A comprehensive study on the impacts of isolation heat exchangers on the energy performance of surface water heat pump systems

被引:3
|
作者
Chen, Xiao [1 ]
Wang, Yuqian [1 ]
Zhu, Zhiwei [1 ]
Tang, Jingyue [1 ]
Zhou, Maojun [2 ]
机构
[1] Hunan Inst Engn, Hunan Prov Engn Res Ctr Energy Saving & Mat Techno, Xiangtan 411104, Peoples R China
[2] Hunan Zunfeng Mech & Elect technol Co Ltd, Dongkou, Hunan, Peoples R China
关键词
Heat pump; Isolation heat exchanger; Surface water temperature; Energy performance evaluation; System configuration optimization; MODEL; SEAWATER; DESIGN; RIVER; LAKE;
D O I
10.1016/j.geothermics.2023.102713
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Surface water heat pumps are included as a subset of ground-source heat pumps for the utilization of shallow geothermal energy. For the surface water heat pump applications in which the location of the heat pump plant is remarkably higher than water surface, the pump energy consumption of an indirect system with isolation heat exchangers (IHE) will be lower than that of a direct system without IHE. However, the entering fluid temperature of heat pumps in an indirect system is higher/lower than that in a direct system in cooling/heating modes due to the existence of IHE, which will bring a certain decrease in heat pump performance. This paper presents a comprehensive study on the impacts of IHE on system energy performance. The energy performance models for indirect and direct systems are developed, and a method for energy-saving judgment between indirect and direct systems is proposed. The case study results show that a direct system is more energy efficient for cooling than an indirect system because the elevation difference between water surface and plant is less than the critical value. Under low surface water temperature condition in winter, an indirect system using antifreeze fluid can eliminate the defect that the heating capacity of heat pumps in a direct system decreases much and auxiliary heat is needed. An optimized system configuration that combines the advantages of direct and indirect systems is proposed. The proposed system can operate without auxiliary heat in winter even though the surface water temperature drops to a low level, and can acquire cooling performance close to that of the cooling systems including chillers and cooling towers.
引用
收藏
页数:8
相关论文
共 50 条
  • [31] Heat transfer analysis of multi-row helically coiled tube heat exchangers for surface water-source heat pump
    Zhou, Chaohui
    Ni, Long
    Yao, Yang
    ENERGY, 2018, 163 : 1032 - 1049
  • [32] THE PERFORMANCE OF A THERMOELECTRIC HEAT PUMP WITH SURFACE HEAT TRANSFER
    ROLLINGER, CN
    SUNDERLAND, JE
    SOLID-STATE ELECTRONICS, 1963, 6 (01) : 47 - 57
  • [33] Numerical simulation of a ground-coupled heat pump system with vertical plate heat exchangers: A comprehensive parametric study
    Amadeh, Ali
    Habibi, Mohammad
    Hakkaki-Fard, Ali
    GEOTHERMICS, 2020, 88
  • [34] Numerical simulation of a ground-coupled heat pump system with vertical plate heat exchangers: A comprehensive parametric study
    Amadeh, Ali
    Habibi, Mohammad
    Hakkaki-Fard, Ali
    Geothermics, 2020, 88
  • [35] Study on annual energy performance of transcritical CO2 heat pump water heating systems in Shanghai
    Liang, Xing-Yu
    Cheng, Jia-Hao
    He, Yu-Jia
    Wang, Lei
    Li, Hui
    Shao, Liang-Liang
    Zhang, Chun-Lu
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2019, 107 : 174 - 182
  • [36] Heat output performance study of magnesium oxide/water chemical heat pump
    Kato, Y
    Takahashi, F
    Nanmoku, W
    Yoshizawa, Y
    KAGAKU KOGAKU RONBUNSHU, 1998, 24 (06) : 840 - 844
  • [37] Developing performance of waste water source heat pump systems by heat transport investigation
    Schon, Balint
    2017 6TH INTERNATIONAL YOUTH CONFERENCE ON ENERGY (IYCE), 2017,
  • [38] PERFORMANCE OF ADD-ON HEAT PUMP WATER HEATER (HPWH) SYSTEMS AND THEIR IMPACTS ON ELECTRIC UTILITY LOADS
    Sharaf-Eldeen, Yahya I.
    Muccio, Craig V.
    Gay, Eric
    ES2010: PROCEEDINGS OF ASME 4TH INTERNATIONAL CONFERENCE ON ENERGY SUSTAINABILITY, VOL 1, 2010, : 439 - 445
  • [39] Experimental and numerical investigation of heat transfer performance and sustainability of deep borehole heat exchangers coupled with ground source heat pump systems
    Cai, Wanlong
    Wang, Fenghao
    Liu, Jun
    Wang, Zhihua
    Ma, Zhenjun
    APPLIED THERMAL ENGINEERING, 2019, 149 : 975 - 986