Design and inelastic behavior of hyperbolic cooling tower

被引:2
|
作者
Hyun-ock Jang
Chang-shik Min
机构
[1] Dongguk Univ.,Dept. of Civil & Environmental Engrg.
关键词
reinforcement design in plate and shell; hyperbolic cooling tower; nonlinear inelastic behavior; finite element analysis;
D O I
10.1007/BF02829106
中图分类号
学科分类号
摘要
A design is performed for the hyperbolic cooling tower (Grand Gulf cooling tower) to check the design strength under a consistent design load; therefore, to verify the adequacy of the design algorithm developed. Based on the equilibrium consideration for the ultimate limit state of reinforcement in tension and cracked concrete in compression, an iterative numerical computational algorithm was developed. The design algorithm is implemented in a finite element analysis computer program developed by Mahmoud and Gupta. The amount of reinforcement is then determined at the center of each element by an elastic finite element analysis with the design ultimate load. Based on ultimate nonlinear analysis performed with the designed reinforcement, the analytically calculated ultimate load exceeded the design ultimate load from 26% to 63% for analyses with tension stiffening parameters of from 5 to 20. Since the effective tension stiffening would vary over the life of the shell due to environmental factors, a degree of uncertainty seems inevitable in calculating the actual failure load by numerical analysis. Even though the ultimate loads are strongly dependent on the tensile properties of concrete, the calculated ultimate loads are higher than the design ultimate loads for the design case. For the case designed, the design algorithm gives a lower bound on the design ultimate load with respect to the lower bound theorem. This shows the adequacy of the design algorithm developed, at least for the shell studied. The presented design algorithm for combined membrane and flexural forces can be evolved as a general design method for reinforced concrete plates and shells, through further studies involving the performance of many more designs and analyses of different shell configurations.
引用
收藏
页码:309 / 318
页数:9
相关论文
共 50 条
  • [21] A comprehensive approach to cooling tower design
    Milosavljevic, N
    Heikkilä, P
    APPLIED THERMAL ENGINEERING, 2001, 21 (09) : 899 - 915
  • [22] Open Cooling Tower Design Considerations
    Peterson, Kent W.
    ASHRAE JOURNAL, 2016, 58 (02) : 50 - 54
  • [23] WIND PRESSURE DISTRIBUTION AROUND A RIBLESS HYPERBOLIC COOLING-TOWER
    SUN, TF
    ZHOU, LM
    JOURNAL OF WIND ENGINEERING AND INDUSTRIAL AERODYNAMICS, 1983, 14 (1-3) : 181 - 192
  • [24] Numerical simulation of mean wind load on large hyperbolic cooling tower
    Bao, Kan-Yuan
    Shen, Guo-Hui
    Sun, Bing-Nan
    Kongqi Donglixue Xuebao/Acta Aerodynamica Sinica, 2009, 27 (06): : 650 - 655
  • [25] Temperature Distribution in the Shell of a Hyperbolic Reinforced Concrete Cooling Tower.
    Tarczynski, Leslaw
    Archiwum Inzynierii Ladowej, 1984, 30 (01): : 147 - 169
  • [26] Vibration analysis of free-fixed hyperbolic cooling tower shells
    Kang, Jae-Hoon
    STRUCTURAL ENGINEERING AND MECHANICS, 2015, 55 (04) : 785 - 799
  • [27] DEFORMATION AND STABILITY OF WIND LOADED HYPERBOLIC COOLING-TOWER SHELLS
    MANG, H
    GALLAGHER, RH
    CEDOLIN, L
    TORZICKY, P
    INGENIEUR ARCHIV, 1978, 47 (06): : 391 - 410
  • [28] The analysis of the destabilizing motion of a hyperbolic cooling tower during demolition blasting
    Jia, Haipeng
    Song, Qianqian
    JOURNAL OF MEASUREMENTS IN ENGINEERING, 2023, 11 (04) : 482 - 495
  • [29] Dynamic optimization of hyperbolic cooling tower shell with ring-stiffeners
    Lu, WD
    Gu, HZ
    NATURAL DRAUGHT COOLING TOWERS, 1996, : 355 - 360
  • [30] Thermal performance and structural behaviour of steel hyperbolic cooling tower with holes
    Song, Guoqing
    Zhi, Xudong
    Li, Zheng
    Fan, Feng
    Jin, Xiaofei
    APPLIED THERMAL ENGINEERING, 2023, 231