Spacer flashover in Gas Insulated Switchgear (GIS) with humid SF6 under different electrical stresses

被引:32
|
作者
Purnomoadi, A. P. [1 ]
Mor, A. Rodrigo [2 ]
Smit, J. J. [2 ]
机构
[1] PLN Res Inst, Transmiss & Distribut R&D, Jakarta, Indonesia
[2] Delft Univ Technol, Elect Sustainable Energy, Delft, Netherlands
关键词
Gas insulated switchgear; Gas insulated substation; GIS; Tropical conditions; Humid insulating gas; Spacer flashover; SF6;
D O I
10.1016/j.ijepes.2019.105559
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Humid insulating gas (SF6) has been observed in a case study of 631 CB-bays of Gas Insulated Switchgear (GIS) operating under tropical conditions. The routine gas quality check in the case study reported that 20% of the non-Circuit Breaker enclosures have humidity above the value recommended by the IEEE and IEC standards. Therefore, an investigation into the flashover characteristics of a spacer in humid SF6 has been initiated in the High Voltage Laboratory of TU Delft, The Netherlands. The setup is a small model resembling the insulation system of a GIS with controlled parameters of humidity content and gas pressure. The electrical stresses in the test are AC, LI+, LI-, and SI with homogeneous, quasi-homogeneous-, and inhomogeneous field configurations. In general, the humidity does not influence the withstand strength of the spacer as long there is no condensation. When condensation occurred, the flashover voltage dropped by 28% during the test under AC at 2.6 bars, and by 38% during the test under LI + at 2.5 bars; both with quasi-homogeneous field configuration. In the test with homogeneous field setup, the flashover voltage was dropped by 67% under LI+ at 3.4 bars. In our setup, it has also been observed that the flashover-drop due to condensation is higher than due to a 2-mm aluminum particle attached to the sample close to the high electric field region simulating the inhomogeneous field configuration.
引用
收藏
页数:9
相关论文
共 50 条
  • [41] 550 KV SF6 GAS-INSULATED SWITCHGEAR FOR THE ITAIPU HYDRO-POWER STATION
    SZENTEVARGA, HP
    BROWN BOVERI REVIEW, 1981, 68 (3-4): : 157 - 159
  • [42] Influence and mechanism of pressure on SF6 decomposition components of gas-insulated switchgear under positive DC partial discharge
    Cao, Zhengqin
    Tang, Ju
    Miao, Yulong
    Zhu, Ning
    Yao, Qiang
    Zeng, Fuping
    IEEJ TRANSACTIONS ON ELECTRICAL AND ELECTRONIC ENGINEERING, 2018, 13 (08) : 1136 - 1141
  • [43] Study on field demonstration of high sensitivity SF6 leakage detection method for gas insulated switchgear
    Tatemi M.
    Inami H.
    Rokunohe T.
    Hirose M.
    IEEJ Transactions on Power and Energy, 2020, 140 (05) : 409 - 414
  • [44] Thermal stability of SF6 associated with metallic conductors incorporated in gas insulated switchgear power substations
    Dervos, C. T.
    Vassiliou, P.
    Mergos, J. A.
    JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2007, 40 (22) : 6942 - 6952
  • [45] Flashover characteristic along the insulator under DC voltage in SF6 gas
    School of Electrical Engineering, Xi'an Jiaotong University, Xi'an 710049, China
    不详
    Gaodianya Jishu, 2009, 8 (1903-1907):
  • [46] Flashover Characteristics along the Insulator in SF6 Gas under DC Voltage
    Jia, Zhijie
    Zhang, Bin
    Tan, Xiaoya
    Zhang, Qiaogen
    2009 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), VOLS 1-7, 2009, : 3409 - 3412
  • [47] ARCING FAULTS IN SF6 INSULATED METAL-CLAD HV SWITCHGEAR
    KRENICKY, A
    SCHMITZ, U
    SONDEREGGER, G
    BROWN BOVERI REVIEW, 1974, 61 (04): : 143 - 151
  • [48] Replacing SF6 in Electrical Gas -Insulated Switchgear: Technological Alternatives and Potential Life Cycle Greenhouse Gas Savings in an EU-28 Perspective
    Billen, Pieter
    Maes, Ben
    Larrain, Macarena
    Braet, Johan
    ENERGIES, 2020, 13 (07)
  • [49] Comparison of CF3CHCl2 Gas with SF6 Gas as an Alternative Substitute for Gas Insulated Switchgear Equipment
    Juliandhy, Tedy
    Haryonol, T.
    Suharyanto
    Perdana, Indra
    2017 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND POWER SYSTEMS (ICHVEPS), 2017, : 198 - 203
  • [50] FACTORS INFLUENCING DIELECTRIC PERFORMANCE OF SF6 INSULATED GIS
    RYAN, HM
    LIGHTLE, D
    MILNE, D
    IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1985, 104 (06): : 1527 - 1535