Validation of virtual sensor-assisted Bayesian inference-based in-situ sensor calibration strategy for building HVAC systems

被引:22
|
作者
Li, Guannan [1 ]
Xiong, Jiahao [1 ]
Sun, Shaobo [2 ]
Chen, Jian [1 ]
机构
[1] Wuhan Univ Sci & Technol, Sch Urban Construct, Wuhan 430065, Peoples R China
[2] Hong Kong Polytech Univ, Dept Bldg Environm & Energy Engn, Hong Kong, Peoples R China
基金
中国国家自然科学基金;
关键词
heating; ventilation and air-conditioning (HVAC); in-situ sensor calibration; Bayesian inference (BI); virtual sensor (VS); influencing factor; energy conservation (EC); FAULT-DIAGNOSIS METHOD; TOLERANT CONTROL; NEURAL-NETWORK; HIDDEN FACTORS; ENERGY MODELS; ACCURACY; PREDICTION; REGRESSION;
D O I
10.1007/s12273-022-0935-7
中图分类号
O414.1 [热力学];
学科分类号
摘要
For building heating, ventilation and air-conditioning systems (HVACs), sensor faults significantly affect the operation and control. Sensors with accurate and reliable measurements are critical for ensuring the precise indoor thermal demand. Owing to its high calibration accuracy and in-situ effectiveness, a virtual sensor (VS)-assisted Bayesian inference (VS-BI) sensor calibration strategy has been applied for HVACs. However, the application feasibility of this strategy for wider ranges of different sensor types (within-control-loop and out-of-control-loop) with various sensor bias fault amplitudes, and influencing factors that affect the practical in-situ calibration performance are still remained to be explored. Hence, to further validate its in-situ calibration performance and analyze the influencing factors, this study applied the VS-BI strategy in a HVAC system including a chiller plant with air handle unit (AHU) terminal. Three target sensors including air supply (SAT), chilled water supply (CHS) and cooling water return (CWR) temperatures are investigated using introduced sensor bias faults with eight different amplitudes of [-2 degrees C, +2 degrees C] with a 0.5 degrees C interval. Calibration performance is evaluated by considering three influencing factors: (1) performance of different data-driven VSs, (2) the influence of prior standard deviations sigma on in-situ sensor calibration and (3) the influence of data quality on in-situ sensor calibration from the perspective of energy conservation and data volumes. After comparison, a long short term memory (LSTM) is adopted for VS construction with determination coefficient R-squared of 0.984. Results indicate that sigma has almost no impact on calibration accuracy of CHS but scanty impact on that of SAT and CWR. The potential of using a prior standard deviation sigma to improve the calibration accuracy is limited, only 8.61% on average. For system within-control-loop sensors like SAT and CHS, VS-BI obtains relatively high in-situ sensor calibration accuracy if the data quality is relatively high.
引用
收藏
页码:185 / 203
页数:19
相关论文
共 47 条
  • [41] Elliptical torus-based Six-axis FBG Force Sensor with In-situ Calibration for Condition Monitoring of Orthopedic Surgical Robot
    Li, Tianliang
    Zhao, Chen
    Wen, Yuhang
    Chen, Fayin
    Tan, Yuegang
    Zhou, Zude
    2024 IEEE INTERNATIONAL CONFERENCE ON ROBOTICS AND AUTOMATION, ICRA 2024, 2024, : 3561 - 3566
  • [42] Highly selective capacitive micromachined ultrasonic transducer-based miniature gravimetric CO2 sensor with in-situ calibration for relative humidity
    Barauskas, Dovydas
    Pelenis, Donatas
    Dzikaras, Mindaugas
    Vanagas, Gailius
    Mikolaju, Marius
    Baltrusaitis, Jonas
    Virzonis, Darius
    SENSORS AND ACTUATORS B-CHEMICAL, 2023, 393
  • [43] Nonintrusive in-situ modeling for unobserved virtual models in digital twin-enabled building HVAC systems: A one-year comparison of data-driven and physics-based approaches in a living laboratory
    Li, Yuxin
    Lee, Jeyoon
    Li, Jiteng
    Wang, Peng
    Yoon, Sungmin
    JOURNAL OF BUILDING ENGINEERING, 2025, 101
  • [44] OPTIMIZATION OF WOOD COMBUSTION IN LOW-POWER FIRING SYSTEMS BY SENSOR-BASED OPERATION: HIGH TEMPERATURE CO/HC SENSOR FOR LONG-TERM IN-SITU OPERATION
    Kohler, Heinz
    Ojha, Binayak
    Zhang, Xin
    PAPERS OF THE 26TH EUROPEAN BIOMASS CONFERENCE: SETTING THE COURSE FOR A BIOBASED ECONOMY, 2018, : 428 - 429
  • [45] In-situ implementation and validation of a CO2-based adaptive demand-controlled ventilation strategy in a multi-zone office building
    Sun, Zhongwei
    Wang, Shengwei
    Ma, Zhenjun
    BUILDING AND ENVIRONMENT, 2011, 46 (01) : 124 - 133
  • [46] Micro-pillar sensor based wall-shear mapping in pulsating flows: In-situ calibration and measurements in an aortic heart-valve tester
    Li, Qianhui
    Stavropoulos-Vasilakis, Evangelos
    Koukouvinis, Phoevos
    Gavaises, Manolis
    Bruecker, Christoph H.
    JOURNAL OF FLUIDS AND STRUCTURES, 2021, 105
  • [47] A robust online refrigerant charge fault diagnosis strategy for VRF systems based on virtual sensor technique and PCA-EWMA method
    Liu, Jiangyan
    Li, Guannan
    Chen, Huanxin
    Wang, Jiangyu
    Guo, Yabin
    Li, Jiong
    APPLIED THERMAL ENGINEERING, 2017, 119 : 233 - 243