Spacer flashover in Gas Insulated Switchgear (GIS) with humid SF6 under different electrical stresses

被引:32
|
作者
Purnomoadi, A. P. [1 ]
Mor, A. Rodrigo [2 ]
Smit, J. J. [2 ]
机构
[1] PLN Res Inst, Transmiss & Distribut R&D, Jakarta, Indonesia
[2] Delft Univ Technol, Elect Sustainable Energy, Delft, Netherlands
关键词
Gas insulated switchgear; Gas insulated substation; GIS; Tropical conditions; Humid insulating gas; Spacer flashover; SF6;
D O I
10.1016/j.ijepes.2019.105559
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Humid insulating gas (SF6) has been observed in a case study of 631 CB-bays of Gas Insulated Switchgear (GIS) operating under tropical conditions. The routine gas quality check in the case study reported that 20% of the non-Circuit Breaker enclosures have humidity above the value recommended by the IEEE and IEC standards. Therefore, an investigation into the flashover characteristics of a spacer in humid SF6 has been initiated in the High Voltage Laboratory of TU Delft, The Netherlands. The setup is a small model resembling the insulation system of a GIS with controlled parameters of humidity content and gas pressure. The electrical stresses in the test are AC, LI+, LI-, and SI with homogeneous, quasi-homogeneous-, and inhomogeneous field configurations. In general, the humidity does not influence the withstand strength of the spacer as long there is no condensation. When condensation occurred, the flashover voltage dropped by 28% during the test under AC at 2.6 bars, and by 38% during the test under LI + at 2.5 bars; both with quasi-homogeneous field configuration. In the test with homogeneous field setup, the flashover voltage was dropped by 67% under LI+ at 3.4 bars. In our setup, it has also been observed that the flashover-drop due to condensation is higher than due to a 2-mm aluminum particle attached to the sample close to the high electric field region simulating the inhomogeneous field configuration.
引用
收藏
页数:9
相关论文
共 50 条
  • [21] Performance of Flashover on the Resin Spacer Surface in N2/SF6 and SF6/Air Gas Mixture under AC Power Frequency
    Wang, Cong
    Tu, YouPing
    Li, Xiao
    Tan, Rong
    CONFERENCE RECORD OF THE 2012 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION (ISEI), 2012, : 141 - 144
  • [22] EFFECT OF MOBILE CONDUCTING PARTICLES ON THE ELECTRICAL STRENGTH OF THE INSULATION SYSTEM OF SF6 INSULATED SWITCHGEAR
    LABUSNAWRAT, K
    GRZYBOWSKI, S
    IEEE 1989 ANNUAL REPORT: CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 1989, : 483 - 488
  • [23] Influence of charges on spacer surface flashover in air and SF6
    Rao, BN
    Dwarkanath, K
    Siddagangappa, MC
    CONFERENCE RECORD OF THE 1998 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1998, : 673 - 676
  • [24] Monitoring of SF6 gas admixtures in gas-insulated electrical equipment
    Paul, Th. A.
    Kramer, A.
    PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 493 - 496
  • [25] Analysis for Partial Discharges Behavior in SF6 Gas Filled Void in Gas Insulated Switchgear under Oscillating Switching Impulses
    Zhang C.
    Ren M.
    Zhou J.
    Dong M.
    Que B.
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2019, 34 (14): : 3074 - 3083
  • [27] Lightning impulse breakdown characteristics of SF6 alternative gases for gas-insulated switchgear
    Hoshina, Y
    Sato, M
    Shiiki, M
    Hanai, M
    Kaneko, E
    IEE PROCEEDINGS-SCIENCE MEASUREMENT AND TECHNOLOGY, 2006, 153 (01) : 1 - 6
  • [28] A Linear Capacitive Sensor for ppm Moisture Measurement in SF6 Gas-Insulated Switchgear
    Zargar, Zubair Hassan
    Akram, Kazi Jabed
    Biswal, Gyan Ranjan
    Islam, Tarikul
    IEEE TRANSACTIONS ON INSTRUMENTATION AND MEASUREMENT, 2021, 70
  • [29] The Impact of Partly Liquefied SF6 on the Dielectric Performance of SF6-Insulated Switchgear
    Straumann, Ueli
    Stoller, Patrick C.
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2019, 26 (01) : 137 - 145
  • [30] Gas-insulated switchgear state monitoring based on SF6 decomposition products detection
    Yan, Xianglian
    Song, Gao
    Wang, Chengyu
    Ji, Yansong
    Yang, Ren
    Jian, Yongfeng
    Liu, Hanmei
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2014, 34 (06): : 83 - 88