On-Line Partial Discharge Monitoring System for Power Transformers Based on the Simultaneous Detection of High Frequency, Ultra-High Frequency, and Acoustic Emission Signals

被引:24
|
作者
Sikorski, Wojciech [1 ]
Walczak, Krzysztof [1 ]
Gil, Wieslaw [2 ]
Szymczak, Cyprian [1 ]
机构
[1] Poznan Univ Tech, Inst Elect Power Engn, PL-60965 Poznan, Poland
[2] Mikronika, PL-60001 Poznan, Poland
关键词
power transformer; partial discharge (PD); on-line PD monitoring system; active dielectric window; acoustic emission; UHF antenna; PIFA; HFCT sensor; UHF SENSORS; FRACTAL ANTENNA; BAND ANTENNA; PIFA; BIOTELEMETRY; BANDWIDTH; CELLULOSE; LOCATION; DESIGN; TRENDS;
D O I
10.3390/en13123271
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The article presents a novel on-line partial discharge (PD) monitoring system for power transformers, whose functioning is based on the simultaneous use of three unconventional methods of PD detection: high-frequency (HF), ultra-high frequency (UHF), and acoustic emission (AE). It is the first monitoring system equipped in an active dielectric window (ADW), which is a combined ultrasonic and electromagnetic PD sensor. The article discusses in detail the process of designing and building individual modules of hardware and software layers of the system, wherein the most attention was paid to the PD sensors, i.e., meandered planar inverted-F antenna (MPIFA), high-frequency current transformer (HFCT), and active dielectric window with ultrasonic transducer, which were optimized for detection of PDs occurring in oil-paper insulation. The prototype of the hybrid monitoring system was first checked on a 330 MVA large power transformer during the induced voltage test with partial discharge measurement (IVPD). Next, it was installed on a 31.5 MVA substation power transformer and integrated according to the standard IEC 61850 with SCADA (Supervisory Control and Data Acquisition) system registering voltage, active power, and oil temperature of the monitored unit. The obtained results showed high sensitivity of the manufactured PD sensors as well as the advantages of the simultaneous use of three techniques of PD detection and the possibility of discharge parameter correlation with other power transformer parameters.
引用
下载
收藏
页数:37
相关论文
共 50 条
  • [31] A Novel Partial Discharge Detection Method for Power Transformers on Site Adopting its Component as Ultra-High Frequency Sensor (vol 34, pg 2269, 2019)
    Zhang, Xuanrui
    Shi, Minxia
    Cai, Jun
    Li, Junhao
    IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (02) : 1058 - 1058
  • [32] Study on the ultra-high-frequency discharge signals of typical PD models in transformers
    Wang, Guoli
    Yuan, Peng
    Shan, Ping
    Hao, Yanpeng
    Li, Yanming
    Wang, Kun
    Zhang, Jiangang
    2002, Science Press (28):
  • [33] High frequency modeling of protection/measurement current transformers for partial discharge detection
    Mohamed, Faisal Peer
    Siew, W. H.
    Soraghan, John
    UPEC: 2009 44TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE, 2009, : 523 - 527
  • [34] Ultra-High Frequency Surface Acoustic Wave Sensors for Temperature Detection
    Dong, Qi
    Yang, Qutong
    Liu, Xiaoyang
    Hu, Shenghe
    Nie, Wenzhe
    Jiang, Zhao
    Fan, Xiaoming
    Luo, Jingting
    Tao, Ran
    Fu, Chen
    MICROMACHINES, 2024, 15 (01)
  • [35] Study on Ultra-high Frequency Partial Discharge Simulator and its Propagation Characteristics
    An, Dawei
    Du, Lin
    Liu, Shuncheng
    Wu, Xiong
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [36] A novel type of ultra-high frequency sensor for partial discharge source location
    Ye, H.F.
    Qian, Y.
    Sheng, G.H.
    Li, X.W.
    Jiang, X.C.
    Australian Journal of Electrical and Electronics Engineering, 2014, 11 (02): : 144 - 152
  • [37] Design of External Ultra-high Frequency Partial Discharge Sensor for Large Transformer
    Zhang X.
    Zhang J.
    Xiao S.
    Gaodianya Jishu/High Voltage Engineering, 2019, 45 (02): : 499 - 504
  • [38] Research on partial discharge location method based on PRPD statistic parameters of ultra-high frequency
    Peng, Chao, 1600, Editorial Department of Electric Machines and Control (18):
  • [39] Propagation characteristic of partial discharge ultra high frequency signals outside transformer
    School of Electrical Engineering, Xi'an Jiaotong University, Xi'an 710049, China
    Hsi An Chiao Tung Ta Hsueh, 2008, 6 (718-722):
  • [40] Detection and Analysis of Partial Discharge using Ultra High Frequency Sensor
    Reddy, P. Gurumurthy
    Kundu, Prasanta
    2014 ANNUAL INTERNATIONAL CONFERENCE ON EMERGING RESEARCH AREAS: MAGNETICS, MACHINES AND DRIVES (AICERA/ICMMD), 2014,