Operation Mode and Energy Consumption Analysis of a New Energy Tower and Ground Source-Coupled Heat Pump System

被引:0
|
作者
Zhang, Yao [1 ]
Wu, Ronghua [1 ]
Yu, Hao [2 ]
Yang, Yujuan [1 ]
Zhan, Hao [2 ]
机构
[1] Qingdao Univ, Coll Mech & Elect Engn, Qingdao 266071, Peoples R China
[2] Qingdao KC Blue New Energy Co Ltd, Qingdao 266000, Peoples R China
关键词
energy tower; ground source heat pump; coupled system; energy consumption analysis; PERFORMANCE;
D O I
10.3390/en16186493
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
In order to solve the problems of performance degradation in energy tower heat pump (ETHP) systems under low temperature conditions and soil heat imbalances in ground source heat pump (GSHP) systems in cold regions, a new coupled system of ETHP and GSHP systems (the ET-GSHP system) and its operating mode were proposed. The mathematical model of the system was constructed along with the system's form and operation scheme. The COP (coefficient of performance) and total energy consumption of the coupled system were then simulated and studied under a number of common operating situations. The heating season is divided into four periods based on varying outdoor ambient temperatures: the first period operates in series mode and has an average outdoor temperature of 2.38 & DEG;C; the second period operates in parallel mode and has an average outdoor temperature of -8.56 & DEG;C; the third period uses soil source heat pumps to operate separately; and the fourth period operates in series mode and has an average outdoor temperature of -11.32 & DEG;C. Operation of the coupled system in four periods was simulated and analyzed, and the operational efficiency and energy saving of the system were analyzed using an actual commercial building in a cold region as an example. The results demonstrate that the ET-GSHP system's overall energy consumption during the heating period is reduced by 4.34% when compared to the traditional GSHP systems; the system's COP can maintain a high level throughout the heating period, with an average COP of 3.315; and the soil temperature at the conclusion of the heating period is 25 & DEG;C, which is 8.89 & DEG;C higher than that of the traditional GSHP system, providing a guarantee of summer heat return. The new ET-GSHP system significantly boosts the efficiency of the system's operation, achieves effective coupling between various heat sources through multi-stage control, and offers improved energy-saving advantages.
引用
收藏
页数:20
相关论文
共 50 条
  • [21] Regulation for energy-saving operation of energy supply system in plant factory with energy-storage ground-source heat pump
    Shi H.
    An W.
    Xu D.
    Tian Q.
    Zhang Z.
    Ren Y.
    Ouyang S.
    1600, Chinese Society of Agricultural Engineering (36): : 245 - 251
  • [22] Energy assessment of solar technologies coupled with a ground source heat pump system for residential energy supply in Southern European climates
    Reda, Francesco
    Arcuri, Natale
    Loiacono, Pasquale
    Mazzeo, Domenico
    ENERGY, 2015, 91 : 294 - 305
  • [23] Performance Analysis of the Coupled Heating System of the Air-Source Heat Pump, the Energy Accumulator and the Water-Source Heat Pump
    Zhou, Wenhe
    Wang, Bin
    Wang, Meng
    Chen, Yuying
    ENERGIES, 2022, 15 (19)
  • [24] SIMULATION AND ANALYSIS OF DYNAMIC ENERGY CONSUMPTION OF A SEAWATER SOURCE HEAT PUMP
    Hu, Songtao
    Cao, Yu
    Liu, Kai
    Wang, Gang
    Song, Wei
    FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS, 2009, : 2011 - 2017
  • [25] Thermal Comfort Assessment and Energy Consumption Analysis about the System of Ground Source Heat Pump Combined with Radiant Heating/Cooling
    Lu, Shikui
    Lv, Yan
    Zhang, Xiaosong
    6TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATING AND AIR CONDITIONING, VOLS I-III, PROCEEDINGS, 2009, : 1158 - 1166
  • [26] Thermal comfort assessment and energy consumption analysis of ground-source heat pump system combined with radiant heating/cooling
    Lu, Shikui
    Zhang, Xiaosong
    Journal of Southeast University (English Edition), 2012, 28 (01) : 52 - 57
  • [27] Ground-Coupled Heat Pump and Energy Storage
    Lohrenz, Ed
    Almeida, Sergio
    ASHRAE JOURNAL, 2013, 55 (04) : 14 - +
  • [29] Energy and Exergy Analysis of a Ground Water Heat Pump System
    Lei Fei
    Hu Pingfang
    INTERNATIONAL CONFERENCE ON APPLIED PHYSICS AND INDUSTRIAL ENGINEERING 2012, PT A, 2012, 24 : 169 - 175
  • [30] CFD assessment of multiple energy piles for ground source heat pump in heating mode
    Cui, Yuanlong
    Zhu, Jie
    APPLIED THERMAL ENGINEERING, 2018, 139 : 99 - 112