A distance Protection/Fault location algorithm for Double-Circuit transmission lines with asymmetrical circuits during Cross-Country faults

被引:0
|
作者
Abdollahzadeh, Hamed [1 ]
机构
[1] Islamic Azad Univ, Dept Elect Engn, East Tehran Branch, Tehran 1866113118, Iran
关键词
Distance protection; Fault location; Double -circuit lines with asymmetrical circuits; cross -country faults (CCFs); Fault distance estimation; vector-input adaptive linear combiner (VI-ALC); RELAYING SCHEME; IMPACT;
D O I
10.1016/j.ijepes.2022.108943
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The impedance-measuring elements and fault locators in distance relays suffer from measuring the correct fault impedance and fault location when facing cross-country faults (CCFs). During such atypical faults, this paper proposes a distance protection along with a fault location algorithm for double-circuit lines with asymmetrical circuits. This is fulfilled through instantaneous fault-branch currents innovatively derived from the line six-phase circuit model analysis on a time-domain basis. The currents derived lead to the relations that are mathematically linear combinations of designated vectors. This makes the possibility of establishing vector-input adaptive linear combiners (VI-ALC) in accordance with the relations derived. Being fed from the vectors of instantaneous measurements at the relaying side, the VI-ALCs with a distinctive capability of online training would swiftly give an accurate estimation of the fault distances during CCFs. The estimations are exploited in a logical procedure for both of the distance protection and fault location functions, taking account of different position status of the CCFs' comprising LG faults. The proposed algorithm is feasibly implementable and is independent of the system configuration. It operates robustly in high-ground resistance and noisy conditions. Through extensive simulation studies in PSCAD/EMTDC, performance of the proposed algorithm would be investigated and verified in a va-riety of fault scenarios.
引用
收藏
页数:22
相关论文
共 50 条
  • [41] Principle and engineering application of double-circuit transmission lines protection
    Xia, Yong-Jun
    Yin, Xiang-Gen
    Hu, Gang
    Zhang, Zhe
    Dong, Yong-De
    Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2009, 37 (03): : 98 - 103
  • [42] Impedance-Based Fault Location Algorithm for Double-Circuit Transmission Lines Using Single-End Data
    Mojtaba Nemati
    Mehdi Bigdeli
    Amir Ghorbani
    Journal of Control, Automation and Electrical Systems, 2020, 31 : 1267 - 1277
  • [43] A Successive Geometric Segmentation Approach Applied to Double-Circuit Transmission Lines Fault Classification and Location
    Gaspar Valente W.A.
    de Mello Honório L.
    de Oliveira E.J.
    de Alcantara Barbosa D.
    Boas E.R.V.
    Journal of Control, Automation and Electrical Systems, 2016, 27 (4) : 452 - 462
  • [44] Robust Fault Location Algorithm for Single Line-to-ground Fault in Double-circuit Transmission Systems
    Prasad, V. D. N.
    Rathinam, A.
    2013 INTERNATIONAL CONFERENCE ON ENERGY EFFICIENT TECHNOLOGIES FOR SUSTAINABILITY (ICEETS), 2013,
  • [45] A Robust Fault Location Algorithm for Single Line-to-ground Fault in Double-circuit Transmission Systems
    Zhang, Wen-Hao
    Rosadi, Umar
    Choi, Myeon-Song
    Lee, Seung-Jae
    Lim, Ilhyung
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2011, 6 (01) : 1 - 7
  • [46] Adaptive distance protection scheme for high resistance phase to phase faults on double-circuit transmission line
    Ciprian, Borascu Ionut
    Iliescu, Sergiu Stelian
    2015 20TH INTERNATIONAL CONFERENCE ON CONTROL SYSTEMS AND COMPUTER SCIENCE, 2015, : 972 - 977
  • [47] New protection scheme for high resistance ground fault on the parallel double-circuit transmission lines
    Nanjing NARI-Relays Electric Co. Ltd., Nanjing 211106, China
    不详
    Dianli Xitong Zidonghue, 2008, 8 (55-58):
  • [48] Directional relaying using support vector machine for double circuit transmission lines including cross-country and inter-circuit faults
    Swetapadma, Aleena
    Yadav, Anamika
    INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2016, 81 : 254 - 264
  • [49] Two-End Unsynchronized Fault Location Algorithm for Double-Circuit Series Compensated Lines
    Fulczyk, Marek
    Balcerek, Przemyslaw
    Izykowski, Jan
    Rosolowski, Eugeniusz
    Saha, Murari Mohan
    2008 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, VOLS 1-11, 2008, : 1641 - +
  • [50] New Fault-Location Algorithm for Series-Compensated Double-Circuit Transmission Line
    Cai, Daiying
    Zhang, Jun
    IEEE ACCESS, 2020, 8 : 210685 - 210694