Improved Demagnetization Control of a Doubly-Fed Induction Generator Under Balanced Grid Fault

被引:61
|
作者
Zhou, Linyuan [1 ]
Liu, Jinjun [1 ]
Zhou, Sizhan [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Elect Engn, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
基金
中国国家自然科学基金;
关键词
Demagnetization control; doubly-fed induction generator (DFIG); low-voltage ride-through (LVRT); DFIG WIND TURBINE; RIDE-THROUGH; VOLTAGE DIPS; CAPABILITY; SYSTEM; POWER;
D O I
10.1109/TPEL.2014.2382603
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Doubly-fed induction generators are one of the most popular machines for variable-speed wind turbine. However, they are very sensitive to grid fault since the stator is directly connected to the grid. This paper analyzes the low-voltage ride-through performance of a doubly-fed induction generator-based wind turbine under balanced grid fault. An improved demagnetization control, immune to system parameter variation, is proposed to shorten the dynamic process. The investigation shows that the proposed method increases the probability of a successful ride-through at the recovery moment of balanced grid fault. Feasibility region for a representatively sized system is also investigated for balanced grid fault. In order to verify the proposed control method, laboratory experiments are carried out and the results demonstrate the analysis.
引用
收藏
页码:6695 / 6705
页数:11
相关论文
共 50 条
  • [21] Transient analysis of grid connected Doubly-fed induction generator
    Bankar, D. S.
    Wadgaonkar, A. J.
    Hirve, S. S.
    Talange, D. B.
    [J]. 2015 INTERNATIONAL CONFERENCE ON INDUSTRIAL INSTRUMENTATION AND CONTROL (ICIC), 2015, : 1278 - 1283
  • [22] High Order Sliding Mode Control of Doubly-fed Induction Generator under Unbalanced Grid Faults
    Zhu, Rongwu
    Chen, Zhe
    Wu, Xiaojie
    Liu, Hongzhi
    [J]. 39TH ANNUAL CONFERENCE OF THE IEEE INDUSTRIAL ELECTRONICS SOCIETY (IECON 2013), 2013, : 1662 - 1667
  • [23] Open switch fault diagnosis for a doubly-fed induction generator
    Sae-Kok, W.
    Grant, D. M.
    [J]. 2007 INTERNATIONAL CONFERENCE ON POWER ELECTRONICS AND DRIVE SYSTEMS, VOLS 1-4, 2007, : 368 - +
  • [24] An improved fault current calculation method and protection scheme of Doubly-fed Induction Generator
    Yin, Jun
    [J]. ENERGY REPORTS, 2021, 7 : 5168 - 5174
  • [25] The Research on the Characteristic of Fault Current of Doubly-Fed Induction Generator
    Ao-Yang, Han
    Zhe, Zhang
    Xiang-Gen, Yin
    [J]. 2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 947 - 950
  • [26] An Improved Droop Control Scheme of a Doubly-Fed Induction Generator for Various Disturbances
    Xu, Yien
    Chen, Pei
    Zhang, Xinsong
    Yang, Dejian
    [J]. ENERGIES, 2021, 14 (23)
  • [27] Additive and multiplicative fault diagnosis for a doubly-fed induction generator
    Boulkroune, Boulaid
    Galvez-Carrillo, Manuel
    Kinnaert, Michel
    [J]. 2011 IEEE INTERNATIONAL CONFERENCE ON CONTROL APPLICATIONS (CCA), 2011, : 1302 - 1308
  • [28] Sliding mode control of a doubly-fed induction generator
    Patin, N.
    Naassani, A.
    Monmasson, Eric
    Louis, J. -P.
    [J]. 2007 EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS, VOLS 1-10, 2007, : 3544 - +
  • [29] A POWER CONTROL SCHEME FOR DOUBLY-FED INDUCTION GENERATOR
    Sguarezi Filho, Alfeu J.
    Oliveira Filho, M. E.
    Ruppert, Ernesto
    [J]. 2009 BRAZILIAN POWER ELECTRONICS CONFERENCE, VOLS 1 AND 2, 2009, : 1 - 8
  • [30] Intelligent control of a brushless doubly-fed induction generator
    Tir, Zoheir
    Malik, Om P.
    Hashemnia, Mohammad Naser
    [J]. INTERNATIONAL JOURNAL OF SYSTEM ASSURANCE ENGINEERING AND MANAGEMENT, 2019, 10 (03) : 326 - 338