Analysis of energy saving potential of air-side free cooling for data centers in worldwide climate zones

被引:130
|
作者
Lee, Kuei-Peng [1 ]
Chen, Hsiang-Lun [2 ]
机构
[1] Natl Taipei Univ Technol, Dept Energy & Refrigerating Air Conditioning Engn, Taipei 106, Taiwan
[2] Natl Taipei Univ Technol, Grad Inst Mech & Elect Engn, Taipei 106, Taiwan
关键词
Free cooling; Data center; Economizer; Energy saving; Energy simulation; Energy efficiency; Consumption; COMMERCIAL BUILDINGS;
D O I
10.1016/j.enbuild.2013.04.013
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Based on the climate classification of ASHRAE 90.1 and the required operating environment conditions for data centers suggested by the ASHRAE Technical Committee TC 9.9, a dynamic building energy simulation program was used to examine the potential energy savings of the air-side free cooling technology with differential enthalpy control used in data centers in 17 climate zones. The results showed that significant free cooling potential was achieved in data centers located in mixed-humid, warm-marine, and mixed-marine climate zones. Because significant humidification is required to adjust outdoor air in climate zones with a lower dew point temperature, such as very-cold, subarctic, cool-dry, and cold-dry climate zones, the power consumed is even higher. Although the cooling degree day (CDD) and heating degree day (HDD) are key factors of climate classification and air conditioning energy consumption, they are not entirely correlated to the specific operating environment conditions of data centers. The results of this study showed that for every 2 degrees C decline in the indoor temperature of a data center, the energy saving of free cooling technology may decrease by 2.8-8.5%. The rate of decline varies in different climate zones. (C) 2013 Elsevier B.V. All rights reserved.
引用
收藏
页码:103 / 112
页数:10
相关论文
共 50 条
  • [1] Energy saving potential of various air-side economizers in a modular data center
    Ham, Sang-Woo
    Kim, Min-Hwi
    Choi, Byung-Nam
    Jeong, Jae-Weon
    [J]. APPLIED ENERGY, 2015, 138 : 258 - 275
  • [2] Factor Analysis of Power-saving Effects in Air-side Economizers for Data Centers
    Tate, Ryuhei
    Kaneko, Shinichiro
    Mino, Yosuke
    Yanagi, Masahide
    [J]. 2015 IEEE INTERNATIONAL TELECOMMUNICATIONS ENERGY CONFERENCE (INTELEC), 2015,
  • [3] Meteorological Assessment and Implementation of an Air-Side Free-Cooling System for Data Centers in Chile
    Diaz, Andres J.
    Neves, Gisella
    Silva-Llanca, Luis
    del Valle, Marcelo
    Cardemil, Jose M.
    [J]. PROCEEDINGS OF THE 2017 SIXTEENTH IEEE INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS ITHERM 2017, 2017, : 943 - 947
  • [4] Energy savings in direct air-side free cooling data centers: A cross-system modeling and optimization framework
    Zhou, Yongcheng
    Li, Shuangxiu
    Li, Qiang
    Wei, Fanchao
    Yang, Dazhi
    Liu, Jinfu
    Yu, Daren
    [J]. ENERGY AND BUILDINGS, 2024, 308
  • [5] Worldwide Energy Analysis of Major Free Cooling Methods for Data Centers
    Gozcu, Ozan
    Ozada, Berk
    Carfi, Muhammed Ugur
    Erden, Hamza Salih
    [J]. PROCEEDINGS OF THE 2017 SIXTEENTH IEEE INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS ITHERM 2017, 2017, : 968 - 976
  • [6] The Energy-Saving Potential of Air-Side Economisers in Modular Data Centres: Analysis of Opportunities and Risks in Different Climates
    Badiei, Ali
    Jadowski, Eric
    Sadati, Saba
    Beizaee, Arash
    Li, Jing
    Khajenoori, Leila
    Nasriani, Hamid Reza
    Li, Guiqiang
    Xiao, Xin
    [J]. SUSTAINABILITY, 2023, 15 (14)
  • [7] Energy Efficiency Analysis of Data Center Based on All-Inverter Coupled Air-Side Free Cooling Technology
    Ai, Chuanxian
    Chen, Yinghu
    Zhang, Liang
    [J]. 2023 5TH ASIA ENERGY AND ELECTRICAL ENGINEERING SYMPOSIUM, AEEES, 2023, : 61 - 69
  • [8] Radiative free cooling for energy and water saving in data centers
    Aili, Ablimit
    Long, Wenjun
    Cao, Zhiwei
    Wen, Yonggang
    [J]. APPLIED ENERGY, 2024, 359
  • [9] Energy saving analysis of evaporative cooling composite air conditioning system for data centers
    Han, Zongwei
    Sun, Xiaoqing
    Wei, Haotian
    Ji, Qiang
    Xue, Da
    [J]. APPLIED THERMAL ENGINEERING, 2021, 186
  • [10] Analysis of Air-Side Economizers in Terms of Cooling-Energy Performance in a Data Center Considering Exhaust Air Recirculation
    Park, Seonghyun
    Seo, Janghoo
    [J]. ENERGIES, 2018, 11 (02)