Numerical performance analysis of modified vertical U-tube ground heat exchangers by adjusting the impact of leg spacing

被引:0
|
作者
Chowdhury, Nafisa Riza [1 ]
Toslim, Abu Hena [1 ]
Ali, Md. Hasan [1 ]
Miyara, Akio [2 ,3 ]
机构
[1] Department of Energy Science and Engineering, Khulna University of Engineering & Technology, Khulna,9203, Bangladesh
[2] Department of Mechanical Engineering, Saga University, 1 Honjo-machi, Saga,840-8502, Japan
[3] International Institute for Carbon-Neutral Energy Research, Kyushu University, Fukuoka-shi,819-0395, Japan
来源
关键词
Boreholes - Geothermal fields - Geothermal heating - Heat exchangers - Heat transfer performance - Low temperature operations - Silica sand - Underground heat transfer;
D O I
10.1016/j.ijft.2024.100959
中图分类号
学科分类号
摘要
Geothermal energy is a reliable and renewable form of energy that offers steady cooling and heating of buildings without relying on sunlight or wind, avoiding price fluctuations. Ground heat exchangers (GHEs) are designed to utilize geothermal energy for building heating and cooling. The present study conducted a numerical investigation on the thermal performance of Modified Vertical U-tube GHEs. Enhancement of the thermal performance of various configurations of GHEs by adjusting the leg spacing and incorporating spiral configuration of U-tube GHEs. The upper section's leg spacing varies to reduce thermal interference and the lower section's leg spacing is kept constant. Some designs incorporated a combination of spiral and straight U-tubes. All GHE models were considered a 20-meter depth. Performances of these GHEs are evaluated with polyethylene, high-density polyethylene, and low-density polyethylene tubes and boreholes filled with silica sand. The surrounding soil consisted of clay. In some configurations, the lower section was modeled with spiral geometry after 10 meters in depth. The design parameters for the spiral section were 70 mm and 100 mm diameter. The simulations were conducted using the ANSYS FLUENT 22.2 software program for cooling operation. The outlet temperature was lower for spiral configurations than for the other configurations after being simulated for 72 hours. Compared to the traditional U-tube configuration, the heat transfer rate achieved by each arrangement is significantly higher. Results indicated that the combination of spiral shape with traditional shape led to a 31.2% increase in average heat transfer rate. Leg spacing variation opens up the opportunity to combine multiple geometries in a single borehole, also providing the solution to reduce the thermal interference between the inlet and outlet pipe. © 2024 The Authors
引用
收藏
相关论文
共 50 条
  • [21] Performance analysis of a solar-assisted ground source heat pump with a single vertical U-tube ground heat exchanger
    Adebayo, Philip
    Shor, Roman
    Mohamad, Abdulmajeed
    Wemhoner, Carsten
    Mwesigye, Aggrey
    APPLIED THERMAL ENGINEERING, 2024, 257
  • [22] Numerical Simulation and Analysis for the U-tube Heat Exchanger of Ground Source Heat Pump
    Chang Zhen
    Guo Min
    2013 32ND CHINESE CONTROL CONFERENCE (CCC), 2013, : 8713 - 8717
  • [23] Thermal performance of the vertical ground heat exchanger with a novel elliptical single U-tube
    Jahanbin, Aminhossein
    GEOTHERMICS, 2020, 86
  • [24] Study on Heat Transfer Capacity Calculation of Multi-hole heat source for Vertical U-Tube Ground Heat Exchangers
    Zhang, Dan
    Wang, Fahui
    Lei, Bo
    Yuan, Yanping
    Cao, Xiaoling
    FRONTIERS OF GREEN BUILDING, MATERIALS AND CIVIL ENGINEERING, PTS 1-8, 2011, 71-78 : 94 - +
  • [25] Techno-economic analysis of single U-tube and double U-tube heat exchangers in Chongqing area
    Wang Yong
    Guo Kai-sheng
    Tian Rong
    Han Chuan-pu
    Lai Dao-xin
    Xu Feng
    JOURNAL OF CENTRAL SOUTH UNIVERSITY OF TECHNOLOGY, 2009, 16 : 244 - 248
  • [26] Techno-economic analysis of single U-tube and double U-tube heat exchangers in Chongqing area
    王勇
    郭凯生
    田荣
    韩传璞
    赖道新
    徐峰
    Journal of Central South University, 2009, 16 (S1) : 244 - 248
  • [27] Techno-economic analysis of single U-tube and double U-tube heat exchangers in Chongqing area
    王勇
    郭凯生
    田荣
    韩传璞
    赖道新
    徐峰
    JournalofCentralSouthUniversityofTechnology, 2009, 16(S1) (S1) : 244 - 248
  • [28] Vertical U-tube Ground Heat Exchanger design method research
    Wang, P. Y.
    Tian, H. F.
    Cao, W. W.
    CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 974 - 978
  • [29] A numerical study on the intermittent operation of u-tube and coaxial borehole heat exchangers
    Harris, B. E.
    Lightstone, M. F.
    Reitsma, S.
    Cotton, J. S.
    GEOTHERMICS, 2024, 121
  • [30] Experimental study of the effect of backfills on the thermal performance of a vertical U-tube ground heat exchanger
    Yang, W.B.
    Wang, S.S.
    Liu, G.Y.
    Zhu, J.L.
    7th International Symposium on Heating, Ventilating and Air Conditioning - Proceedings of ISHVAC 2011, 2011, 4 : 1341 - 1346