A comprehensive study on the impacts of isolation heat exchangers on the energy performance of surface water heat pump systems

被引:3
|
作者
Chen, Xiao [1 ]
Wang, Yuqian [1 ]
Zhu, Zhiwei [1 ]
Tang, Jingyue [1 ]
Zhou, Maojun [2 ]
机构
[1] Hunan Inst Engn, Hunan Prov Engn Res Ctr Energy Saving & Mat Techno, Xiangtan 411104, Peoples R China
[2] Hunan Zunfeng Mech & Elect technol Co Ltd, Dongkou, Hunan, Peoples R China
关键词
Heat pump; Isolation heat exchanger; Surface water temperature; Energy performance evaluation; System configuration optimization; MODEL; SEAWATER; DESIGN; RIVER; LAKE;
D O I
10.1016/j.geothermics.2023.102713
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Surface water heat pumps are included as a subset of ground-source heat pumps for the utilization of shallow geothermal energy. For the surface water heat pump applications in which the location of the heat pump plant is remarkably higher than water surface, the pump energy consumption of an indirect system with isolation heat exchangers (IHE) will be lower than that of a direct system without IHE. However, the entering fluid temperature of heat pumps in an indirect system is higher/lower than that in a direct system in cooling/heating modes due to the existence of IHE, which will bring a certain decrease in heat pump performance. This paper presents a comprehensive study on the impacts of IHE on system energy performance. The energy performance models for indirect and direct systems are developed, and a method for energy-saving judgment between indirect and direct systems is proposed. The case study results show that a direct system is more energy efficient for cooling than an indirect system because the elevation difference between water surface and plant is less than the critical value. Under low surface water temperature condition in winter, an indirect system using antifreeze fluid can eliminate the defect that the heating capacity of heat pumps in a direct system decreases much and auxiliary heat is needed. An optimized system configuration that combines the advantages of direct and indirect systems is proposed. The proposed system can operate without auxiliary heat in winter even though the surface water temperature drops to a low level, and can acquire cooling performance close to that of the cooling systems including chillers and cooling towers.
引用
收藏
页数:8
相关论文
共 50 条
  • [21] Design of heat exchangers for CO2 -: Heat pump water heaters
    Rieberer, R
    Halozan, H
    HEAT TRANSFER ISSUES IN NATURAL REFRIGERANTS, 1997, 1997 (05): : 96 - 104
  • [22] Case Study of a Heat Pump Installation with Horizontal Ground Heat Exchangers
    Marius, Mantulescu
    Stan, Fota
    Ioan, Tuns
    PROCEEDINGS OF THE 5TH WSEAS INTERNATIONAL CONFERENCE ON APPLIED AND THEORETICAL MECHANICS (MECHANICS '09), 2009, : 128 - 133
  • [23] Performance of plate heat exchangers and compressor in a domestic heat pump using propane
    Pelletier, O
    Palm, B
    APPLICATIONS FOR NATURAL REFRIGERANTS, 1996, : 497 - 506
  • [24] Study Case of a Heat Pump Installation with Horizontal Ground Heat Exchangers
    Marius, Mantulescu
    Stan, Fota
    Ioan, Tuns
    PROCEEDINGS OF THE 2ND INTERNATIONAL CONFERENCE ON ENVIRONMENTAL AND GEOLOGICAL SCIENCE AND ENGINEERING, 2009, : 278 - 283
  • [25] Computer simulation of borehole ground heat exchangers for geothermal heat pump systems
    Lee, C. K.
    Lam, H. N.
    RENEWABLE ENERGY, 2008, 33 (06) : 1286 - 1296
  • [26] Thermal-hydraulic and drainage performance of microchannel heat exchangers for refrigeration and heat pump systems under frosting, defrosting, and wet conditions: A comprehensive review
    Xiong, Tong
    Liu, Guoqiang
    Gao, Qiang
    Yan, Gang
    Yu, Jianlin
    JOURNAL OF BUILDING ENGINEERING, 2023, 64
  • [27] Performance of a large capacity propane heat pump with low charge heat exchangers
    Cavallini, Alberto
    Da Riva, Enrico
    Del Col, Davide
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (02): : 242 - 250
  • [28] Operating Results of Two Differently Designed Bivalent Heat Pump Heating Systems with Surface Heat Exchangers.
    Schimmelpfennig, K.
    Hanke, A.
    Elektrowarme international. Edition A, Elektrowarme im technischen Ausbau, 1982, 40 (02): : 67 - 73
  • [29] Performance analysis of an automotive heat pump system with desiccant coated heat exchangers
    Na, Sun-Ik
    Kim, Minsung
    Kim, Min Soo
    APPLIED THERMAL ENGINEERING, 2022, 213