Single fuzzy inference based fault detection and classification protection scheme for different types of short circuit faults on double circuit transmission lines

被引:1
|
作者
Vikram Raju, Gotte [1 ]
Srikanth, Nandiraju Venkata [1 ]
机构
[1] Natl Inst Technol, Elect Engn Dept, Warangal 506004, Telangana, India
来源
关键词
Double circuit transmission lines; discrete fourier transform; protection scheme; fuzzy inference system; fault detection and classification; TRANSFORM; ALGORITHM; LOCATION; MACHINE; ANN;
D O I
10.1080/02286203.2023.2193912
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
An intelligent protection scheme based on the single fuzzy inference system and discrete Fourier transform is proposed for the faulty phase detection and classification of faults on the mutually coupled double circuit transmission lines. This proposed protection technique uses the magnitude of the pre-processed current information of the sending end bus only. This is implemented in the MATLAB/Simulink environment on a 400 kV, 50 Hz, and 300 km double circuit power system model. The efficacy of the proposed scheme has been tested by performing a wide range of simulation studies concerning different types of faults (common short circuit faults, cross-country and evolving faults, and high impedance faults) and typical fault scenarios (current transformer saturation, noisy environment, and fault during power swing conditions) with variations in different fault parameters and operating conditions. The results presented confirm that the proposed method detects/classifies all the faults within one cycle time and is reliable with a detection/classification accuracy of 99.75%. It is immune to variations in fault parameters, and different operating conditions, and is not affected by the zero sequence mutual impedance. It does not require any training and communication link. Further, the performance is also appraised with other training-based protection schemes.
引用
收藏
页码:218 / 236
页数:19
相关论文
共 50 条
  • [31] A distance Protection/Fault location algorithm for Double-Circuit transmission lines with asymmetrical circuits during Cross-Country faults
    Abdollahzadeh, Hamed
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2023, 148
  • [32] A non-unit protection scheme for double circuit series capacitor compensated transmission lines
    Swetapadma, Aleena
    Mishra, Praveen
    Yadav, Anamika
    Abdelaziz, Almoataz Y.
    ELECTRIC POWER SYSTEMS RESEARCH, 2017, 148 : 311 - 325
  • [33] Data mining applied to the electric power industry: Classification of short-circuit faults in transmission lines
    Morais, Jefferson
    Pires, Yomara
    Cardoso, Claudomir
    Klautau, Aldebaro
    PROCEEDINGS OF THE 7TH INTERNATIONAL CONFERENCE ON INTELLIGENT SYSTEMS DESIGN AND APPLICATIONS, 2007, : 943 - 948
  • [34] A high accuracy Fuzzy-Logic based fault classification ill double-circuit transmission corridors
    Oliveira, Ezequiel da Silva
    Anzai, Alexandre H.
    Gaspar, Wander Antunes
    2014 11TH IEEE/IAS INTERNATIONAL CONFERENCE ON INDUSTRY APPLICATIONS (INDUSCON), 2014,
  • [35] Classification of short circuit faults causing voltage sags based on double dq transformation
    Du, Xiong
    Zhou, Luowei
    Xu, Kefu
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2010, 34 (05): : 86 - 90
  • [36] DISTANCE-PROTECTION PERFORMANCE UNDER CONDITIONS OF SINGLE-CIRCUIT WORKING IN DOUBLE-CIRCUIT TRANSMISSION LINES
    HUMPAGE, WD
    KANDIL, MS
    PROCEEDINGS OF THE INSTITUTION OF ELECTRICAL ENGINEERS-LONDON, 1970, 117 (04): : 766 - &
  • [37] A new protection scheme for fault detection, direction discrimination, classification, and location in transmission lines
    Jiang, JA
    Chen, CS
    Liu, CW
    IEEE TRANSACTIONS ON POWER DELIVERY, 2003, 18 (01) : 34 - 42
  • [38] Protection Scheme based on Fault Detection and Fault Classification using Fuzzy inference system in IEEE-9 Bus System
    Patel, Aditya
    Prashant, M. V. S.
    Sahu, Jharna
    Kujur, Ancy Prerena
    Verma, Sankalp
    2018 INTERNATIONAL CONFERENCE ON RECENT INNOVATIONS IN ELECTRICAL, ELECTRONICS & COMMUNICATION ENGINEERING (ICRIEECE 2018), 2018, : 626 - 638
  • [39] One-end impedance based fault location in double-circuit transmission lines with different configurations
    Ramar, K.
    Low, H. S.
    Ngu, E. E.
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2015, 64 : 1159 - 1165
  • [40] Single-Phase Grounding Fault Location Method Based on Iteration Thought for Double Circuit Transmission Lines
    Zhu, Yi Ming
    Zhou, Huan
    Gao, Xuan
    Proceedings of SPIE - The International Society for Optical Engineering, 2023, 12722