MECHANICAL SHOCKS AS CAUSE OF LATE DISCHARGES IN VACUUM CIRCUIT-BREAKERS

被引:21
|
作者
GEBEL, R
HARTMANN, W
机构
[1] Siemens AG Corporate Research and Development, Erlangen
来源
关键词
Correlation methods - Damping - Electric contacts - Electric discharges - Electron tubes - Particles (particulate matter) - Probability - Shock waves - Stresses - Vacuum;
D O I
10.1109/14.231527
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
HV circuit breakers equipped with vacuum tubes occasionally show late discharges (reignition) after successful interruption of short circuit currents. The time dependence of late discharges in vacuum circuit breakers after current interruption has been measured as a function of the mechanical and electrical stress exerted on the vacuum circuit breaker bottle. A correlation between the occurrence of strong, shock-like acceleration peaks of > 10(4) m/s2 and the increase of the probability of late discharges has been found. A reduction of the shock wave amplitudes by simple mechanical damping results in a reduction of the probability of late strikes by as much as 50%. As a result, we conclude that most of the late discharges observed in these experiments are caused by particles which adhere loosely to the contact and vapor shield surfaces, and which are released by the strong mechanical shocks.
引用
收藏
页码:468 / 472
页数:5
相关论文
共 50 条
  • [21] RELIABILITY OF MEDIUM-VOLTAGE VACUUM POWER CIRCUIT-BREAKERS
    HEISING, CR
    [J]. IEEE TRANSACTIONS ON RELIABILITY, 1983, 32 (01) : 3 - 6
  • [22] HV dielectric strength of shielding electrodes in vacuum circuit-breakers
    Giere, S
    Kurrat, M
    Schümann, U
    [J]. ISDEIV: XXTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, PROCEEDINGS, 2002, 20 : 119 - 122
  • [23] HIGH-SPEED MECHANISM FOR SYNCHRONOUS VACUUM CIRCUIT-BREAKERS
    LOEWEN, T
    ERVEN, CC
    HICK, MAS
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1977, 96 (04): : 1073 - 1073
  • [24] CAPACITANCE SWITCHING WITH VACUUM CIRCUIT-BREAKERS - A COMPARATIVE-EVALUATION
    GLINKOWSKI, M
    GREENWOOD, A
    HILL, J
    MAURO, R
    VARNECKES, V
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1991, 6 (03) : 1088 - 1095
  • [25] LIMITATION OF SURGES DUE TO INDUCTIVE SWITCHING BY VACUUM CIRCUIT-BREAKERS
    BAZUTKIN, VV
    YEVDOKUNIN, GA
    KHALILOV, FK
    [J]. ELECTRICAL TECHNOLOGY, 1994, (01): : 63 - 72
  • [26] INVESTIGATION OF HIGH-CURRENT INTERRUPTION OF VACUUM CIRCUIT-BREAKERS
    DULLNI, E
    SCHADE, E
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1993, 28 (04): : 607 - 620
  • [27] MEASUREMENTS FOR NONINVASIVE MECHANICAL DIAGNOSTICS OF POWER CIRCUIT-BREAKERS
    PARK, SY
    LAI, ML
    LIN, CC
    NAIDU, H
    SOOM, A
    REINHORN, AM
    LEE, YH
    DEMJANENKO, V
    BENENSON, DM
    SOONG, TT
    WRIGHT, SE
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 1990, 19 (01) : 1 - 10
  • [28] DEVELOPMENT TESTS FOR CIRCUIT-BREAKERS
    HERMANN, W
    RAGALLER, K
    [J]. BROWN BOVERI REVIEW, 1979, 66 (04): : 281 - 287
  • [29] Dynamic Dielectric Recovery Property for Vacuum Circuit-Breakers with Double Breaks
    Liao Minfu
    Duan Xiongying
    Cheng Xian
    Zou Jiyan
    [J]. ISDEIV 2010: XXIVTH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, 2010, : 224 - 227
  • [30] CIRCUIT-BREAKERS PROTECT BETTER
    HIRSCH, H
    [J]. ELEKTROTECHNISCHE ZEITSCHRIFT B-AUSGABE, 1978, 30 (23): : 905 - 914