Multi-stage heat pump with two-phase injection for cold climate applications implementing natural refrigerants☆

被引:0
|
作者
Fix, Andrew [1 ]
Kang, Dana [1 ]
Siam, Md Mehrab Hossen [1 ]
Hwang, Yunho [1 ]
Radermacher, Reinhard [1 ]
机构
[1] Univ Maryland, Ctr Environm Energy Engn, College Pk, MD 20742 USA
关键词
Heat pump; Cold climate; Natural refrigerants; Two-phase injection; Efficiency; VAPOR-INJECTION; SCROLL COMPRESSOR; LIQUID INJECTION; SATURATION CYCLE; PERFORMANCE; SYSTEM; OPTIMIZATION; EXCHANGER; R410A; INTERMEDIATE;
D O I
10.1016/j.applthermaleng.2025.125474
中图分类号
O414.1 [热力学];
学科分类号
摘要
Heat pump adoption in cold climates is limited by various technical challenges, including heat capacity degradation, compressor deterioration, and frost accumulation on the outdoor heat exchanger. Furthermore, widespread adoption of heat pumps with high global warming potential presents a possible environmental concern. Thus, we present a heat pump concept termed the "saturation cycle," which uses numerous compression stages to improve energy efficiency and injects two-phase refrigerant between compression stages to dramatically reduce compressor discharge temperatures. Given the growing interest in heat pumps, there is a need for a straightforward framework for parametric evaluation of natural refrigerants in high-efficiency heat pump cycle architectures, like the saturation cycle, in adverse climates. This study develops a thermodynamic modeling framework and focuses on the application of natural refrigerants to explore the performance trends at extremely cold climates down to -25 degrees C. This study shows that a two-stage saturation cycle and four-stage saturation cycle can reduce the compressor discharge superheating by up to 51-57 % or 73-80 %, respectively, depending on the refrigerant. Furthermore, at -25 degrees C, a two-stage R-290 saturation cycle heat pump theoretically can use 25 % less power than a single-stage heat pump or can provide up to 59 % more heating capacity when using the same compressor power as the baseline single-stage heat pump. The exergetic parametric analyses show that twophase refrigerant injection fundamentally improves the thermodynamic performance of the heat pump, reducing overall exergy destruction by 10 % compared to a vapor-injection heat pump, compared at -25 degrees C. Thus, the saturation cycle is a promising heat pump cycle architecture for cold climate applications due to its superior energy savings (or capacity improvement) and substantial de-superheating capabilities.
引用
收藏
页数:16
相关论文
共 50 条
  • [21] Fine-resolution two-phase flow heat transfer coefficient measurements of refrigerants in multi-microchannel evaporators
    Szczukiewicz, Sylwia
    Borhani, Navid
    Thome, John Richard
    INTERNATIONAL JOURNAL OF HEAT AND MASS TRANSFER, 2013, 67 : 913 - 929
  • [22] Analysis and optimization of a natural gas multi-stage expansion plant integrated with a gas engine-driven heat pump
    Xu, Xiao
    Cai, Liang
    Chen, Tao
    Zhan, Zhixing
    ENERGY, 2021, 236
  • [23] Modeling of a two-phase CO2-filled vertical borehole for geothermal heat pump applications
    Eslami-Nejad, Parham
    Ouzzane, Mohamed
    Aidoun, Zine
    APPLIED ENERGY, 2014, 114 : 611 - 620
  • [24] The multi-stage centred-scheme approach applied to a drift-flux two-phase flow model
    Munkejord, Svend Tollak
    Evje, Steinar
    Flatten, Tore
    INTERNATIONAL JOURNAL FOR NUMERICAL METHODS IN FLUIDS, 2006, 52 (06) : 679 - 705
  • [25] Anisotropy analysis of two-phase flow permeability in the multi-stage shear process of hydrate-bearing sediments
    Wu, Peng
    Chen, Yukun
    Shang, Anran
    Ding, Jiping
    Wei, Jiangong
    Liu, Weiguo
    Li, Yanghui
    ENERGY, 2024, 293
  • [26] EXTRACTION OF TETRACYCLINE USING THE IONIC LIQUID-BASED AQUEOUS TWO-PHASE SYSTEMS: SINGLE-STAGE VERSUS MULTI-STAGE
    Liu, Yi
    Chen, Li
    Zhou, Jun
    Yan, Zongcheng
    CHEMICAL INDUSTRY & CHEMICAL ENGINEERING QUARTERLY, 2018, 24 (04) : 387 - 397
  • [27] REVIEW ON TWO-PHASE PRESSURE DROP AND HEAT TRANSFER COEFFICIENT DURING FLOW BOILING OF NATURAL AND SYNTHETIC REFRIGERANTS: A PARAMETRIC ANALYSIS.
    Charnay, R.
    Revellin, R.
    Bonjour, J.
    23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 851 - 858
  • [28] Effective Two-Phase Heuristic and Lower Bounds for Multi-Stage Flexible Flow Shop Scheduling Problem with Unloading Times
    Hidri, Lotfi
    SYMMETRY-BASEL, 2023, 15 (11):
  • [29] Simulation of Novel Air-Source Heat Pump with Two-Stage Compression and Economizing for Cold Climate Field Tests
    Caskey, Stephen L.
    Kultgen, Derek
    Menzi, Tobias
    Groll, Eckhard A.
    Hutzel, William J.
    Bertsch, Stefan S.
    SEVENTH INTERNATIONAL COLD CLIMATE HVAC CONFERENCE, 2012, : 354 - 361
  • [30] Analysis of performance and economical efficiency of two-stage compression heat pump system with inter-stage injection in cold regions of northern China
    Jin, Xu
    Wu, Zhe
    Zhang, Kuo
    Liu, Zhongyan
    Hong, Wenpeng
    Li, Xiaoyi
    BUILDING SIMULATION, 2019, 12 (04) : 551 - 562