Active protection scheme based on high-frequency current for distribution networks with inverter-interfaced distributed generators

被引:0
|
作者
Li, Haifeng [1 ]
Liang, Huamin [1 ]
Wang, Zhidong [1 ]
Zhang, Zhenggang [2 ]
Liang, Yuansheng [1 ]
机构
[1] South China Univ Technol, Sch Elect Power Engn, Guangzhou 510641, Peoples R China
[2] China Southern Power Grid Co Ltd, Shenzhen Power Supply Bur Co LTD, Shenzhen, Peoples R China
关键词
active protection scheme; distribution networks; high-frequency current; inverter-interfaced distributed generators; power system protection; T-connected branch; OVERCURRENT PROTECTION;
D O I
10.1049/rpg2.13119
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
With the high penetration and flexible access of inverter-interfaced distributed generators (IIDGs), it is gradually becoming difficult for traditional protection schemes to meet the requirements for the safe operation of distribution networks (DNs). Active protection schemes based on power electronic equipment provide a new approach. On the basis of the controllability of voltage source converters, a method for active high-frequency signal injection and a selection principle for the corresponding control parameters are proposed. Considering the impact of T-connected load branches on the protected line, the high-frequency current characteristics at the three terminals during internal and external faults are analysed. On this basis, an active protection scheme based on high-frequency current is proposed for DNs with IIDGs. The performance of the proposed scheme is verified via PSCAD/EMTDC simulation software. The test results show that the proposed scheme can reliably trip during internal faults and identify faulty phases, which has better endurance to fault resistance. This paper proposes a high-frequency current-based active protection scheme for a distribution network with T-connected inverter-interfaced distributed generators and T-connected load branches. The performance of the proposed protection scheme is verified via PSCAD/EMTDC simulation software. image
引用
收藏
页码:2737 / 2750
页数:14
相关论文
共 50 条
  • [41] A Distance Based Protection Scheme for Distribution Systems with Distributed Generators
    Nikolaidis, V. C.
    Arsenopoulos, C.
    Safigianni, A. S.
    Vournas, Costas D.
    2016 POWER SYSTEMS COMPUTATION CONFERENCE (PSCC), 2016,
  • [42] Study on adaptive current instantaneous trip protection scheme for distribution network with inverter interfaced DG
    Sun, Jingliao
    Li, Yongli
    Li, Shengwei
    Jin, Qiang
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2009, 33 (14): : 71 - 76
  • [43] Whole-line fault analysis method for unbalanced distribution networks with inverter interfaced distributed generators
    Li, Yingliang
    Wang, Deming
    IET GENERATION TRANSMISSION & DISTRIBUTION, 2022, 16 (15) : 3016 - 3026
  • [45] Locating and sizing of distributed generators and current protection strategy in distribution networks
    Fu, Wenxiu, 1600, Automation of Electric Power Systems Press
  • [46] Power-Based Concept for Current Injection by Inverter-Interfaced Distributed Generations during Transmission-Network Faults
    Polajzer, Bostjan
    Grcar, Bojan
    Cernelic, Jernej
    Ritonja, Jozef
    APPLIED SCIENCES-BASEL, 2021, 11 (21):
  • [47] Current Protection Optimization Scheme in Distribution Network With Large Capacity Distributed Generators
    Yuan Z.
    Xu Q.
    Xu G.
    Lei J.
    Yu R.
    Lin Y.
    Dianwang Jishu/Power System Technology, 2021, 45 (05): : 1862 - 1868
  • [48] Optimization method of inverse-time overcurrent protection setting for distribution network with inverter-interfaced distributed generator and energy storage system
    Wang, Gang
    Feng, Jingtong
    Bai, Hao
    Li, Jie
    Zhou, Qilin
    Wang, Haoming
    Huang, Min
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2024, 44 (11): : 202 - 209
  • [49] Active Islanding Detection for Multiple Parallel-Connected Inverter-Based Distributed Generators Using High-Frequency Signal Injection
    Reigosa, David
    Briz, Fernando
    Blanco, Cristian
    Garcia, Pablo
    Manuel Guerrero, Juan
    IEEE TRANSACTIONS ON POWER ELECTRONICS, 2014, 29 (03) : 1192 - 1199
  • [50] A Differential Sequence Component Protection Scheme for Microgrids With Inverter-Based Distributed Generators
    Casagrande, E.
    Woon, W. L.
    Zeineldin, H. H.
    Svetinovic, D.
    IEEE TRANSACTIONS ON SMART GRID, 2014, 5 (01) : 29 - 37