Energy efficiency optimization analysis for a cooling composite air conditioning system for internet data centers

被引:0
|
作者
Li, Zhao [1 ]
Tong, Jihua [1 ]
Zheng, Zhuling [2 ]
Dong, Pengli [1 ]
Yang, Shangqing [1 ]
机构
[1] Univ Shanghai Sci & Technol, Sch Environm & Architecture, Shanghai 200093, Peoples R China
[2] SRIBS Energy Saving Technol Co Ltd, Shanghai, Peoples R China
基金
中国国家自然科学基金;
关键词
LIQUID REFRIGERANT PUMP; DRIVEN;
D O I
10.1080/23744731.2024.2321817
中图分类号
O414.1 [热力学];
学科分类号
摘要
In this study, a validated mathematical model for a composite air conditioning system was established based on onsite test data. The system consists of a refrigerant pump driven two-phase cooling loop (RPTCL) and vapor compression refrigeration (VCR) cycles. The system can be switched to refrigerant pump (RP) mode, compressor mode, or hybrid mode, according to the outdoor temperature. By analyzing, the inadequacy of the existing Internet Data center (IDC) air conditioning system operation strategy was confirmed, and subsequently, five optimization strategies were proposed. The optimization strategies took two identical composite air conditioning systems as optimization unit, and under the premise of meeting the demand for cooling capacity, maximizing the operating time of RP and hybrid mode, which with higher energy efficiency, through complementary cooling capacity, to reduce the energy consumption. Meanwhile, when the cooling supply was higher than the demand, paired with optimization unit's ON/OFF ratio control, the unit's energy consumption was further reduced. The most optimization strategy provided 525.6 MWh of cooling energy to meet demand while consuming a minimum of 182.5 MWh. The optimization strategy also achieved a minimum of 12.1% and a maximum of 52.5% energy savings for IDCs in other climate zones of China.
引用
收藏
页码:1167 / 1181
页数:15
相关论文
共 50 条
  • [1] Energy saving analysis of evaporative cooling composite air conditioning system for data centers
    Han, Zongwei
    Sun, Xiaoqing
    Wei, Haotian
    Ji, Qiang
    Xue, Da
    [J]. APPLIED THERMAL ENGINEERING, 2021, 186
  • [2] Review on Cooling System Energy Consumption in Internet Data Centers
    Amoabeng, Kofi Owura
    Choi, Jong Min
    [J]. INTERNATIONAL JOURNAL OF AIR-CONDITIONING AND REFRIGERATION, 2016, 24 (04)
  • [3] Modeling of air conditioning systems for cooling of data centers
    Anton, R
    Jonsson, H
    Palm, B
    [J]. ITHERM 2002: EIGHTH INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS, PROCEEDINGS, 2002, : 552 - 558
  • [4] Optimization strategy for minimizing energy consumption of air conditioning terminal system in the Internet data center
    Huang, Xiaofei
    Yan, Junwei
    Zhou, Xuan
    Shen, Ao
    Yang, Zhixian
    [J]. JOURNAL OF BUILDING ENGINEERING, 2024, 96
  • [5] OPTIMIZATION OF OUTSIDE AIR COOLING IN DATA CENTERS
    Kumari, Niru
    Shih, Rocky
    McReynolds, Alan
    Sharma, Ratnesh
    Christian, Tom
    Bash, Cullen
    [J]. PROCEEDINGS OF THE ASME PACIFIC RIM TECHNICAL CONFERENCE AND EXHIBITION ON PACKAGING AND INTEGRATION OF ELECTRONIC AND PHOTONIC SYSTEMS, MEMS AND NEMS 2011, VOL 2, 2012, : 519 - 525
  • [6] A review of air conditioning energy performance in data centers
    Ni, Jiacheng
    Bai, Xuelian
    [J]. RENEWABLE & SUSTAINABLE ENERGY REVIEWS, 2017, 67 : 625 - 640
  • [7] Comparative energy analysis of cooling energy performance between conventional and hybrid air source internet data center cooling system
    Lamptey, Nicholas Boafo
    Anka, Selorm Kwaku
    Cho, Yong
    Lee, Kwang Ho
    Choi, Jong Woong
    Choi, Jong Min
    [J]. ENERGY AND BUILDINGS, 2024, 302
  • [8] System Optimization and Exergy Analysis of Air Conditioning System for Data Center
    Jing, Youyin
    Liu, Qianqian
    Wang, Jiangjiang
    [J]. ADVANCES IN ENERGY SCIENCE AND TECHNOLOGY, PTS 1-4, 2013, 291-294 : 1857 - 1862
  • [9] Study on operation strategy of evaporative cooling composite air conditioning system in data center
    Han, Zongwei
    Xue, Da
    Wei, Haotian
    Ji, Qiang
    Sun, Xiaoqing
    Li, Xiuming
    [J]. RENEWABLE ENERGY, 2021, 177 : 1147 - 1160
  • [10] Energy efficiency of a railway carriage air conditioning system: parametric analysis and optimization through DoE techniques
    Carlos Ramos, Juan
    Anton, Raul
    Aramburu, Jorge
    Larraona, Gorka
    Rivas, Alejandro
    Fernandez, Jorge
    [J]. DYNA, 2020, 95 (06): : 640 - 645