INVESTIGATION OF HIGH-CURRENT INTERRUPTION OF VACUUM CIRCUIT-BREAKERS

被引:47
|
作者
DULLNI, E [1 ]
SCHADE, E [1 ]
机构
[1] ABB MANAGEMENT LTD,RES CTR,BADEN,SWITZERLAND
来源
关键词
D O I
10.1109/14.231543
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a survey of the physical processes occurring during recovery of a vacuum interrupter after high-current interruption. In the past, new results have been obtained by the application of modern diagnostic techniques like laser shadow imaging, laser-induced fluorescence on atoms and of metal vapor ions, Mie scattering of droplets and high-resolution recording of voltage and current on digital oscilloscopes. The density of metal vapor produced by the arc determines the kind of breakdown processes occurring after current zero. Liquid droplets and residual plasma play a minor role. The commonly used contact material, i.e. copper-chromium, is compared with pure copper and its advantage is explained by the surface structure of the melt.
引用
收藏
页码:607 / 620
页数:14
相关论文
共 50 条
  • [1] High-current interruption in vacuum circuit breakers
    Binnendijk, M
    Merck, WFH
    Smeets, RPP
    Watanabe, K
    Kaneko, E
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1997, 4 (06) : 836 - 840
  • [2] Physics of high-current interruption of vacuum circuit breakers
    Schade, E
    [J]. IEEE TRANSACTIONS ON PLASMA SCIENCE, 2005, 33 (05) : 1564 - 1575
  • [3] PARALLEL INTERRUPTION OF HEAVY DIRECT-CURRENT BY VACUUM CIRCUIT-BREAKERS
    TAMURA, S
    SHIMADA, R
    KITO, Y
    KANAI, Y
    KOIKE, H
    IKEDA, H
    YANABU, S
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1980, 99 (03): : 1119 - 1129
  • [4] High-current interruption in vacuum circuit breakers (vol 4, pg 836, 1997)
    Binnendijk, M
    Merck, WFH
    Smeets, RPP
    Watanabe, K
    Kaneko, E
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1998, 5 (03) : 467 - 467
  • [5] High current interruption in vacuum circuit breakers.
    Binnendijk, M
    Merck, WFH
    Smeets, RPP
    Watanabe, K
    Kaneko, E
    [J]. ISDEIV - XVIITH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM, PROCEEDINGS, VOLS I AND II, 1996, : 281 - 285
  • [6] RESTRIKES IN VACUUM CIRCUIT-BREAKERS WITHIN 9-S AFTER CURRENT INTERRUPTION
    BERNAUER, C
    KNY, E
    RIEDER, W
    [J]. EUROPEAN TRANSACTIONS ON ELECTRICAL POWER ENGINEERING, 1994, 4 (06): : 551 - 555
  • [7] HIGH-CURRENT MOLDED CASE CIRCUIT-BREAKERS SAVE SPACE AND COST
    KIDD, AL
    [J]. ELECTRICAL REVIEW, 1973, 192 (03): : 87 - 91
  • [8] CIRCUIT-BREAKERS - THE MECHANICS OF FAULT INTERRUPTION
    WORSLEY, EG
    [J]. PULP & PAPER-CANADA, 1985, 86 (11) : 56 - 58
  • [9] GENERAL STUDY OF PERFORMANCE OF FAST HIGH-CURRENT - CIRCUIT-BREAKERS THAT OPEN MECHANICALLY
    RIOUX, C
    RIOUXDAM.F
    [J]. REVUE DE PHYSIQUE APPLIQUEE, 1974, 9 (03): : 539 - 549
  • [10] VACUUM CIRCUIT-BREAKERS ON TRIAL
    不详