A distance Protection/Fault location algorithm for Double-Circuit transmission lines with asymmetrical circuits during Cross-Country faults

被引:0
|
作者
Abdollahzadeh, Hamed [1 ]
机构
[1] Islamic Azad Univ, Dept Elect Engn, East Tehran Branch, Tehran 1866113118, Iran
关键词
Distance protection; Fault location; Double -circuit lines with asymmetrical circuits; cross -country faults (CCFs); Fault distance estimation; vector-input adaptive linear combiner (VI-ALC); RELAYING SCHEME; IMPACT;
D O I
10.1016/j.ijepes.2022.108943
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The impedance-measuring elements and fault locators in distance relays suffer from measuring the correct fault impedance and fault location when facing cross-country faults (CCFs). During such atypical faults, this paper proposes a distance protection along with a fault location algorithm for double-circuit lines with asymmetrical circuits. This is fulfilled through instantaneous fault-branch currents innovatively derived from the line six-phase circuit model analysis on a time-domain basis. The currents derived lead to the relations that are mathematically linear combinations of designated vectors. This makes the possibility of establishing vector-input adaptive linear combiners (VI-ALC) in accordance with the relations derived. Being fed from the vectors of instantaneous measurements at the relaying side, the VI-ALCs with a distinctive capability of online training would swiftly give an accurate estimation of the fault distances during CCFs. The estimations are exploited in a logical procedure for both of the distance protection and fault location functions, taking account of different position status of the CCFs' comprising LG faults. The proposed algorithm is feasibly implementable and is independent of the system configuration. It operates robustly in high-ground resistance and noisy conditions. Through extensive simulation studies in PSCAD/EMTDC, performance of the proposed algorithm would be investigated and verified in a va-riety of fault scenarios.
引用
收藏
页数:22
相关论文
共 50 条
  • [1] Distance Relaying of Asymmetrical Double-Circuit Transmission Lines Considering Abnormal Faults
    Abdollahzadeh, Hamed
    IRANIAN JOURNAL OF SCIENCE AND TECHNOLOGY-TRANSACTIONS OF ELECTRICAL ENGINEERING, 2023, 47 (02) : 563 - 599
  • [2] Distance Relaying of Asymmetrical Double-Circuit Transmission Lines Considering Abnormal Faults
    Hamed Abdollahzadeh
    Iranian Journal of Science and Technology, Transactions of Electrical Engineering, 2023, 47 : 563 - 599
  • [3] An algorithm scheme for detecting single-circuit, inter-circuit, and grounded double-circuit cross-country faults in GUPFC-compensated double-circuit transmission lines
    Abasi, Mahyar
    Joorabian, Mahmood
    Saffarian, Alireza
    Seifossadat, Seyed Ghodratollah
    ELECTRICAL ENGINEERING, 2022, 104 (04) : 2021 - 2044
  • [4] An algorithm scheme for detecting single-circuit, inter-circuit, and grounded double-circuit cross-country faults in GUPFC-compensated double-circuit transmission lines
    Mahyar Abasi
    Mahmood Joorabian
    Alireza Saffarian
    Seyed Ghodratollah Seifossadat
    Electrical Engineering, 2022, 104 : 2021 - 2044
  • [5] Location of double-circuit grounded cross-country faults in GUPFC-compensated transmission lines based on current and voltage phasors analysis
    Abasi, Mahyar
    Saffarian, Alireza
    Joorabian, Mahmood
    Seifossadat, Seyed Ghodratollah
    ELECTRIC POWER SYSTEMS RESEARCH, 2021, 195
  • [6] Analysis of homogeneous phase cross-country faults of double-circuit lines on the same tower
    Sun Z.
    Deng Y.
    Chen H.
    Liu Z.
    Wang Y.
    1600, Power System Protection and Control Press (49): : 154 - 159
  • [7] ON ALLOWING FOR SUSCEPTANCE IN FAULT LOCATION ON DOUBLE-CIRCUIT TRANSMISSION LINES
    MALYI, AS
    ELECTRICAL TECHNOLOGY, 1968, 3 : 166 - &
  • [8] Adaptive distance protection of double-circuit lines for faults involving earth
    Izykowski, Jan
    Bozek, Marcin
    PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (9A): : 22 - 26
  • [9] An accurate fault location algorithm for double-circuit transmission systems
    Ahn, YJ
    Choi, MS
    Kang, SH
    Lee, SJ
    2000 IEEE POWER ENGINEERING SOCIETY SUMMER MEETING, CONFERENCE PROCEEDINGS, VOLS 1-4, 2000, : 1344 - 1349
  • [10] Accurate Fault Location for Double-Circuit Lines on the Same Tower with Asymmetrical Parameters
    Zhu Yiyang
    Du Hongji
    PROCEEDINGS OF THE6TH INTERNATIONAL CONFERENCE ON MECHATRONICS, MATERIALS, BIOTECHNOLOGY AND ENVIRONMENT (ICMMBE 2016), 2016, 83 : 175 - 181