Energy and Exergy Analysis of a Ground Water Heat Pump System

被引:8
|
作者
Lei Fei [1 ]
Hu Pingfang [1 ]
机构
[1] Huazhong Univ Sci & Technol, Sch Environm Sci & Engn, Wuhan 430074, Peoples R China
关键词
Energy analysis; Exergy analysis; groundwater heat pump; coefficient of performance; residential building;
D O I
10.1016/j.phpro.2012.02.026
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
In the application of ground water source heat pump technology, energy saving considerations play an important role. The main objective of the present study is to investigate the performance characteristics of a groundwater heat pump system (GWHP) on the actual operation, using the energy and exergy analysis method. The system was installed in a apartment buildings of Wuhan, China. In the duration of one year, various operating parameters of the system were monitored and the coefficient of performance (COP) values of system and chiller is determined based on a series of measurements. The exergy transports and destruction between the components of the system are determined for the average measured parameters obtained from the experimental results. Inefficient facts are found out. Lower approach temperature is effective energy saving. In addition to the energy analysis, a full exergy analysis helps to identify the components where inefficiencies occur. (c) 2011 Published by Elsevier B.V. Selection and/or peer-review under responsibility of ICAPIE Organization Committee.
引用
收藏
页码:169 / 175
页数:7