xin
    Li, Zhengqi
    [J]. APPLIED ENERGY, 2017, 189 : 133 - 141
  • [4] Asymmetric combustion characteristics and NOx emissions of a down-fired 300 MWe utility boiler at different boiler loads
    Kuang, Min
    Li, Zhengqi
    Zhang, Yan
    Chen, Xiachao
    Jia, Jinzhao
    Zhu, Qunyi
    [J]. ENERGY, 2012, 37 (01) : 580 - 590
  • [5] Industrial-scale Investigations on Combustion Characteristics and NO x Emissions of a 300-MWe Down-fired Boiler: Bituminous Coal Combustion and Coal Varieties Comparison
    Zhang, Xin
    Chen, Zhichao
    Li, Liankai
    Zeng, Lingyan
    Li, Zhengqi
    [J]. COMBUSTION SCIENCE AND TECHNOLOGY, 2022, 194 (15) : 3155 - 3174
  • [6] Combustion and NOx emission characteristics of a retrofitted down-fired 660 MWe utility boiler at different loads
    Li, Zhengqi
    Liu, Guangkui
    Zhu, Qunyi
    Chen, Zhichao
    Ren, Feng
    [J]. APPLIED ENERGY, 2011, 88 (07) : 2400 - 2406
  • [7] Effect of the anthracite ratio of blended coals on the combustion and NOx emission characteristics of a retrofitted down-fired 660-MWe utility boiler
    Liu, Guangkui
    Li, Zhengqi
    Chen, Zhichao
    Zhu, Xingying
    Zhu, Qunyi
    [J]. APPLIED ENERGY, 2012, 95 : 196 - 201
  • [8] Industrial Experiments on Anthracite Combustion and NOx Emissions with Respect to Swirling Secondary Air for a 300 MWe Deep-Air-Staged Down-Fired Utility Boiler
    Wang, Qingxiang
    Chen, Zhichao
    Liu, Tao
    Zeng, Lingyan
    Zhang, Xin
    Du, He
    Li, Zhengqi
    [J]. ENERGY & FUELS, 2018, 32 (07) : 7878 - 7887
  • [9] Promotion of Anthracite Burnout for a 300 MWe Down-Fired Boiler with a Novel Combustion Technology
    Wang, Qingxiang
    Chen, Zhichao
    Yan, Tianshu
    Liu, Tao
    Zeng, Lingyan
    Li, Zhengqi
    [J]. ENERGY & FUELS, 2018, 32 (11) : 11924 - 11935
  • [10] Influence of the Overfire Air Ratio on the NOx Emission and Combustion Characteristics of a down-Fired 300-MWe Utility Boiler
    Ren, Feng
    Li, Zhengqi
    Chen, Zhichao
    Fan, Subo
    Liu, Guangkui