Experimental analysis of dehumidification performance of an evaporative cooling-assisted internally cooled liquid desiccant dehumidifier

被引:38
|
作者
Park, Joon-Young [1 ]
Kim, Beom-Jun [1 ]
Yoon, Soo-Yeol [1 ]
Byon, Yoo-Suk [1 ]
Jeong, Jae-Weon [1 ]
机构
[1] Hanyang Univ, Coll Engn, Dept Architectural Engn, 222 Wangsimni Ro, Seoul 04763, South Korea
基金
新加坡国家研究基金会;
关键词
Dehumidification system; Internally cooled liquid desiccant system; Desiccant cooling; Evaporative cooling; MASS-TRANSFER PROCESSES; HEAT; MODEL;
D O I
10.1016/j.apenergy.2018.10.101
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The aim of this study is to empirically investigate the impact of the working-to-primary air flow ratio variation on the dehumidification performance of an evaporative cooling-assisted internally cooled liquid desiccant dehumidifier. In the experiment, the process air passed through the primary (or dehumidification) channels of the internally cooled liquid desiccant dehumidifier at a constant flow rate, while the working air flow passing through the secondary (or evaporative cooling) channels was modulated to vary the working-to-primary air flow ratio from 0.25 to 1.0 in 0.25 increments. To evaluate the impact of the working-to-primary air flow ratio on the dehumidification and cooling performance of the internally cooled liquid desiccant dehumidifier, four different performance indices, i.e., cooling capacity, wet-bulb effectiveness, volumetric mass transfer coefficient, and coefficient of performance, were measured in a series of experiments performed under various working-to primary air flow ratios. From those performance indicators, the overall heat, mass transfer performance, and energy efficiency of the internally cooled liquid desiccant dehumidifier could be rated. The experimental results indicate that the maximum values of the four selected performance indices are obtained at a working-to-primary air flow ratio of 0.5. To verify the reliability of the experimental results, a detailed simulation of the internally cooled liquid desiccant dehumidifier was performed using a sorption system simulation program (SorpSim). The measured performance data was in good agreement with the simulation results, within 20% error bounds. Consequently, we determined that the optimal dehumidification and cooling performance of the internally cooled liquid desiccant dehumidifier could be expected when the working-to-primary air flow ratio is 0.5.
引用
收藏
页码:177 / 185
页数:9
相关论文
共 50 条
  • [21] Quick performance prediction for internally cooled/heated liquid desiccant dehumidification system
    Qi, Ronghui
    Lu, Lin
    Yang, Hongxing
    BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2014, 35 (01): : 99 - 112
  • [22] Performance of heat pump driven internally cooled liquid desiccant dehumidification system
    Liu, Jun
    Liu, Xiaohua
    Zhang, Tao
    ENERGY CONVERSION AND MANAGEMENT, 2020, 205
  • [23] Experimental study on a new internally cooled/heated dehumidifier/regenerator of liquid desiccant systems
    Yin, Yonggao
    Zhang, Xiaosong
    Wang, Geng
    Luo, Lei
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (05): : 857 - 866
  • [24] Experimental study on partially internally cooled dehumidification in liquid desiccant air conditioning system
    Gao, W. Z.
    Shi, Y. R.
    Cheng, Y. P.
    Sun, W. Z.
    ENERGY AND BUILDINGS, 2013, 61 : 202 - 209
  • [25] Study on an internally-cooled liquid desiccant dehumidifier with CFD model
    Luo, Yimo
    Chen, Yi
    Yang, Hongxing
    Wang, Yuanhao
    APPLIED ENERGY, 2017, 194 : 399 - 409
  • [26] Performance study of the internally-cooled ultrasonic atomization liquid desiccant dehumidification system
    Yang, Zili
    Tao, Ruiyang
    Ni, Hui
    Zhong, Ke
    Lian, Zhiwei
    ENERGY, 2019, 175 : 745 - 757
  • [27] Experimental analysis of an internally-cooled/heated liquid desiccant dehumidifier/regenerator made of thermally conductive plastic
    Liu, Jun
    Zhang, Tao
    Liu, Xiaohua
    Jiang, Jingjing
    ENERGY AND BUILDINGS, 2015, 99 : 75 - 86
  • [28] Investigation on solar assisted liquid desiccant dehumidifier and evaporative cooling system for fresh air treatment
    Chen, Yi
    Yang, Hongxing
    Luo, Yimo
    ENERGY, 2018, 143 : 114 - 127
  • [29] Performance analysis of an internally-cooled plate membrane liquid desiccant dehumidifier (IMLDD): An analytical solution approach
    Huang, Si-Min
    Yang, Minlin
    Hu, Bing
    Tao, Shi
    Qin, Frank G. F.
    Weng, Wanliang
    Wang, Wenhao
    Liu, Jian
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2018, 119 : 577 - 585
  • [30] Energy Performance of Liquid Desiccant and Evaporative Cooling-Assisted 100% Outdoor Air Systems under Various Climatic Conditions
    Li, Shiying
    Jeong, Jae-Weon
    ENERGIES, 2018, 11 (06):