On-Line Partial Discharge Monitoring System for Power Transformers Based on the Simultaneous Detection of High Frequency, Ultra-High Frequency, and Acoustic Emission Signals

被引:24
|
作者
Sikorski, Wojciech [1 ]
Walczak, Krzysztof [1 ]
Gil, Wieslaw [2 ]
Szymczak, Cyprian [1 ]
机构
[1] Poznan Univ Tech, Inst Elect Power Engn, PL-60965 Poznan, Poland
[2] Mikronika, PL-60001 Poznan, Poland
关键词
power transformer; partial discharge (PD); on-line PD monitoring system; active dielectric window; acoustic emission; UHF antenna; PIFA; HFCT sensor; UHF SENSORS; FRACTAL ANTENNA; BAND ANTENNA; PIFA; BIOTELEMETRY; BANDWIDTH; CELLULOSE; LOCATION; DESIGN; TRENDS;
D O I
10.3390/en13123271
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The article presents a novel on-line partial discharge (PD) monitoring system for power transformers, whose functioning is based on the simultaneous use of three unconventional methods of PD detection: high-frequency (HF), ultra-high frequency (UHF), and acoustic emission (AE). It is the first monitoring system equipped in an active dielectric window (ADW), which is a combined ultrasonic and electromagnetic PD sensor. The article discusses in detail the process of designing and building individual modules of hardware and software layers of the system, wherein the most attention was paid to the PD sensors, i.e., meandered planar inverted-F antenna (MPIFA), high-frequency current transformer (HFCT), and active dielectric window with ultrasonic transducer, which were optimized for detection of PDs occurring in oil-paper insulation. The prototype of the hybrid monitoring system was first checked on a 330 MVA large power transformer during the induced voltage test with partial discharge measurement (IVPD). Next, it was installed on a 31.5 MVA substation power transformer and integrated according to the standard IEC 61850 with SCADA (Supervisory Control and Data Acquisition) system registering voltage, active power, and oil temperature of the monitored unit. The obtained results showed high sensitivity of the manufactured PD sensors as well as the advantages of the simultaneous use of three techniques of PD detection and the possibility of discharge parameter correlation with other power transformer parameters.
引用
收藏
页数:37
相关论文
共 50 条
  • [1] Recognition of single and multiple partial discharge sources in transformers based on ultra-high frequency signals
    Sinaga, Herman H.
    Phung, B. T.
    Blackburn, Trevor R.
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2014, 8 (01) : 160 - 169
  • [2] Study of the Influence of Winding and Sensor Design on Ultra-High Frequency Partial Discharge Signals in Power Transformers
    Beura, Chandra Prakash
    Beltle, Michael
    Tenbohlen, Stefan
    SENSORS, 2020, 20 (18) : 1 - 17
  • [3] Application of ultra-high-frequency partial discharge detection in power transformers
    Zhao, Xiao-Hui
    Lu, Xiu-Li
    Yang, Jing-Gang
    Yuan, Peng
    Li, Yan-Ming
    Gaodianya Jishu/High Voltage Engineering, 2007, 33 (08): : 111 - 114
  • [4] Design of a compact ultra-high frequency antenna for partial discharge detection in oil immersed power transformers
    Salah, Walid S. S.
    Gad, Ahmed H. H.
    Attia, Mahmoud A. A.
    Eldebeikey, Soliman M. M.
    Salama, Abdelhady R. R.
    AIN SHAMS ENGINEERING JOURNAL, 2022, 13 (02)
  • [5] Simulation of the Propagation Characteristic of Ultra High Frequency Signals Excited by Partial Discharge in Power Transformers
    Xu, Bin
    Li, Yanming
    Li, Junhao
    Zhao, Junhong
    Wang, Xinjun
    2015 CHINESE AUTOMATION CONGRESS (CAC), 2015, : 1209 - 1210
  • [6] Partial discharge monitoring system based on ultra-high frequency method and pulse current method
    Gan, Degang
    Liu, Fan
    Xiao, Wei
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2013, 33 (03): : 162 - 165
  • [7] An Intelligent Sensor for the Ultra-High-Frequency Partial Discharge Online Monitoring of Power Transformers
    Li, Jian
    Li, Xudong
    Du, Lin
    Cao, Min
    Qian, Guochao
    ENERGIES, 2016, 9 (05)
  • [8] A Novel Partial Discharge Detection Method for Power Transformers On Site Adopting Its Component as Ultra-High Frequency Sensor
    Zhang, Xuanrui
    Shi, Minxia
    Cai, Jun
    Li, Junhao
    IEEE TRANSACTIONS ON POWER DELIVERY, 2019, 34 (06) : 2269 - 2271
  • [9] Drawing Method of Frequency Division Fault Maps for GIS Partial Discharge Based on Ultra-high Frequency Signals
    Zhang, Xiao-Lan
    Huang, Guo-Qiang
    Qi, Wei-Dong
    Wu, Jing-Feng
    Niu, Bo
    Wang, Jing
    2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [10] Special Requirements of High Frequency Current Transformers in the On-Line Detection of Partial Discharges in Power Cables
    Xu, Yang
    Gu, Xiao
    Liu, Bin
    Hui, Baojun
    Ren, Zhigang
    Meng, Shaoxin
    IEEE ELECTRICAL INSULATION MAGAZINE, 2016, 32 (06) : 8 - 19