Thermal-hydraulic and drainage performance of microchannel heat exchangers for refrigeration and heat pump systems under frosting, defrosting, and wet conditions: A comprehensive review

被引:13
|
作者
Xiong, Tong [1 ]
Liu, Guoqiang [1 ]
Gao, Qiang [2 ]
Yan, Gang [1 ]
Yu, Jianlin [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Energy & Power Engn, Dept Refrigerat & Cryogen Engn, Xian 710049, Shaanxi, Peoples R China
[2] Hangzhou Sanhua Microchannel Heat Exchanger Co Ltd, Hangzhou 310000, Zhejiang, Peoples R China
来源
关键词
Microchannel heat exchanger; Frosting; Defrosting; Wet conditions; Thermal -hydraulic performance; Drainage performance; AIR-SIDE PERFORMANCE; LONGITUDINAL VORTEX GENERATOR; LOUVERED-FIN; EVAPORATOR MODEL; FLAT-TUBE; TRANSFER ENHANCEMENT; START-TIME; COMPACT; SURFACE; PARALLEL;
D O I
10.1016/j.jobe.2022.105654
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Currently, microchannel heat exchangers (MCHXs) are widely employed in refrigeration and heat pump systems due to their advantages of being more efficient, smaller in size, lower refrigerant charge, and cheaper price. However, when used as evaporators, MCHXs have the issues of a faster frosting rate and frost melt water, condensate that is more difficult to remove than fin-and-tube heat exchangers. This review paper focuses on the research progress on the thermal-hydraulic and drainage performance of MCHX under frosting, defrosting, and wet conditions from the year 2000-2022. First, experimental research on the frosting and drainage characteristics of MCHX is summarized and analyzed in periodic frosting and defrosting conditions. Then, three typical methods for improving the frosting and defrosting performance of MCHX are introduced. Moreover, empirical correlations and simulation models developed to predict the frosting and defrosting characteristics of MCHX are discussed. Uneven frost layer distribution should be considered in the frosting model and the effect of drainage characteristics on defrosting perfor-mance should be considered in the defrosting model. The thermal-hydraulic and drainage per-formance of MCHX under wet conditions is also reviewed. First, methods for testing real-time condensate retention are introduced. Then, the parameters affecting the thermal-hydraulic and drainage characteristics of the MCHX are analyzed. Based on the above research, two methods for improving the performance of MCHX under wet conditions are introduced. Empirical correlations and numerical models for predicting thermal-hydraulic performance under wet conditions are classified and compared. A novel one-dimensional numerical model based on the fin theory combined with the moving boundary technique can accurately capture the actual dehumidifi-cation state with a small computational cost. The main conclusions regarding the thermal -hydraulic and drainage performance of MCHX based on the open literature are presented. Finally, some research initiatives and vital improvement measures are suggested for future studies. This review aims to serve as a reference guide for the thermal-hydraulic and drainage characteristics studies of MCHX under frosting, defrosting, and wet conditions.
引用
收藏
页数:28
相关论文
共 50 条
  • [1] Heat transfer characteristics of the heat exchangers for refrigeration, air conditioning and heat pump systems under frosting, defrosting and dry/wet conditions-A review
    Patil, Mahesh Suresh
    Seo, Jae-Hyeong
    Lee, Moo-Yeon
    APPLIED THERMAL ENGINEERING, 2017, 113 : 1071 - 1087
  • [2] INVESTIGATION OF THE PERFORMANCE OF A HEAT-PUMP UNDER FROSTING AND DEFROSTING CONDITIONS
    VOTSIS, PP
    TASSOU, SA
    WILSON, DR
    MARQUAND, CJ
    HEAT RECOVERY SYSTEMS & CHP, 1989, 9 (05): : 399 - 406
  • [3] Thermal performance of microchannel heat exchangers according to the design parameters under the frosting conditions
    Kim, Kyoungmin
    Kim, Min-Hwan
    Kim, Dong Rip
    Lee, Kwan-Soo
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2014, 71 : 626 - 632
  • [4] Experimental investigation of the performance of microchannel heat exchangers with a new type of fin under wet and frosting conditions
    Xu, Bo
    Zhang, Chi
    Wang, Ying
    Chen, Jiangping
    Xu, Kunhao
    Li, Feng
    Wang, Nianjie
    APPLIED THERMAL ENGINEERING, 2015, 89 : 444 - 458
  • [5] Thermal-hydraulic performance evaluation of airside of wavy fin compact heat exchangers under wet conditions
    Ejaz, Faheem
    Qasem, Naef A. A.
    Zubair, Syed M.
    INTERNATIONAL COMMUNICATIONS IN HEAT AND MASS TRANSFER, 2024, 156
  • [6] A model for predicting the thermal-hydraulic performance of louvered-fin, flat-tube heat exchangers under frosting conditions
    Xia, Y.
    Jacobi, A. M.
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2010, 33 (02): : 321 - 333
  • [7] Thermal and drainage performance of a louvered fin heat exchanger according to heat exchanger inclination angle under frosting and defrosting conditions
    Park, Jin-Seong
    Kim, Junghan
    Lee, Kwan-Soo
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2017, 108 : 1335 - 1339
  • [8] PERFORMANCE OF AN AIR-TO-AIR HEAT-PUMP UNDER FROSTING AND DEFROSTING CONDITIONS
    KAYGUSUZ, K
    APPLIED ENERGY, 1994, 48 (03) : 225 - 241
  • [9] A Review on the Thermal-Hydraulic Performance and Optimization of Compact Heat Exchangers
    Liao, Gaoliang
    Li, Zhizhou
    Zhang, Feng
    Liu, Lijun
    E, Jiaqiang
    ENERGIES, 2021, 14 (19)
  • [10] Thermal-Hydraulic Performance of Microstructured Heat Exchangers
    Heltzel, Alex J.
    SAE INTERNATIONAL JOURNAL OF AEROSPACE, 2009, 1 (01): : 1036 - 1045